 ZGF Series

       DC 60kV 120KV 200KV High Voltage Test Equipment DC Hipot Tester


Product introduction:

 

ZGF series DC high voltage Generator tester is a new generation portable DC high voltage tester designed and manufactured according to the new Chinese power industry standard DL/T848.1-2004 "General technical conditions for DC high voltage generators". It is mainly used in the power sector of power sector, industrial and mining, metallurgy, steel and other enterprises to conduct DC withstand voltage test on high-voltage electrical equipment such as zinc oxide surge arresters, power cables, transformers and generators.

 

Function: for DC high voltage test of zinc oxide arresters, power cables, generators, transformers, etc.

 


Product Features :

1. Aluminum alloy carrying box

2. With High Frequency Voltage-multiplying circuit, PWM technology and high power IGBT device

3. Adopts voltage feedback, Higher voltage stability, smaller ripple coefficient.

4. Full range smooth voltage regulation, regulation accuracy≤1%, stability≤1%, voltage current error +/-1.5%±d

5. Raise voltage from zero voltage potentiometer

6. The 75% UDC 1mA function button is convenient for Zinc Oxide Arrester test.

7. Over voltage cylinder uses dialing number set, and the error +/-2%.

8. It’s coated with special insulating materials with good electric performance and water resistance

9. The product conform to DL/T848.1-2004 technology requirement, also passed test of quality inspection

Technical Parameter:

Rated voltage: 60kV/120kV, Rated current: 2mA/3mA/5mA

Power supply: AC220V±10%, 50Hz

Ripple coefficient: ≤3.0%

Voltage measuring accuracy: ±(1.5 %reading±2digit)

Voltage stabilization: stochastic wave, ≤1% when power wave±10%

 

           Specification

 

 

Parameters 

60/260/5120/2120/5120/10200/2200/5200/10300/2300/5
Rated Voltage (kV)6060120120120200200200300300
Rated Current(mA)252510251025
Rated Power (W)1203002406001200400100020006001500
Box Weight (kg)882594.54.55.55.55.5
High voltage cylinder Weight (kg)4568978.39.31111.5
High voltage cylinder Hegiht (mm)44044053553575089097098012501250
Voltage measuring accuracyDigital Meter ±(1.5%reading±2words)
Current measuring accuracyDigital Meter ±(1.5%reading±2words)
Ripple factor≤3%
Voltage stabilityRandom fluctuations, changes ≤1% when power supply±10%
Over Load capacityNo load voltage can be 10% more than rated voltage working 10 mimutes, maximum charging current is 125% the rated current
Power supplySingle phase AC 50HZ 220V±10%
Working wayIntermittently
One time continuous working: 10 minutes
Working environmentTemperature: 0~40℃
Relative Humidity is no more than 85% when room temperature is 25℃(No condensation)
Altitude: below 1500 meters
Structure characterExopy glass steel electrical insulated high voltage cyclinder
Air insulation, no worry of leakage
Operation box characterHigh precision 0.75UDC1mA single touch button (accuracy≤2.0%), most suitable for zinc oxide arrester test
Dialing number set for overvoltage protection
All in an aluminum alloy box, integrated structure, portable

 


What should be paid attention to when using DC high voltage generator?

 

DC high voltage generator is mainly used for DC withstand voltage test of high voltage electrical equipment, such as generators, transformers, power cables, zinc oxide surge arresters and other high voltage electrical equipment. The scope of application covers different industries of power, steel, industrial and mining, and metallurgy. For the testing of high voltage electricity, safety has always been a top priority. ZGF series DC high voltage generators have the advantages of portability and high test accuracy, and have been widely recognized by users. So what issues need attention in the process of using the instrument? As follows :
 
1. The DC high-voltage generator must be used in strict accordance with Article 168 of the "Electrical Safety Regulations". At the same time, before the test power supply enters the equipment, two obvious disconnect points must be installed. The power disconnection points are clearly disconnected.
 
2. Make sure that the grounding wires of the tester control box, voltage doubler and the test object are connected well before the test. The ground wire of the test circuit is grounded strictly in accordance with the equipment manual.
 
3. The discharge of the large-capacitance test sample shall be performed by a 100Ω / V discharge resistance rod. When discharging, pay attention that the discharge rod can not immediately contact the test object, but gradually approach the test object until a certain distance from the air gap begins to free hiss. When there is no sound, you can use the discharge rod to discharge, and finally directly connect the ground wire to discharge.
 
4. During the test, testers should not shake hands with each other or touch the ground with their hands. Otherwise, a slight electric shock will occur. This is because when the DC high voltage is 200 kV and above, the testers wear insulation boots and Outside the safety distance, however, the influence of the high-voltage DC ion space electric field distribution causes different DC potentials on several standing bodies nearby. This phenomenon is more pronounced in dry areas and in winter, but it generally does not cause harm to people due to less energy.
 
5. After the test, be sure to hang the ground wire to the high-voltage output end before removing the high-voltage lead.
 
6. Note that when using the test instrument, you must confirm that there is reliable grounding. Do not hold the high-voltage outgoing cable in your hand. Pay attention to safety.
 
 

 

 

Our Sevice :

 

 

 

 

Signing Contracts And Technical Agreements

Ensure Execution Of Contract And Agreement

Active Communication

Complete After-Sales Service

 

Professional After-Sale Service Team

1 Year Free Warranty, Life-Long Maintenance

Help Troubleshooting Within 24 Hours

Professional R & D Team

 

 

Hot Products

Inductance Adjustable AC Voltage Withstand Resonant Test System for Generators High Voltage Test ...
ZXBXZ Series Resonant Test System for Substation Product introduction This ZXBXZ Series Devices are ...
ZXBXZ Series Resonant Test System for Substation Product introduction This ZXBXZ Series Devices are ...
Resonant test system for CVT This resonant tester is widely used for Capacitive Voltage Transformer ...
High Voltage Resonant Test System Inductance Adjustable AC High Voltage Resonant Test System For ...
ZXBXZ Series Resonant Test System for Substation Product introduction This ZXBXZ Series Devices are ...