Home Companies Wuhan GDZX Power Equipment Co., Ltd

DC 60KV 80KV High Voltage Test Equipment Electronic Control For Water Cooled Generator

Wuhan GDZX Power Equipment Co., Ltd

Contact Us

[China] country

Trade Verify

Address: No.1 Fenghuangyuan Second Road, Jiangxia District, Wuhan City, Hubei Province, China

Contact name:Emma

Inquir Now

Wuhan GDZX Power Equipment Co., Ltd

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

DC 60KV 80KV High Voltage Test Equipment Electronic Control For Water Cooled Generator

Country/Region china
City & Province wuhan hubei
Categories Other Chargers
InquireNow

Product Details

DC 60KV 80KV High Voltage Test Equipment Hipot Test set for Water-cooled Generator

 

 

ZGS series is the equipment of testing DC voltage and DC leakage current of water-cooled generator in the situation of water through, which completely overcome the problems of long blow water time, bottom water hard to dry, easy to cause arcing within the coil. The device is light, simple wiring, and easy to read. Polarization compensation voltage is output directly by the case.

 

Features

 

1. Electronic control and tune, easy to operate.

2. The date of voltage and current are recorded in the panel, reading without conversion.

3. One minute timing and tip function.

4. Perfect over-voltage and over-current protection function inside, also zinc oxide over-voltage protection outside, which ensure safety of generator.

5. Portable design, suitable for on-site testing.

6. Four parts separated: control unit, Intermediate Frequency Transformer, doubler and accessories, all packed with special shockproof aluminum alloy cabinet, easy to move

Parameter:

Output voltage(kV)

DC 0~60/80kV

Output power(W)

5K-16K

Voltage measurement

Digital/Analog double display ±2%(full scale)

Stator Winding Leakage Current measuring

Analog Micro-ammeter display ±2% (full scale)

Protection Device

Over-voltage and over-current protection circuit inside, over-voltage set by number dial switch. Also zinc oxide over-voltage protection outside

Output current(mA)

80~200

Voltage stability

≤2.0% when Power supply Voltage vary within 10%

catchment tube polarization voltage compensation

±2.5V

Voltage stability

≤2.0%

Control cabinet weight ( 60kV/200mA )

35 KG

Cylinder weight ( 60kV/200mA )

10 KG

Intermediate Frequency Transformer ( 60kV/200mA )

24 KG

 

     Model-kV/kVA

 

Item 

50/10050/12060/15060/20080/200
Output Voltage kV5050606080
Output Current mA100120150200200
Output Power W5000600090001200016000
Voltage Measuring error≤1.0% ±1d
Current Measuring error≤1.0% ±1d
Over Voltage setting error≤1.0%
Ripple Coefficient≤3.0%
Voltage stability≤1.0%
Power SupplyAC220VAC380V(3P4W)
Carrying box weight25.0kg25.0 kg25.0kg
Cylinder Weight45.0kg65.0kg70.0kg

 

Hot Products

Product Description This series devices are designed for AC withstand voltage test of substation ...
Inductance Adjustable AC Voltage Withstand Resonant Test System for Generators High Voltage Test ...
ZXBXZ Series Resonant Test System for Substation Product introduction This ZXBXZ Series Devices are ...
ZXBXZ Series Resonant Test System for Substation Product introduction This ZXBXZ Series Devices are ...
Resonant test system for CVT This resonant tester is widely used for Capacitive Voltage Transformer ...
High Voltage Resonant Test System Inductance Adjustable AC High Voltage Resonant Test System For ...