Home Companies Guangdong ALI Testing Equipment Co,.Ltd

3 Pole MCB Perkins Diesel Generator , 404C-22G1 HS , 380 - 415V

Guangdong ALI Testing Equipment Co,.Ltd
Active Member

Contact Us

[China] country

Address: No. 2, Shajiao Sijia Gate, Humen Town, Dongguan City, Guangdong Province, China

Contact name:Kris

Inquir Now

Guangdong ALI Testing Equipment Co,.Ltd

3 Pole MCB Perkins Diesel Generator , 404C-22G1 HS , 380 - 415V

Country/Region china
City & Province dongguan guangdong
Categories Diesel Generators
InquireNow

Product Details

 

1. Standby power:                                  24 kw

2.Engine Make & Model:         Perkins 404C-22G1 HS

3.Alternator Model:                             LL1012N

4.Fuel Tank Capacity:             litres (US gal):45 (11.9)

5.Cooling Method:                        Water Governing

6.Compression Ratio:                           23.3:1

7.Displacement: l (cu.in)                   2.2 (135.2) 

8.Bore/Stroke: mm (in)              84.0 (3.3)/100.0 (3.9)

9.Moment of Inertia: kg m² (lb. in²)   3.20 (10935) 

10.Weights: kg (lb) :                          446 (983)

3 Pole MCB Perkins Diesel Generator , 404C-22G1 HS

 

Output Ratings

Generating Set Model

*                               JPPH30E2

Prime*                     Standby*

380-415V, 50 Hz

*                               30.0 kVA

*                               24.0 kW

220/127V, 60 Hz

*                               *

*                               *

 

  • Refer to ratings definitions on page 4.

            Ratings at 0.8 power factor.

 

Technical Data

Engine Make & Model:

Perkins 404C-22G1 HS

Alternator Model:

LL1012N

Base Frame Type:

Heavy Duty FabriCAT-parts-partsed Steel

Circuit Breaker Type:

3 Pole MCB

Frequency:

50 Hz           60 Hz

Engine Speed: RPM

3000                -

Fuel Tank Capacity: litres (US gal)

45 (11.9)

Fuel Consumption:   P16.5P2  l/hr (US gal/hr)

-                         -

Fuel Consumption:  P18E2      l/hr (US gal/hr)

8.9 (2.4)             -

PH30E2

 

Engine Technical Data

 

Physical Data

 

Manufacturer:                                                      Perkins

Model:                                                           404C-22G1 HS

No. of Cylinders/Alignment:                               4 / In Line

Cycle:                                                                 4 Stroke

Induction:                                                   Naturally Aspirated

Cooling Method:                                          Water Governing

Type:                                                       Mechanical Governing

Class:                                                             ISO 8528 G2

Compression Ratio:                                             23.3:1

Displacement: l (cu.in)                                     2.2 (135.2)

Bore/Stroke: mm (in)                               84.0 (3.3)/100.0 (3.9)

Moment of Inertia: kg m² (lb. in²)                   3.20 (10935)

Engine Electrical System:

-Voltage/Ground:                                           12/Negative

-Battery Charger Amps:                                          55

Weight: kg (lb)

- Dry:                                                               218 (481)

- Wet:                                                              234 (517)

 

Air System                                    50 Hz                                                        60 Hz

 

Air Filter Type:                                                          Replaceable

Element Combustion Air Flow: m³/min (cfm)       

-Standby:                                    2.4 (85)                

-Prime:                                           

- Max. Combustion Air Intake

Restriction: kPa (in H2O)          6.4 (25.7)               

- Radiator Cooling Air Flow: m³/min (cfm)                   71.0 (2507)             

- External Restriction to

Cooling Air Flow: Pa (in H2O)                                       125 (0.5)               

 

Cooling System                            50 Hz                                                       60 Hz

Cooling System Capacity:l (US gal)                               6.8 (1.8)                

- Water Pump Type:                                                    Centrifugal

Heat Rejected to Water & Lube Oil: kW (Btu/min)

-Standby:                                   29.3 (1666)              

-Prime:                                           

- Heat Radiation to Room:kW (Btu/min)        

-Standby:                                     11.9 (677)              

-Prime:                                        

- Radiator Fan Load: kW (hp)        1.2 (1.7)                

Cooling system designed to operate in ambient conditions up to 50°C (122°F).

 

 

Performance                                50 Hz                                                       60 Hz

 

Engine Speed: RPM                       3000                      

- Gross Engine Power: kW (hp)

-Standby:                                  31.9 (43.0)                 

-Prime:                                            

- BMEP: kPa (psi)

-Standby:                             1151.0 (167.0)                -

-Prime:                                             -                          

- Regenerative Power: kW            19.0                       

 

LubriCAT-parts-partsion System

 

Oil Filter Type:                                                  Spin-On, Full Flow

Total Oil Capacity l (US gal):                                    10.6 (2.8)

Oil Pan l (US gal):                                                      8.9 (2.4)

Oil Type:                                                            AP1CH4 15W-40

Cooling Method:                                                         Water

 

Fuel System

 

Fuel Filter Type:                                                    Replaceable

Element Recommended Fuel:                            Class A2 Diesel

Fuel Consumption: l/hr (US gal/hr)

110%              100%               75%                50%

Load               Load               Load               Load

 

PH30E2

 

50 Hz                                  8.9 (2.4)          7.1 (1.9)          5.6 (1.5)

60 Hz                                        -                       -                      -

 

(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)

 

Exhaust System                           50 Hz                                                        60 Hz

 

Silencer Type:                                                               Level 1

Silencer Model & Qty:                         MXC0996 (1) Pressure Drop Across

Silencer System: kPa (in Hg)                                   5.03 (1.485)             

- Silencer Noise Reduction

Level: dB                                                                

- Max. Allowable Back

Pressure: kPa (in. Hg)                                                10.2 (3.0)               

- Exhaust Gas Flow:

m³/min (cfm)       

-Standby:                                    7.6 (268)        

-Prime:                                         

- Exhaust Gas Temperature:  °C (°F)

m³/min (cfm)       

-Standby:                                   475 (887)          

-Prime:               

PH30E2

 

 

Alternator Performance Data

 

 

 

Data Item

50 Hz                                                    

415/240V

400/230V

380/220V

Motor Starting Capability* kVA

62

58

53

Short Circuit Capacity** %

0

0

0

Reactances: Per Unit

Xd X'd X''d

3.480

 

0.090

 

0.044

3.750

 

0.100

 

0.047

4.160

 

0.110

 

0.052

 

Reactances shown are applicable to prime ratings

  • Based on 30% voltage dip. Improved motor starting capability is available with optional Permanent Magnet generator or AREP excitation.

** With optional Permanent Magnet generator or AREP excitation.

 

Alternator Technical Data

 

Physical Data                                                                   Operating Data

Manufacturer:  FG WILSON

Overspeed: RPM       4500

Model:  LL1012N

Voltage Regulation (steady state) (%):  + /- 0.5

No. of Bearings:    1

Wave Form NEMA = TIF:    50

Insulation Class:   H

Wave Form IEC = THF:  2.0%

Winding Pitch Code: 2/3 - 6

Total Harmonic Content LL/LN:   4.0%

Wires: 12

Supression is in line with European Standard

Radio Interference:       EN61000-6

Ingress Protection Rating:        IP23

Radiant Heat: kW (Btu/min)

-50 Hz:     4.2 (239)

-60 Hz:                                           -

Excitation System:      SHUNT

AVR Model: R230

PH30E2

 

Technical Data

 

3 Phase Ratings and Performance at 50 Hz, 3000 RPM

3 Phase Ratings and Performance at 60 Hz,


 

Voltage      Prime Model      Standby Model     Voltage     Prime Model           Standby Model

                                       PH30E2       

 

kVA                 kW

kVA                 kW

kVA                 kW

kVA                  kW

415/240V

-                      -

30.0                24.0

 

 

400/230V

-                      -

30.0                24.0

 

 

380/220V

-                      -

30.0                24.0

 

 

 

 

Definitions

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).


 

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.


 

Standard Reference Conditions

Note: Standard reference conditions 27°C (80°F) Air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

 

 

Weights and Dimensions

 

Weights: kg (lb)                                                             Dimensions: mm (in)

 

 

Net (+ lube oil)

 

439 (968)

 

Length

 

1320 (52.0)

Wet (+ lube oil & coolant)

446 (983)

Width

552 (21.7)

Fuel, lube oil & coolant

484 (1067)

Height

1258 (49.5)

 

 

General Data

 

Documents

 

A full set of operation and maintenance manuals, circuit wiring diagrams, and commissioning/fault finding instruction leaflets.


 

Generating Set Standards

 

The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, VDE 0530, NEMA MG-1.22.

 

FG Wilson is a fully accredited ISO 9001 company.


 

Warranty

 

All equipment carries full manufacturer's warranty. Extended warranty terms available. 

 

Hot Products

Alternator Brand:Original Stamford Alternator Model:UCI274C Prime Power:80KW / 100KVA Frequency:50HZ ...
150kva Volvo Generator Diesel( JP-V120) Volvo Engine: TAD731GE Prime Power: 150KVA/120KW 150kva ...
Standby power:200 kW Prime power:182 kW Rated speed:1800 RPM Phase:3 Rated voltage:480 V 6 Cylinder ...
Model:TAD940GE Cylinder Arrangement:6 in line Air Intake System:Turbo Rated Power:240KW 240KW Single ...
Genset Model:JP-V250 Genset Output Power:250KW Rated Voltage:380/220V Frequency:50hz 4 stroke Volvo ...
​ 400KW IP21 Volvo Diesel Generator , Turbo Charged Generator Brand:VOLVO Genset Model:JP-V400 ...