1. High quality and competitive price.

2. lastest stype and china OEM

3. Standby power:  120.0 kW

4.Engine Make & Model:Perkins 1006TAG

5.Alternator Model:LL3014F

6.Base Frame Type:Heavy Duty FabriCAT-parts-partsed Steel

7.Circuit Breaker Type:3 Pole MCCB

8.Fuel Tank Capacity: litres (US gal) 290 (76.6)

9.Type:                           Electronic Governing 

10.Class:                          ISO 8528 G2

11.Compression Ratio:            17.0:1

12.Displacement: l (cu.in)    6.0 (365.5) 

13.Bore/Stroke: mm (in)        100.0 

 

150 kVA Perkins Diesel Generator , JPP150E , 3 Pole MCCB

 

Output Ratings

Generating Set Model

*    JPP150E Prime*                     Standby*

380-415V, 50 Hz

135.0 kVA                150.0 kVA

108.0 kW                 120.0 kW

480V, 60 Hz

150.0 kVA                165.0 kVA

120.0 kW                 132.0 kW

  • Refer to ratings definitions on page 4.

            Ratings at 0.8 power factor.


 

Technical Data

Engine Make & Model:

Perkins 1006TAG

Alternator Model:

LL3014F

Base Frame Type:

Heavy Duty FabriCAT-parts-partsed Steel

Circuit Breaker Type:

3 Pole MCCB

Frequency:

50 Hz           60 Hz

Engine Speed: RPM

1500                1800

Fuel Tank Capacity: litres (US gal)

290 (76.6)

Fuel Consumption:   P135      l/hr (US gal/hr)

31.2 (8.2)        38.2 (10.1)

Fuel Consumption:  P150E       l/hr (US gal/hr)

34.4 (9.1)        41.5 (11.0)

P135 / P150E

 

Engine Technical Data

 

Physical Data                                                                 Air System                                   50 Hz           60 Hz

 

Manufacturer:                                                      Perkins

Model:                                                                1006TAG

No. of Cylinders/Alignment:                            6 / In Line

Cycle:                                                                 4 Stroke

Induction:   Turbocharged Air To Air Charge Cooled

Cooling Method:                               Water Governing

Type:                                                           Electronic Governing

Class:                                                           ISO 8528 G2

Compression Ratio:                                       17.0:1

Displacement: l (cu.in)                                     6.0 (365.5)

Bore/Stroke: mm (in)                       100.0 (3.9)/127.0 (5.0)

Moment of Inertia: kg m² (lb. in²)            1.61 (5502)

Engine Electrical System:

-Voltage/Ground:                                         12/Negative

-Battery Charger Amps:                                   55

Weight: kg (lb) - Dry:                                 586 (1292)

- Wet:                                                           630 (1389)

 

Air Filter Type:                                           Replaceable Element Combustion Air Flow:

m³/min (cfm)        -Standby:           9.8 (346)         13.2 (466)

-Prime:                                              9.2 (325)         12.7 (448)

Max. Combustion Air Intake

Restriction: kPa (in H2O)               5.0 (20.1)         5.0 (20.1)

Radiator Cooling Air Flow:

m³/min (cfm)                               192.0 (6780)   244.0 (8617)

External Restriction to

Cooling Air Flow: Pa (in H2O)         125 (0.5)          125 (0.5)

 

Cooling System                50 Hz           60 Hz

 

 

Cooling System Capacity:

 

l (US gal)                37.2 (9.8)         37.2 (9.8)

Water Pump Type:                                                Centrifugal

Heat Rejected to Water & Lube Oil: kW (Btu/min)

-Standby:             72.9 (4146)      82.5 (4692)

-Prime:                 66.4 (3776)      70.1 (3987)

Heat Radiation to Room:

kW (Btu/min)        -Standby:       39.1 (2224)      50.9 (2895)

-Prime:                                          25.3 (1439)      31.2 (1774)

Radiator Fan Load: kW (hp)              4.5 (6.0)       8.0 (10.7)

Cooling system designed to operate in ambient conditions up to 50°C (122°F).

 

 

Performance                          50 Hz         60 Hz

 

 

Engine Speed: RPM                                 1500                    1800

Gross Engine Power: kW (hp)

 

-Standby:        145.8 (196.0)      163.5 (219.0)

-Prime:         134.6 (181.0)      150.0 (201.0)

BMEP: kPa (psi)

-Standby:       1949.0 (282.7)    1822.0 (264.2)

-Prime:        1800.0 (261.0)    1671.0 (242.3) Regenerative Power: kW             

                                12.6                    16.2

 

LubriCAT-parts-partsion System

 

 

Oil Filter Type:                                            Spin-On, Full Flow Total Oil Capacity l (US gal):                             19.0 (5.0)

Oil Pan l (US gal):                                              16.0 (4.2)

Oil Type:                                                      AP1CD 15W-40

Cooling Method:                                                    Water

 

Fuel System

 

 

Fuel Filter Type:                     Replaceable Element Recommended

Fuel:                                            Class A2 Diesel

Fuel Consumption: l/hr (US gal/hr)

 

110%              100%               75%                50% Load               Load               Load               Load

P135

 

50 Hz           34.4 (9.1)        31.2 (8.2)        24.2 (6.4)        17.4 (4.6)

60 Hz         41.5 (11.0)      38.2 (10.1)       30.0 (7.9)        21.7 (5.7)

 

P150E

 

50 Hz             34.4 (9.1)        26.5 (7.0)        18.9 (5.0)

60 Hz           41.5 (11.0)       32.5 (8.6)        23.4 (6.2)

 

(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)

 

Exhaust System                             50 Hz           60 Hz

 

Silencer Type:                                                       Level 1

Silencer Model & Qty:                                        SD100 (1) Pressure Drop Across

Silencer System: kPa (in Hg)          4.00 (1.181)     4.00 (1.181)

Silencer Noise Reduction

Level: dB                                                     12                    12

Max. Allowable Back

Pressure: kPa (in. Hg)                            6.0 (1.8)           6.0 (1.8) Exhaust Gas Flow:

m³/min (cfm)        -Standby:              28.2 (996)       36.3 (1282)

-Prime:                                                 26.2 (925)       34.5 (1218)

Exhaust Gas Temperature:  °C (°F)

m³/min (cfm)        -Standby:              570 (1059)        522 (971)

-Prime:                                                 560 (1039)        514 (957)

 

P135 / P150E

 

Alternator Performance Data

 

 

 

Data Item

50 Hz                                                            60 Hz

415/240V

400/230V

230/115V

200/115V

380/220V

220/110V

220/127V

480/277V

240/139V

380/220V

220/110V

240/120V

208/120V

230/115V

440/254V

220/127V

 

 

Motor Starting Capability* kVA

 

 

329

 

 

309

 

 

283

 

 

362

 

 

360

 

 

241

 

 

 

283

 

 

264

 

 

311

 

 

Short Circuit Capacity** %

 

 

 

300

 

 

 

300

 

 

 

300

 

 

 

300

 

 

 

300

 

 

 

300

 

 

 

300

 

 

 

300

 

 

 

300

 

 

Reactances: Per Unit

 

 

Xd X'd X''d

 

 

 

 

 

 

2.640

 

0.090

 

0.055

 

 

 

 

 

 

2.850

 

0.100

 

0.059

 

 

 

 

 

 

3.150

 

0.110

 

0.065

 

 

 

 

 

 

2.180

 

0.080

 

0.045

 

 

 

 

 

 

2.640

 

0.090

 

0.055

 

 

 

 

 

 

4.200

 

0.150

 

0.087

 

 

 

 

 

 

3.510

 

0.120

 

0.073

 

 

 

 

 

 

3.790

 

0.130

 

0.079

 

 

 

 

 

 

3.140

 

0.110

 

0.065

 

Reactances shown are applicable to prime ratings

  • Based on 30% voltage dip. Improved motor starting capability is available with optional Permanent Magnet generator or AREP excitation.

        ** With optional Permanent Magnet generator or AREP excitation.

 

Alternator Technical Data

 

Physical Data                                                                   Operating Data

 

Manufacturer:                                                   FG WILSON

 

Overspeed: RPM                                                     2250

 

Model:                                                                  LL3014F

 

Voltage Regulation (steady state) (%):                   + /- 0.5

 

No. of Bearings:                                                       1

 

Wave Form NEMA = TIF:                                         50

 

Insulation Class:                                                      H

 

Wave Form IEC = THF:                                         2.0%

 

Winding Pitch Code:                                           2/3 - 6

 

Total Harmonic Content LL/LN:                         4.0%

 

Wires:                                                                       12

Supression is in line with European Standard

Radio Interference:       EN61000-6

 

Ingress Protection Rating:                                        IP23

 

Radiant Heat: kW (Btu/min)

 

 

-50 Hz:                                   10.0 (569)

 

-60 Hz:                                   10.5 (597)

 

Excitation System:                                                 SHUNT

 

AVR Model:                                                             R230

P135 / P150E

 

Technical Data

 

3 Phase Ratings and Performance at 50 Hz, 1500 RPM

3 Phase Ratings and Performance at 60 Hz, 1800 RPM

 

 

 

Voltage         Prime Model                Standby Model          Voltage          Prime Model                Standby Model

P135                           P150E                                         P135                           P150E

 

kVA                 kW

kVA                 kW

 

kVA                 kW

kVA                  kW

415/240V

135.0              108.0

150.0              120.0

480/277V

150.0              120.0

165.0              132.0

400/230V

135.0              108.0

150.0              120.0

220/127V

150.0              120.0

165.0              132.0

380/220V

135.0              108.0

150.0              120.0

380/220V

150.0              120.0

165.0              132.0

230/115V

135.0              108.0

150.0              120.0

240/120V

150.0              120.0

165.0              132.0

220/127V

125.0              100.0

138.0              110.4

230/115V

150.0              120.0

165.0              132.0

220/110V

135.0              108.0

150.0              120.0

440/254V

150.0              120.0

165.0              132.0

200/115V

135.0              108.0

150.0              120.0

220/110V

150.0              120.0

165.0              132.0

 

 

 

208/120V

150.0              120.0

165.0              132.0

 

 

 

230/115V

150.0              120.0

165.0              132.0

 

 

Definitions

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

 

Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.


Standard Reference Conditions

Note: Standard reference conditions 27°C (80°F) Air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

 


 

Weights and Dimensions

 

Weights: kg (lb)                                                             Dimensions: mm (in)

 

 

Net (+ lube oil)

 

1460 (3219)

 

Length

 

2675 (105.3)

Wet (+ lube oil & coolant)

1480 (3263)

Width

900 (35.4)

Fuel, lube oil & coolant

1725 (3803)

Height

1460 (57.5)

 

 

General Data

 

Documents

A full set of operation and maintenance manuals, circuit wiring diagrams, and commissioning/fault finding instruction leaflets.


 

Generating Set Standards

The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, VDE 0530, NEMA MG-1.22.

 

Warranty

All equipment carries full manufacturer's

Hot Products

Alternator Brand:Original Stamford Alternator Model:UCI274C Prime Power:80KW / 100KVA Frequency:50HZ ...
150kva Volvo Generator Diesel( JP-V120) Volvo Engine: TAD731GE Prime Power: 150KVA/120KW 150kva ...
Standby power:200 kW Prime power:182 kW Rated speed:1800 RPM Phase:3 Rated voltage:480 V 6 Cylinder ...
Model:TAD940GE Cylinder Arrangement:6 in line Air Intake System:Turbo Rated Power:240KW 240KW Single ...
Genset Model:JP-V250 Genset Output Power:250KW Rated Voltage:380/220V Frequency:50hz 4 stroke Volvo ...
​ 400KW IP21 Volvo Diesel Generator , Turbo Charged Generator Brand:VOLVO Genset Model:JP-V400 ...