Home Companies Flo-Instruments Co., Ltd

SE509 Separate Ultrasonic Energy Meter For Easy To Set Up

Flo-Instruments Co., Ltd

Contact Us

[China] country

Trade Verify

Address: 2F, Rongxing Building,No.1007 Banxuegang Avenue, Bantian Street, Longgang District, Shenzhen, 518129 Guangdong, China.

Contact name:

Inquir Now

Flo-Instruments Co., Ltd

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

SE509 Separate Ultrasonic Energy Meter For Easy To Set Up

Country/Region china
City & Province shenzhen guangdong
Categories Testing Equipment
InquireNow

Product Details

SE509 Ultrasonic Energy Meter

Clamp-on simple type ultrasonic energy meter.

 

Introduction

SE509-PT1000 ultrasonic energy meter, which is used for measuring individual energy consumption in any liquid heating/cooling systems. The meter is supplied complete with flowmeter and temperature sensor, which can makes the system real-time detect the temperature of supply and return pipe.

The temperature sensor is to use conversion element characteristics of electromagnetic parameters change with temperature, the temperature and temperature related parameters for testing device.The resistancechange of the temperature change can be converted to known as thermal resistance sensors.

SE509-PT1000 Meter provides highly accurate thermal energy measurement in chilled water,hot water and condenser water systems based on
signal inputs from two temperature sensors and ultrasonic flow meters.

 

Main Features

Flo-Instruments SE509 ultrasonic flowmeter offers high-accurate, repeatable and stable flow measurement for liquids. It is made of strong metal case. Combined the outstanding performance transducer with high industrial grade material, it's ideal for pipes size from 1''(25mm) up to 80''(2000mm) in diameter. IP68 transducers that are easy to install requires this pipe not to be cut, thus reducing installation and labor costs. Clear and obvious interface makes it very convenient to operate.

 

Working Principle

Introduction to TVT

TVT(Transit-Time Vortex) technology represents a cutting-edge approach to ultrasonic flow measurement, combining the principles of transit-time ultrasonics with the capability to harness the vortex shedding phenomenon, delivering unparalleled accuracy and versatility in ultrasonic flow meters. This innovative integration technology enhances the accuracy, versatility, and performance of ultrasonic flow meters, making them well-suited for a wide range of applications across various industries and is a valuable solution for industries requiring precise flow measurements in varying flow conditions.

  • Enhanced Accuracy in Turbulent Flows:

TVT technology excels in applications where fluid flow conditions vary between laminar and turbulent. The incorporation of vortex shedding data enhances accuracy in challenging flow environments.

  • Versatility in Fluid Types:

TVT technology is versatile and suitable for a wide range of fluid types, including liquids with varying viscosities and densities.

 

 

Specifications

Performance Index
Flow Range0m/s ~ 12m/s(0ft/s ~ 40ft/s)
AccuracyValued ±1.0%
Repeatability2.0%

Pipe Diameter

Range(Optional)

DN25~DN2000 (1’’ ~ 80’’)
Measuring Mediumwater, sea water, oil,alcohol...
Pipe Material(Optional)PVC, stainless steel, carbon steel, copper...
Function Index
Communication InterfaceModBus RS485, 4~20mA, Maximum load: 750Ω, OCT upper and lower limit alarm
Power Supply24V DC
Keyboard4 touch keys
Display2.2" TFT LCD 320*240
TemperatureTransmitter ambient temperature: -40℉~140℉(-40℃~60℃)
Transducer measurement medium: -40℉~176℉(-40℃~80℃)
PT1000 Temp. Sensor: 35.6℉~221℉(2℃~105℃)
HumidityRH 0~95% RH,non-condensing
IPIP54
Flow UnitSupport metric unit selection,Cubic Meters(m3), Liters(l),USA Gallons(gal).
/hour, /min, The factory default unit is m3 per hour.
Energy UnitGiga Joule (GJ), Kilocalorie (Kc), KWh, BTU
Physical Characteristics
TransmitterAluminum alloy
SensorClamp-on
CableStandard length: 10m
 
 
PT1000 Reference Table
Temperature0123456789
()Resistance value (Ω)
01000.01003.91007.81011.71015.61019.51023.41027.31031.21035.1
101039.01042.91046.81050.71054.61058.51062.41066.31070.21074.0
201077.91081.81085.71089.61093.51097.31101.21105.11109.01112.8
301116.71120.61124.51128.31132.21136.11139.91143.81117.71151.5
401155.41159.31163.11167.01170.81174.71178.51182.41186.21190.1
501194.01197.81201.61205.51209.31213.21217.01220.91224.71228.6
601232.41236.21240.11243.91247.71251.61255.41259.21263.11226.9
701270.71274.51278.41282.21286.01280.81293.71297.51301.31305.1
801308.91302.71316.61320.41324.21320.81331.81335.61339.41343.2
901347.01350.81354.61358.41362.21366.01369.81373.61377.41381.2
1001385.01388.81392.61396.41400.21403.91407.71411.51415.31419.1

 

 

Hot Products

SE603 Separate Ultrasonic Energy Flowmeter Clamp-on simple type ultrasonic flow meters. Introduction ...
SE603 Separate Ultrasonic Energy Flowmeter Clamp-on simple type ultrasonic flow meters. Introduction ...
SE509 Ultrasonic Energy Meter Clamp-on simple type ultrasonic flow meters. Introduction SE509-PT1000 ...
SE509 Ultrasonic Energy Meter Clamp-on simple type ultrasonic energy meter. Introduction SE509...
SE509 Ultrasonic Energy Meter Clamp-on simple type ultrasonic energy meter. Introduction SE509...
SE509 Ultrasonic Energy Meter Clamp-on simple type ultrasonic energy meter. Introduction SE509...