48V 100A Battery Discharge Capacity Tester

Hebei Kaixiang Electrical Technology Co., Ltd
Active Member

Contact Us

Address: No68 Jianshe Street,Shijiazhuang,Hebei,China

Phone: 86-311-86125326

Contact name:Bruce Pan

Inquir Now

Hebei Kaixiang Electrical Technology Co., Ltd

48V 100A Battery Discharge Capacity Tester

City & Province Shijiazhuang Hebei
Categories Polishers
InquireNow

Product Details

48V 100A Battery Discharge Capacity Tester is designed for deep discharge maintenance and capacity test of storage batteries.Simple to operation, easy to move, it can be applied to various of power plants, communication base stations, substations, battery manufacturers. It suit for storage battery with different models and specifications. After setting theparameter, it can automatic constant current control the capacity test of battery.It is of high power density, no naked light, safe and long life.

Main functions and features

1.Display mode:LED digital meter display voltage,current,capacity,discharge time.

2.Control mode:Keyboard setting the whole group battery protection voltage,discharge current,discharge capacity,discharge time.

3.Control precision:Itadopts imported high power FETMOS tube and IGBT module for control segment, with high control accuracy. It adopts Japan Hall sensor for current sampling with high measuring precision.

4.Autostop function:It will autostop under any of following reach the setting value: discharge time,capacity,protection voltage.

5.Protection function:When internal overheat,positive and negative is reverse,connection wire of the battery group is disconnected, it will unload and give a alarm.

6.Power consumption components:it adopts special alloy resistor, produce with patent technology, high power density, no naked flight, safe and reliable, long service live.

7.Integrated design:it adopts integrated design for the control circuit and power consumption components, with compact size, convenient to carry and it adopts forced air cooling.

8.Memory function:It can reserve parameter setting of last time automatically.


Technical parameter

48V 100A Battery Discharge Capacity Tester

Model

DC48-100

Nominal voltage

DC48V

Discharge voltage

It can discharge during 12V to 60V and 48V±5% guarantee the highest current 100A, can discharge for long time, changing according to Ohm's Law.

Protection voltage

1-60V

Discharge current

1-100A

Discharge time

1minute-99hours59minutes

Discharge capacity

1-9999Ah

Precision

Current 0.1A,Voltage 0.1V

Constant-current Discharge Control precision

±(0.3%+0.2A)

Working power supply

AC single phase 220V±10%,50Hz

Cooling

Forced air cooling

Ambient temperature

-10- +40

Dimension(mm)

About 426×505×172mm(Width*Deep*Height)

Weight(kg)

About 15kg

Hot Products

Main features 1. Multiple control mode:(1) manual panel control (2) remote control (3)software ...
~Compact and Lightweight design that is ideal for moving from job site to job site or within your ...
~Compact and Lightweight design that is ideal for moving from job site to job site or within your ...
~Compact and Lightweight design that is ideal for moving from job site to job site or within your ...
Main Specification Rated Load Voltage: 380VAC, 3 phase4 wire, 50HZ or 60HZ Power Factor: 1 Rated ...
~Main Specification Rated Load Voltage: 380VAC, 50HZ Power Factor: 1 Rated Load Power: 1000KW Max ...