Home Companies Ningbo Tianan (Group) Co.,Ltd.

FR3 Vegetable / Mineral Oil Immersed Transformer Manufacturer 3 Phases220KV 20 ~ 400MVA

Ningbo Tianan (Group) Co.,Ltd.

Contact Us

[China] country

Trade Verify

Address: 3/F, Building B7 , 999 Yangfan Road,High-tech Zone, Ningbo, China 315040

Contact name:Lian Huanhuan

Inquir Now

Ningbo Tianan (Group) Co.,Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

FR3 Vegetable / Mineral Oil Immersed Transformer Manufacturer 3 Phases220KV 20 ~ 400MVA

Country/Region china
City & Province ningbo zhejiang
InquireNow

Product Details

220KV 20 ~ 400MVA Oil Immersed Transformer Manufacturer 3 Phases

 

220kV-252kV Power Transformer
NINGBO TIANAN (GROUP) CO., LTD.
1. Product standards
>> GB1094.1 ~ 2-1996.
>> GB1094.3, 5-1985.
>> GB/T6451-1995.
>> IEC60076.
2. Low loss
- Optimization of electromagnetic calculations, using combined technology of electrical shielding
and magnetic circuit, effectively controlled leakage, so as to reduce the load loss and to avoid
partial overheating.
- Use high quality cold-rolled lattice orientation high permeability silicon steel, to reduce the load loss,
no-load current.
- Core all-helical stacking with STEP joints, and advanced stacking process, reduced the load loss, load
current and electromagnetic noise.
3. Low partial discharge
To ensure the safe and steady operation of the transformer under continuous rated voltage, our Electric Power Research Institute conducted a lot of research to develop a more reasonable insulation structure, plus the strict technology specifications and technical staff experience, ensured the low partial discharge of our products.
4. High strength
- Adoption of six-side method positioning for the body, meets the transportation requirements of, horizontal acceleration not more than 0.3G, vertical direction not greater than 0.15g.
- Upper and Lower Clamps and the formation of tight fixed side beam frame.
- The tank can withstand the vacuum test and required positive pressure test.
5. Low Noise
- Use of high-quality core silicon steel;
- Core STEP stepping joints;
- Reduction of the flux density, despite of the increase of cost;
- Use low-noise fan as the air cooling equipment;
- Increase the shock absorbing measures;
- Well interior-protection, to avoid direct rigid contact of the body and tank;
6. Maintenance-free
Our company adopts the domestic leading technology, use fully enclosed structure for the transformer tank, ensuring product life of 30 years, and maintenance-free operation.
 
Reference Technical specification:
 
220kV ,31500kVA~180000kVA three-phase, two windings,
on-load voltage regulation power transformer:
 

Rated power
(kVA)

Voltage combination and

tap range

vector groupShort-circuit impendence(%)No-load loss
(kW)
On-load loss(kW)No-load current(%)
HV(kV)LV(kV)
31500220±8×1.25%6.3
6.6
10.5
11
35
37
38.5
YNd1112-14301280.7
40000361490.63
50000431800.56
63000502090.56
9000010.5 11
35
37
38.5
642740.49
120000793290.49
150000933850.42
1800001084450.42
12000066
69
823370.49
150000963940.42
1800001124510.42

 
Three- Phase Three-Winding On-Load Voltage Regulating Auto Power Transformer

Type

Rated capacity

(kVA)

Rated

Voltage

Connection

symbol

Loss

(kW)

No-load current

(%)

Capacity assignment

(%)

Impedance

(%)

HV
(Kv)

HV
(Kv)

HV
(Kv)

No
-load

load
SFSZ11-31500/22031500

220±8
×1.25%

115
121

6.3
6.6
10.5
11
35
37
38.5

Yna
0d11

201030.56100/100/50

High-
middle
8~10
 
High-
low
28~34
 
Middle-
low
18~24

SFSZ11-40000/22040000241250.56
SFSZ11-50000/22050000291490.49
SFSZ11-63000/22063000341800.49
SFSZ11-90000/22090000412350.42
SFSZ11-120000/220120000

10.5
11
35
37
38.5

512930.42
SFSZ11-150000/220150000613470.35
SFSZ11-180000/220180000683980.35
SFSZ11-240000/220240000835130.30

Note: 1. listed data in table is suitable for reduction pressure product.
2. 6.3KV,6.6KV,10.5KV,11KV low voltage product are not be recommended


****For detailed technical specifications, please contact us.
 

 

 

Hot Products

NINGBO TIANAN (GROUP) CO., LTD. SCB -10 Step Down Cast Resin Dry Type Transformer / Electrical ...
20KV Electrical Distribution Step Down Dry Type Electrical Transformers Basic Info. Model NO.: SG (H...
Insulating Non-encapsulated Environmental Cast Resin Dry Type Transformer Overview: Insulating Non...
35KV Transformer Station Resin Insulation Dry - Type Power Transformer Overview SCB series resin ...
35KV Transformer Station Resin Insulation Dry - Type Power Transformer Overview This product adopts ...
6 ~ 35 KV / 30 ~ 2500 KVA Resin Casting Dry Type Distribution Transformer ​ General: As the ...