Home Companies CN Cable Group Co., Ltd.

Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

CN Cable Group Co., Ltd.
Active Member

Contact Us

[China] country

Address: No.80 Dianchang Road,High-Tech Industrial Zone, Zhengzhou,China

Contact name:Andrea

Inquir Now

CN Cable Group Co., Ltd.

Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

Country/Region china
City & Province zhengzhou henan
Categories Power Cables
InquireNow

Product Details

Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

 

APPLICATION
Trailing cable on ac mining equipment where service conditions are severe and maximum safety is mandatory; such as
power shovels and drag lines in open-pit mines, quarries, gantry cranes and slag reclaiming.
Used for high voltage distribution in underground mines where frequent relocation is necessary or where extra
flexibility and toughness is desired.
Meets all requirements of ICEA S-75-381.
CHARACTERISTIC
Excellent flexibility
Highly ozone, sun, weather and flame resistant
Excellent impact and abrasion resistant
Rated and flexible at -500C
Oil and heat resistant

 

 

1. Phase, Grounding Conductors, Ground check conductors: Soft or annealed tinned coated copper
conductor, rope lay flexible stranding per ASTM B172
2. Conductor Shield: A helically applied semiconducting tape.
3. Insulation: High quality, heat, moisture, ozone and thermosetting ethylene propylene rubber (EPR)
meeting ICEA.
4. Insulation Shield: An overlapped semiconducting tape shall be applied over the insulation.
5. Metallic Component: A composite fiber-copper braid shield, tinned coated copper wires, Coverage
minimum 60 ,with colored fibers for phase identification (black, white, red).
6. Assembly: Phase, ground check and grounding conductors cabled together with hygroscopic fillers and a
binder tape.
7. Ground Check: Polypropylene insulation yellow colored for identification.
8. Jacket(CPE): Heavy duty or extra heavy duty chlorinated polyethylene (CPE) compound, applied in one
layer over a fibrous reinforcement layer, Black or other colors can be provided.
8. Jacket(TPU): Extra heavy duty, high torsion resistant, integral-filled, thermoplastic Polyurethane jacket,
Black or other colors can be provided.

 

Technical Data

SHD-GC 2 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductorApproximate overall
diameter
Ampacity
40°Cambient
temperature
SizeStranding
AWG or MCM InchesInchesAWG InchesA
61337x190.0700.15510497x71.2693
42597x370.0700.15581337x191.36122
22597x370.0700.17061337x191.55159
12597x370.0800.17051337x191.71184
1/026619x140.0800.19042597x371.81211
2/034219x180.0800.20532597x391.94243
3/041819x220.0800.20522597x372.07279
4/053219x280.0800.22012597x372.24321
25062719x330.0950.2201/026619x142.44355
30074037x200.0950.2351/026619x142.70395
35088837x240.0950.2352/034219x182.73435
500122137x330.0950.2654/053219x283.10536

 

SHD-GC 5 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductorApproximate overall
diameter
Ampacity
40°Cambient
temperature
SizeStranding
AWG or MCM InchesInchesAWG InchesA
61337x190.1100.18510497x71.5193
42597x370.1100.18581337x191.60122
22597x370.1100.20561337x191.79159
12597x370.1100.20551337x191.88184
1/026619x140.1100.22042597x371.98211
2/034219x180.1100.22032597x372.12243
3/041819x220.1100.23522597x372.26279
4/053219x280.1100.23512597x372.51321
25062719x330.1200.2501/026619x142.57355
35088837x240.1200.2652/034219x182.83435
500122137x330.1200.2804/053219x283.18536

 

SHD-GC 8 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductorApproximate overall
diameter
Ampacity
40°Cambient
temperature
SizeStranding
AWG or MCM InchesInchesAWG InchesA
42597x370.1500.20581337x191.9393
22597x370.1500.22061337x192.02122
12597x370.1500.22051337x192.10159
1/026619x140.1500.22042597x372.21184
2/034219x180.1500.23532597x372.34211
3/041819x220.1500.25022597x374.49243
4/053219x280.1500.25012597x372.63279
25062719x330.1500.2501/026619x142.75321
35088837x240.1500.2802/034219x183.05355
500122137x330.1500.2954/053219x283.39435

 

SHD-GC 15 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductorApproximate overall
diameter
Ampacity
40°Cambient
temperature
SizeStranding
AWG or MCM InchesInchesAWG InchesA
22597x370.2100.23561337x192.31164
12597x370.2100.23551337x192.40187
1/026619x140.2100.25042597x372.52215
2/034219x180.2100.25032597x372.60246
3/041819x220.2100.26522597x372.79283
4/053219x280.2100.26512597x372.90325
250*62719x330.2100.2651/026619x143.05355
350*88837x240.2100.2802/034219x183.31435
500*122137x330.2100.2954/053219x283.72536

 

SHD-GC 25 kV
Selection data
Power
conductor size
Power conductor
stranding
Nominal
thickness of
insulation
Jacket
thickness
Grounding conductorApproximate overall
diameter
Ampacity
40°Cambient
temperature
SizeStranding
AWG or MCM InchesInchesAWG InchesA
22597x370.2950.23561337x192.55178
12597x370.2950.26551337x192.86191
1/026619x140.2950.26542597x372.91218
2/034219x180.2950.28032597x373.06249
3/041819X220.2950.28022597x373.19286
4/053219x280.2950.29512597x373.34327
250*62719x330.2950.2951/026619x143.43360
350*88837x240.2950.2952/034219x183.66435

 

Hot Products

RZ1-K LSZH Cable use for where fire, smoke emission and toxic fumes create a potential threat to ...
plain single or multi copper conductor Halogen free sheathed cable NHMH-J and NHMH-O Application ...
Halogen free sheathed cable with improved fire characteristics NHXMH-J type cable Application These ...
Indoor cables for telecommunication J-YY ... Bd As communication cable for permanent installation. ...
Fire-alarm cable J-YY cable as communication cable for permanent installation making out connection ...
YXZ2V 0.6/1 kV TS IEC 60502-1 N2XRY 0.6/1 kV VDE 0271 Structure 1. Solid or stranded copper ...