AMAXPOWER NEW ENERGY TECH CO., LTD |
|
Amaxpower 2V 3000Ah OPzS Tubular Battery Flooded Lead Acid Battery (2V 3000Ah)
Amaxpower Battery Solar System 2V 3000Ah OPzS Tubular Battery Flooded Lead Acid Battery-Wind-Power-Storage-Solar Power
OPzS Tubular Deep Cycle Solar AGM Batteries and Gel Batteries
2V1000Ah, 1200Ah, 1500Ah,2000Ah,2500Ah,3000Ah most popular
models Advanced Features:
Φ Environmentally friendly Φ Completely Maintenance-Free Φ
Non-Spillable construction design.
Φ Wide Operating Temperature Range(-20°C~+60°C) Φ Longer
Life(20years designed life) Φ Explosion Proof
Φ Valve Regulated & High Discharge Rate Capability Φ Low Self
Discharge Φ Independent of Position
Φ Ease of Shipment Φ No need of balanced charge or boost ΦNo Memory
OPzS series of 2V AGM deep cycle batteries are recognized as the most reliable and high quality battery system in the industry. They are designed with advanced patented GEL technology, Long service life designed with 10-15 years, 50% DOD 1200 Cycles, the batteries comply to the most popular international standards, such as IEC60896-21/22, BS6290-4, Eurobat Guide
Rate Voltage | 2V(Single cell) | |
Nominal Capacity | 3000Ah @10 hour-rate | |
Dimension | Length | 576±1mm (22.68 inches) |
Width | 212±1mm (8.35 inches) | |
Container Height | 772±2mm (30.39 inches) | |
Total Height | 826±2mm (32.52 inches) | |
Weight | Approx. 218kg (480.61lbs) | |
Container Material | ABS | |
Reference Capacity (25°C) | 20hr (157.5A) | 3150Ah |
10hr (300A) | 3000Ah | |
5hr (510A) | 2550Ah | |
1hr (1896A) | 1896Ah | |
Max. Discharge Current | 10000A (5S) | |
Internal Resistance (25°C) | Approx. 0.19mΩ | |
Cycle Use Voltage | Initial Charging Current: Less than 600A Voltage: 2.37-2.4V @ 25°C (77°F) | |
Float Charging Voltage | 2.25-2.3V @ 25°C (77°F) | |
Operating Temperature Range | Discharge | -15~50°C |
Charge | 0~40°C | |
Storage | -15~50°C | |
Nominal Operating Temperature Range | 25°C±3°C (77±5°F) | |
Capacity affected by Temperature (20 hour rate) | 40°C (104°F) | 105% |
25°C (77°F) | 100% | |
0°C (32°F) | 89% | |
-15°C (5°F) | 79% | |
Self-Discharge | Less than 3% at 25°C (77°F) per month |
Telecom, Electric Utilities, Control Equipments, Security Systems, Medical Equipments, UPS systems, Railroad Utilities, Photovoltaic Systems, Renewable Energy System and so on.