Luoyang Sanwu Cable Co., Ltd., |
Verified Suppliers
|
|
Insulated XLPE ABC Aluminum Overhead Aerial Bundle Power Conductor Electrical Cable 0.6/1kv
Characteristics of Overhead Insulated Cable
1)Rated voltage U0/U :0.6/1 KV
2)Max. permissible long-time working temperature : PVC or PE
insulated conductor is not more than 70 ,and that of XLPE
insulation is not more than 90 .
3)Installing temperature should not be below -20 .
4)Admissible bending radius to cable :When overall-diameter (D) is
less than 25 mm , it should be not less than 4D . When overall
diamter(D) is 25mm or more , it should not be less than 6D .
Our overhead insulated cable have formed a system, such as single
core, two-core ,three core and four core. There are conductors of
aluminium , aluminium alloy or aluminium steel-reinforced . We can
manufacture the overhead insulated cable not only in accordance
with China`s standard GB12527-90 but also the other standards and
special requiement by the custormers. If you have any suggestions
or opinions about our products,please leave a message,and we will
immediately answer your questions. Thanks for your support.
(Service drop cable)
1. Stranded aluminium conduct
2. PE or XLPE insulation
3. ACSR, AAAC Messenger wire
Application
It is preferred to use of service drop (ABC cables) instead of
uninsulated conductors at low voltage networks. service drop (ABC
cables)are especially used at areas where the cost of underground
networks is expensive and also for electrification of rural areas
like villages.
If you have any suggestions or opinions about our products,please
leave a message,and we will immediately answer your questions.
Thanks for your support.
Triplex AAAC cable
Code Word | AWG or Kcmil | Neutral AAAC | Phase AAC |
Minex | 2*6 AWG+1*30.58 | 7/1.68 | 1/4.11 |
Hippa | 2*6 AWG+1*30.58 | 7/1.68 | 7/1.56 |
Prawn | 2*4 AWG+1*48.69 | 7/2.12 | 1/5.19 |
Bamacle | 2*4 AWG+1*48.69 | 7/2.12 | 7/1.96 |
Shrimp | 2*2 AWG+1*77.47 | 7/2.67 | 7/2.47 |
Gammarus | 2*1/0 AWG+1*123.3 | 7/3.37 | 7/3.12 |
Leda | 2*1/0 AWG+1*123.3 | 7/3.37 | 19/1.89 |
Triplex ACSR cable
Code Word | AWG or Kcmil | Neutral ACSR | Phase AAC |
Paludina | 2*6 AWG+1*6AWG | 6+1 /1.68 | 1/4.11 |
Voluta | 2*6 AWG+1*6AWG | 6+1 /1.68 | 7/1.56 |
Whelk | 2*4 AWG+1*4AWG | 6+1 /2.12 | 1/5.19 |
Periwinkle | 2*4 AWG+1*4AWG | 6+1 /2.12 | 7/1.96 |
Conch | 2*2 AWG+1*2AWG | 6+1 /2.67 | 7/2.47 |
Neritina | 2*1/0 AWG+1*1/0 AWG | 6+1 /3.37 | 7/3.12 |
Cenia | 2*1/0 AWG+1*1/0 AWG | 6+1 /3.37 | 19/1.89 |
Duplex Service Drop
Code word | AWG or kcmil | Bare Neutral Messenger | Phase conductor | Weight Kg/km | Allowcable Ampacities(A) | |||||||
ACSR | Rated Strength Lbs. | AAC | Insul Thick.mm | XLPE | PE | |||||||
NO. | Dia. mm | NO. | Dia. mm | NO. | Dia.mm | |||||||
Setter Shepherd Eskimo Terrier Chow Bull | 1*6AWG+1*6AWG 1*6AWG+1*6AWG 1*4AWG+1*4AWG 1*4AWG+1*4AWG 1*2AWG+1*2AWG 1*1/0AWG+1*1/0AWG | 1 1 1 1 1 1 | 1.68 1.68 2.12 2.12 2.67 3.37 | 6 6 6 6 6 6 | 1.68 1.68 2.12 2.12 2.67 3.37 | 1190 1190 1860 1860 2850 4380 | 1 7 1 7 7 19 | 4.11 1.56 5.19 1.96 2.47 1.89 | 1.14 1.14 1.14 1.14 1.14 1.52 | 111 113 171 173 266 427 | 85 85 115 115 150 205 | 70 70 90 90 120 160
|