Home Companies Jiangsu Acrel Electrical Manufacturing Co., LTD.

Acrel ADW200-D16-4S multichannel energy meter with ct energy monitor multi channel energy meter for base station

Jiangsu Acrel Electrical Manufacturing Co., LTD.

Contact Us

[China] country

Trade Verify

Address: No. 9 Xincheng Road,Chengjiang Street, Jiangyin City, Jiangsu Province,China

Contact name:Dina Huang

Inquir Now

Jiangsu Acrel Electrical Manufacturing Co., LTD.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Acrel ADW200-D16-4S multichannel energy meter with ct energy monitor multi channel energy meter for base station

Country/Region china
City & Province jiangsu
Categories Used Measuring & Analysing Instruments
InquireNow

Product Details

 

ADW200-D16-4S multichannel energy meter for base station

 

General

    ADW2XX series rail type multi-loop power meters are mainly used for measuring the full electric parameters of  multiple three-phase circuits, up to four three-phase loop current inputs can be connected simultaneously.It Can measure voltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters.

 

 

Technical parameter


 

Auxiliary powerAC/DC 85~265V; Consumption≤10VA;
InputFrequency45~65Hz;
VoltageAC 3×220V/380V; Overload: 1.2 times of rated value (continuous);
2 times of rated value / 1s 
consumption: ≤ 0.5VA;
CurrentAC 5A,100A,400A,600A;(External opening transformer); 
Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s;
consumption: ≤ 0.5VA
Measurement Accuracy

Frequency 0.05Hz,

voltage,current: 0.5 level

active electric energy: level 1,

reactive electric energy: level 2;

2-31st times harmonic accuracy: ± 1%;

FeaturesPulse OutputOutput mode: optocoupler pulse with open collector;
CommunicationRS485,Modbus-RTU; Baud rate 1200~38400;
SwitchingInputDry contact input,Built-in power supply;
 OutputOutput mode: Relay normally open contact output; contact rating: AC 250V/3A DC 30V/3A;
OutlineL*W*H(mm)72*97.7*71.5
Environmentworking temperature-10℃~+45℃
storage temperature-40℃~+70℃
relative humidity95% No condensation
altitude2500m

 

 

 

Dimension


 

 

 

 

 

 

Guide rail installation:


 

 

 

Optional modules


 

 

 

External Module (MTL)
12 External NTC Temp. Measurement
4 Channels Residual Current Measurement

 

 

External Wireless Module(AWT100)
Downlink RS485; Uplink 4G, 2G, NB, Lora, LoraWAN, Ethernet, WiFi, GPS, Profibus

External Module(MK)
12 Channels DI + 4 Channels DO

           

 

 

 

 

Contact us