241122.290 1000W SIL3 OVP Eltek Flatpack S 24V 1000W Rectifier

 

Specifications

 

Model24/ 1000 SIL3 OVP
Part number241122.290
INPUT DATA
Voltage (nominal)230 V AC/ DC
Voltage (full power)185 - 275 V AC/ DC
Voltage (full power, reduced power factor)275 - 305 V AC/ DC
Voltage (reduced power, linear de-rating)85 - 185 V AC/ DC
Frequency (nominal / range)45 - 66 Hz / 0 Hz
Current (maximum)5.9 A RMS
Power Factor> 0.99 at 50% load or more
ProtectionFuse and Shutdown above 305 V AC / 300 V DC and below 85V AC/ DC
OUTPUT DATA
Voltage (default)26.7 V DC
Voltage (adjustable range)21.5 - 28 V DC
Power (maximum) @ nominal input1000 W
Power @ 85 VAC420 W
Current (maximum) @ nominal input41.7 A (@V OUT < 24 VDC)
Current sharing (10 - 100% load)±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load)±0.5%
Dynamic Voltage regulation±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Hold up time>20ms; output voltage > 41 V DC
Ripple< 200 mV peak to peak, 30 MHz bandwidth
ProtectionBlocking OR-ing Diode, Short circuit proof and High temperature protection
Overvoltage protection, SIL3 parameters

Protection level: 30V • PFD = TBS

Proof test interval: 15 years • SFF = TBS

Handles dual component failure

OTHER SPECIFICATIONS
Efficiency @ nominal input92.50 %
Isolation3.0 kVAC - input to output, 1.5 kV AC - input to earth & 0.5 kV DC - output to earth
Alarms: Red LED

Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage

shutdown on output, Fan failure, Low voltage alarm, CAN bus failure

Warnings: Yellow LED

Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of

range, flashing at overvoltage

Normal operation: Green LED
Potential alarm relay (normally open)

Opens on alarms, mains outage and >40% loaded (ensures redundancy in 1+1 system) when

not connected to a controller

Normal (module running): Green LED 'on'
Acoustic noise< 46dBA at nominal input and full load
MTBF (Telcordia SR-332 Issue I method III (a))>300 000 (@ T ambient : 25 °C)
Operating temperature

-40 to +85°C ( -40 to +185°F), humidity 5 - 95% RH non-condensing

Output power de-rates linear from 1000W @ 45°C (113°F) to 400W @ 85°C(185°F)

Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight72 x 41.5 x 210mm (2.83 x 1.63 x 8.27”) / < 1 kg (2 lbs)
DESIGN STANDARDS
Electrical safetyUL 60950-1, EN 60950-1, IEC 61508
MarineDNV-OS-D202, Ch.2 Sec.4 (DNV2.4): Temperature Cl.B, Humidity Cl.B, Vibration Cl.A, EMC Cl.B1) IEC 60945-4th edition
EMC

ETSI EN 300 386 V.1.4.1

EN 61000-6-1 / -2 / -3 / -4 / -5

FCC Part 15 Subpart 109

Environment

ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)

RoHS (2011/ 65/ EU) and WEEE (2002/96/ EC) compliant

1) Class B requires external filter on input (p/ n 241120.930)

 

Overview

 

Compact HE rectifiers for marine, offshore and process industry applications

Applications in these markets demand state of the art, reliable and safe DC power systems. Flatpack S delivers an industry leading power density in its segment, many safety functions, wide operating temperature range and superb reliability in its small 210mm deep housing.

The Flatpack S 24/ 1000 SIL3 OVP is targeted Safety and Automation Systems (SAS) in offshore and process industry requiring SIL rated overvoltage protection on DC output.

Used in the 3U rack with Smartpack S controller, the Flatpack S rectifiers cover 2 to 8kW applications using a minimum of space, less than 18 liters, and low heat dissipation.

 

Features

 

Small

Short

Power Dense, 26 w / Cu In

High Efficiency

Oring Protection On Output

Sil3 Rated Overvoltage Protection On Output

Hot Pluggable

Voltage Keying

 

Application

 

Offshore And Process Industry

Safety And Automation Systems (SAS)

 


3 TIMES 2 RECTIFIERSSYSTEM IN A 3U RACK

SMARTPACK S CONTROLLER

8 RECTIFIERS 3U SYSTEM -BULK OUTPUT

FLATPACKS 24V 1000W EFFICIENCY PLOT

Hot Products

2-port 100M Ethernet Media Converter IEEE 802.3u 100Base-TX and 100Base-FX Features Support 1 100M ...
2-port 100M Industrial Media Converter Management Card Features Support 2 100M copper ports Input ...
2-port 100M Industrial Media Converter Unmanaged Daughter Card Overview The series adopt industrial ...
2-port 100M Unmanaged Industrial Media Converter Features Support 1 100M fiber port, 1 100M copper ...
3-port 100M Transceiver IP40 Optic Unmanaged Industrial Media Converter Features Support 1 100M ...
3 Port Fast Automatic Flow Control Transceiver Ethernet to Fiber Media Converter Features Support 1 ...