Home Companies Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

TFT Display KWh Electrical Power Calibrator 65Hz Shunt Running

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Active Member

Contact Us

[China] country

Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China

Contact name:Andy

Inquir Now

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

TFT Display KWh Electrical Power Calibrator 65Hz Shunt Running

Country/Region china
City & Province beijing beijing
Categories Other Electric Power Tools
InquireNow

Product Details

INTRODUCTION

The Portable Three Phase kWh Meter test equipment is used for grid corporation of measurement and energy test center, management department of power supply bureau, national energy measurement of testing authorities, and also used to test each kind of single/three phase kWh meter of industries and mining enterprises as well as electric meter manufacturers. Meanwhile, the calibrator also can be used as one high precision standard power source.

 

FEATURES

 

  • Able to test basic error, shunt running, start, standard error automatically and manually in single-step of single/three phase, according to relative regulation of kWh meter.
  • Able to do change test caused by voltage influence, frequency influence and harmonic influence.
  • Output of power source is speedy and stable, AC maximum output of each phase can reach 120A in maximum.
  • Voltage, current and phase position of each phase can be adjusted in split-phase, improving the flexibility of power source.
  • Frequency of each impulse input port can reach 40Hz.
  • 7-inch TFT color display touch screen, English menu, simple and convenient operation, commonly used functions and current basic load point can be controlled in one button.
  • Each meter position can provide one standard, dependent RS485 port, and able to perform multi-function test, such as communication test.
  • Impulse port of each meter position, external polarity can be set randomly, able to adapt kWh meter of impulse cascade and common-anode.

 

TECHNICAL PARAMETERS

Accuracy0.05%, 0.1%
Power SupplyOne Phase AC 180-265V, frequency 50/60Hz.
AC Voltage Output 
Range(U1,U2,U3)57.7V, 100V, 220V, 380V
or 69.3V, 120V, 240V, 480V( optional)
Adjustment range(0-120)%RG(1)
Adjustment fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability0.01%/120s
Distortion0.3% (Non-capacitive load)
Output loadeach phase 25VA
Measuring accuracy0.05%RG
AC Current Output 
Range(I1,I2,I3)200mA, 1A, 5A, 20A, 100A
Adjustment range(0-120)%RG
Adjustment fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability<0.01%/120s
Distortion≤0.3% (Non-capacitive load)
Output load45VA
Accuracy0.05%RG
Power Output  
Active power output stability<0.01%RG/120s
Reactive power output stability<0.02%RG/120s
Active power measuring accuracy0.05%RG
Reactive power measuring accuracy0.1%RG
Phase Output  
Output adjustment range0°-359.999°
Output adjustment fineness10, 1, 0.1, 0.01 as optional.
Resolution0.01°
Accuracy0.05°
Power Factor 
Adjustment range-1 ~ 0 ~ 1
Resolution0.0001
Measurement accuracy0. 0005
Frequency Output  
Adjustment range45Hz-65Hz
Output adjustment fineness5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution0.001Hz
Accuracy0.005Hz
Voltage /Current/Harmonic Setting 
Harmonic number2-51times
Harmonic content0-40%
Harmonic phase0-359.99
Harmonic setting accuracy(10%±0.1%)RD(2)
Power Energy Measurement Error 
Active power energy0.05%RG
Reactive power energy0.1%RG
Power Pulse Output  
Power pulse typeactive pulse, reactive pulse
Active power pulse output5V, 10mA
Power Pulse Input 
Energy pulse typesupport active and reactive pulse, the highest frequency power pulse input is 180K.
Mechanical parameters 
Dimensions (W×D×H) (mm)500x600x175
Weight (kg)About 27
 

Hot Products

S120 1200A 1MV/A AND 1MA/A OUTPUT AC CURRENT CLAMP ON CT Description The S120 is a high performance ...
Q125B High Accuracy Current Clamp On Measuring Instrument Description The Q125B is a high performanc...
HQ46 CABLE TYPE 500A MV OUTPUT AC CLAMP ON CURRENT PROBE Description The HQ46 AC Current Probe is ...
HQ15 HIGH-VALUE VOLTAGE OUTPUT AC CURRENT CLAMP SENSOR Description The HQ15 AC Current Probe is ...
FEATURES AND TECHNICAL PARAMETERS Calibrate three phase, single phase, active or reactive meter ...
PROFILE GF312V2 portable three phase multifunction energy meter calibrator is with comfort design, ...