Product Details

Portable Electronics Current Transformer error Test Equipment With Standard IEC60044-1 & IEC61869

 

 

GF1061 Portable Electronics Current Transformer error Test Equipment With Standard IEC60044-1 & IEC61869 is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.

 

 

Injects low test signals into secondary side of the CT

Determines the CT‘s equivalent circuit parameters

Identifies all relevant CT performance parameters

Displays all relevant parameters of the CT and its accuracy at different currents and burdens

Evaluates the CT according to the selected standard

Determines unknown CT nameplate parameters

Demagnetizes the CT after the test

 

Ratio and phase accuracy
Winding resistance
Excitation characteristics (knee points)
Composite error (ALF, ALFi, FS, FSi, Vb)
Burden impedance
Transient CT classes and parameters
(TPS, TPX, TPY and TPZ type CTs)
Transient dimensioning factor (Ktd)
If missing/unknown: CT type, class, ratio, knee point, power factor, nominal burden, operating burden, primary and secondary winding resistance
Remanence and residual magnetism
Immediate good/bad evaluation

 

Features

 

1. Steady and transient state characteristic tests of various types of CT/PT

 

2. The use of advanced power technology, the test knee point reaches up to 50kV

 

3. No external other auxiliary equipment, stand-alone to complete all test items

 

4. CT test, easy to test, all the tests are using the same wire connection except the load test

 

5. It carries with thermal printer, so it can print test results on site Reference Standard IEC 60044, ANSI/ IEEE C57.13, IEC61869, GB 1207-2006, GB 1208-2006

 

6. Parameters such as knee point current and voltage

 

7. Parameters such as 10% error curve, 5% error curve

 

8. With battery, working 7days.

 

9. The device can store 10000 groups of test data which would not be lost if the device is power off.

 

10. The data can be displayed and analyzed after the test, or transferred to PC through USB disk and produce a Word file report

 

11. Portability: weight <4kg, the best light ct analyzer

 

 

 

MAIN FUNCTIONS

 

I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity
4. 5% and 10% error curve4. Ratio error, phase error
5. Accuracy limiting factor (ALF)5. Degauss
6. Degauss6. Calculation of knee point value
7. Ratio error, phase error7. Actual secondary load test (burden test)
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test (burden test)
10. Resistance test 
11. Secondary time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)
16. Instruments security factor(FS)
17. Composite error

PARAMETERS

Electrical parameters
Accuracy0.05%
Power supplyAC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage0-100Vrms
Output current0-5Arms (20A peak-value)
Output power0-400 VA (1500 VApeak)
Automatic frequency variation range0.1-60Hz
Equivalent excitation voltage≤5000V
Accuracy≤0.5%
Secondary winding DC resistance measurementRange0.1-1000Ω
Accuracy≤0.05%
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5%±0.1VA
CT/PT phase error measurementAccuracy±1min (typical) / 3 min (guaranteed)
Resolution0.1min
CT ratio error measurementRange1-50000
Accuracy≤0.05%
PT ratio error measurementRange1-10000
Accuracy≤0.05%
Standards 
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm)280 x 250 x 160
Weight (kg)≤4
Environmental conditions 
Relative humidityRelative humidity 5%-95% not condensing
Operating temperature-10°C to +50°C
Storage temperature-20°C to +70°C
Altitude≤1000m

Photo

Hot Products

LZCG530-10 Protection relay device using 5P20 50/1A Zero Sequence Current Transformer Zero Sequence ...
LZCG530-10 Zero Phase Current Transformer, Ring net cabinet 5P10 Ratio 100A / 1A Zero Sequence ...
LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20 ...
LZCK-55 100/5A outdoor clamp type split core current transformer with voltage sampling function ...
P50 Grey color split core clamp on current transformer with 600/5A The round jaw design on the P50 ...
Outdoors waterproof 1500A medium voltage Φ55 permalloy split core current transformer LZCK series ...