Home Companies Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Portable Smart CT PT Analyzer , Current Transformer Testing Equipments On Feild Testing

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Active Member

Contact Us

[China] country

Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China

Contact name:Andy

Inquir Now

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Portable Smart CT PT Analyzer , Current Transformer Testing Equipments On Feild Testing

Country/Region china
City & Province beijing beijing
Categories Rubber Product Making Machinery Parts
InquireNow

Product Details

GF106 CT/PT TESTER is mainly used for field testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.

FEATURES

  • Steady and transient state characteristic tests of various types of CT/PT
  • The use of advanced power technology, the test knee point reaches up to 40kV
  • No external other auxiliary equipment, stand-alone to complete all test items
  • CT test, easy to test, all the tests are using the same wire connection except the load test
  • It carries with thermal printer, so it can print test results on site
  • Parameters such as knee point current and voltage
  • Parameters such as 10% error curve, 5% error curve
  • The device can store 3000 groups of test data which would not be lost if the device is power off.
  • The data can be displayed and analyzed after the test, or transferred to PC through USB disk and produce a Word file report
  • Portability: weight < 12kg
 

FUNCTION

I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity
4. 5% and 10% error curve4. Ratio error, phases
5. Current Injecting5. Degauss
6. Degauss6. Calculation of knee point value
7. Ratio error, phases7. Actual secondary load (burden), test (burden)
8. Automatic calculation of excitation knee point value8. Resistance test
9. Actual secondary load test (burden) (load test) 
10. Resistance test 
11. Secondary winding time constant (Ts) 
12. Remanence coefficient (Kr) 
13. Transient dimensioning factor (Ktd) 
14. Peak instantaneous error (Er) 
15. Magnetizing inductance (LU) 

PARAMETERS

Electrical parameters
Accuracy0.05%, 0.1%
Power supplyAC 220V±10% or AC 110V±10%, 50/60Hz
Excitation output voltage0-220Vrms
Excitation output current0-5Arms (20A peak-value)
Automatic frequency variation range0.1-60Hz
Equivalent excitation voltage≤5000V
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurementRange0.1-300Ω
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurementAccuracy±4min
Resolution0.01min
CT ratio error measurementRange1-30000
Accuracy≤0.5%
PT ratio error measurementRange1-10000
Accuracy≤0.5%
Standards 
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2/3/4/6
Mechanical parameters 
Overall dimension (L x W x H) (mm)410 x 250 x 300
Weight (kg)≤10
Environmental conditions 
Relative humidity90RH%
Operating temperature-10°C to +40°C
Altitude≤2000m

MAIN FUNCTIONS

The test items mainly include 
SteadyTransient
excitation characteristicsecondary winding time constant (Ts)
transformation ratioremanence coefficient (Kr)
polaritytransient dimensioning factor (Ktd)
ratio errorpeak instantaneous error (Er)
phasesmagnetizing inductance (LU)
5% and 10% error curvesother parameters
resistance 
secondary load 
 

 

 

 

Hot Products

LZZT620-10 resin cast Three phase bushing type Zero Sequence Current Transformer for protection ...
LZZT943-10 resin cast Three phase Zero Sequence Current Transformer for Ring cabinet and inflatable ...
150mm diameter 2000A/1A 5P20 Cast Resin Zero Sequence Current Transformer with IEC 61869-2 LZCK2501 ...
LZCG530-10 Protection relay device using 5P20 50/1A Zero Sequence Current Transformer Zero Sequence ...
LZCG530-10 Zero Phase Current Transformer, Ring net cabinet 5P10 Ratio 100A / 1A Zero Sequence ...
LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20 ...