General description
XA series pump is a back-open type.Driven by an electric motor directly connect with a flexible couplings or belt driven by petrol/diesel engine.The pump used in agriculture,for handling water for irrigation,drainage and sprinking,as well as used in fire protection,city water treatment and so on.

Model Explanation

Capacity (Q)4.5-1080m3/h
Head (H)5 100 m
Max.Pressure1.0MPa(With special designed) - 1.6Mpa
Max.Temperature: -10~105
Rotary Speed1450~2900rpm(50HZ)

Technical data
For example:XA65/20-18502
XA Pump Model
65 The diameter of outlet in mm
20The diameter of impller in cm
18510 multiple of power (motor)
022 stage motor (14500r/min)

Applications
For delivery of water and liquid which have similar physical and chemical properties to water
~Water treatment,boosting pressure
~Circulating,refrigeration,drainage, feeding boliers,cooling towers
~Air conditioning, fire protection, agriculture irrigation ,drainage and springkling

The installation instruction for XA shaft-coupled series

It is important to install and fit pump on the right place.To get pump working in a good condition,please notice the below inforamtion.

1,The steel base of pump installed on reinforced concrete base directly,to relieve imbalance load effectively.

2,Place a rubber piece between reinforced concrete base and ground,to avoid transfering vibration generated by pump to ground.

3,The dimention of reinforced concrete base should be 15~20cm bigger than steel base of pump's on length and width.

4,When install pipeline on where close to inlet and outlet,the pipeline should be fixed on the right place with a device,to avoid pipeline affect pump.

5,A centring adjustment it is need to do ater installation of pump,may some parts of pump will move to wrong place during transportation and installation.Please note below when make the centring adjustment:There is distance of 4-6mm between couplings,the tolerance of end face offset would be within 0.2mm,radial runout would be within 0.2mm,the shaft of pump and the shaft of electrical motor should be kept in the same center line.

Document download

XA PUMP PROCHURE

XA END SUCTION PUMP

Related product recommendations
XA Shaft-coupled Series
XA End-Suction Pump(1005)
XA End-Suction Pump(9017)
XA End-Suction Pump(1007)
XA End-Suction Pump(1033)

Hot Products

Product "Beyond the service conceptCreate a new service" XA End-Suction Pump(9017) General ...
Product "Beyond the service conceptCreate a new service" XA End-Suction Pump(1033) General ...
Product "Beyond the service conceptCreate a new service" XA End-Suction Pump(Red) General descriptio...
Product "Beyond the service conceptCreate a new service" XA End-Suction Pump(1007) General ...
Product "Beyond the service conceptCreate a new service" XA End-Suction Pump(Blue) General ...
Product "Beyond the service conceptCreate a new service" XA End-Suction Pump(1005) General ...