Medium Voltage Power Cables Aerial Bundle Cable 3X70 50mm2 Alu 12 / 20kV Unipolar MT Cable

1.1. MATERIALS AND CONSTRUCTION

1.1.1. General

Only compatible materials that are suitable for the specified service conditions shall be used in the construction of the cables.

1.1.2. Phase Cores

  • Each core of the aerial bundled cable shall be suitable for use in a system operating voltage of 11,000V 50Hz.
  • The conductor shall be made from hard drawn, circular, stranded and compacted plain aluminum conductor as per IEC 60228.
  • The conductor screen shall consist of an extruded layer of semi-conducting compound, applied to each conductor direct, in the same operation as the application of the dielectric and of the core screen. The outer surface of the conductor screen shall be in continuous adherent contact with the inner surface of the dielectric. The screen shall be readily removable from the conductor and it shall have a thickness of at least 0.5mm.
  • The insulation (dielectric) shall consist of an extruded sheath of cross-linked polyethylene (XLPE). The nominal thickness of the dielectric shall conform to Table 2 (the thickness of screening materials shall not be included in the measured dielectric thickness).
  • A dielectric screen consisting of a semi-conducting core screen, bedding tape and metallic screen shall be applied to each core.
  • The core screen shall consist of an extruded layer of semi-conducting compound, applied in intimate contact with the dielectric of each core, in the same operation as the application of the conductor screen and the dielectric. The layer shall be continuous and uniform in quality and shall be removable without causing damage to the dielectric. It shall have a thickness of at least 0.5mm.
  • A semi-conducting bedding tape shall be applied over the semi-conducting core screen.
  • The metallic screen shall consist of annealed copper tape helically applied over the bedding tape. The metallic screen shall be electrically continuous and any joints shall be made in an acceptable, workmanlike manner and so finished that no sharp edges or protrusions remain. The copper tape shall be applied with a minimum overlap of 15%.
  • The metallic screen shall be suitably water blocked.
    • The outer sheath shall be extruded PVC, black and ultra-violet protected for operation in direct sunlight.

 

 

  • Supporting Catenary
    • The supporting catenary shall consist of stranded galvanized steel wires. Galvanizing of the wires shall comply with the requirements of IEC 60888 for class 1.
    • The lay of the wires shall be right-hand (Z) with lay ratio not less than 10 and not more than 14.
    • The covering shall be PVC applied by forced extrusion to provide a smooth outer finish, and shall be ultra-violet protected for operation in direct sunlight.
    • Table 1: Supporting Catenary

      Catenary Size, mm²5070
      Number of Wires77
      Wire Size (diameter), mm3.003.60
      Minimum Tensile Strength of each Wire, kN9.2613.13
      Elongation at break, minimum %3.54
      Thickness of protective coveringNominal, mm1.201.20
      Minimum at any point, mm0.960.96

       ELECTRICAL AND MECHANICAL CHARACTERISTICS

      The aerial bundled cables shall comply with the following table:

      Table 2: Electrical and Mechanical Characteristics

      Conductor size, mm²7095185
      Diameter over conductor, nominal, mm9.3-10.211.616.4
      Thickness of dielectricNominal, mm3.43.43.4
      Minimum at a point, mm2.962.962.96
      Diameter over insulation Nominal, mm16.1-17.021.325.9
      Diameter over semi-conducting core screen Nominal, mm18.1-1923.327.9
      Thickness of copper tape Nominal, mm0.150.150.15
      Thickness of sheathNominal, mm1.81.81.9
      Minimum at a point, mm1.431.431.51
      Catenary size, mm²505070
      Overall diameter of bundle, Nominal, mmBidder to state67.879.2
      Nominal mass, kg/mBidder to state3.254.65
      Resistance, Ω/km0.4430.320.164
      Strands, no.121530

 

 

 


 

 

 

Hot Products

All Aluminium Strand Wire AAC 265mm2 Bare AAC Conductor BS Standard Application: Mainly for Overhead ...
All Aluminium Strand Wire AAC 400mm2 Bare AAC Conductor BS Standard Application: Mainly for Overhead ...
All Aluminium Strand Wire AAC 185mm2 Bare AAC Conductor BS Standard Application: Mainly for Overhead ...
AAC AAAC ACSR Bare Conductor ASTM Standard ACSR Conductor Cable 160 Mm2 IEC 61089 The conductors are ...
Bare Copper Earthing Conductor Câble cuivre nu de 29mm²BS 7884 The bare copper conductor is hard ...
Sheathed Overhead Insulated Cable ABC Aluminum Stranded Wire 3X95 Mm2 Construction of NFC 33-209 ...