Home Companies Shenzhen Qianhai Lensen Technology Co., Ltd

Analog Signal AD DA Converter 6 Channel RTD To RS485 Converter LS-TD4015

Shenzhen Qianhai Lensen Technology Co., Ltd

Contact Us

[China] country

Trade Verify

Address: 701, Yongchang Building, Xicheng Industrial Zone, Xixiang, Bao'an District, Shenzhen, China 518126

Contact name:Sunny

Inquir Now

Shenzhen Qianhai Lensen Technology Co., Ltd

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Analog Signal AD DA Converter 6 Channel RTD To RS485 Converter LS-TD4015

Country/Region china
City & Province shenzhen guangdong
Categories Solar Chargers
InquireNow

Product Details

1. General Introduction

The LS-TD4015 is an industrial grade standard RTD acquisition product that supports PT100, PT1000, Cu50, Cu100, Ge53, BA1, BA2, R5000 and R500 6-channel three-wire RTD inputs. RS485 interface is optoelectronic isolated. AD acquisition part is also modulus optoelectronic isolated. It adopts standard MODBUS RTU protocol. Complaint with industry standards, LS-TD4015 is suitable to use for a variety of industrial applications and automation systems. It is convenient to communicate with the host computer and realize a rapid networking and build your monitoring system.

 

Thermal resistance supports:

 

PT100-200~850℃BA1-200~650℃
PT1000-200~850℃sBA2-200~650℃
CU50-50~150℃R50000~5000Ω
CU100-50~150℃R5000~500Ω
Ge53-50~150℃  

 

2. Parameter

Technique parameterDescription
Power supply9~30V DC
Input rangesPT100,PT1000,Cu50,Cu100,Ge53,BA1,BA2,R5000 and R500
Excitation current250uA
AdvantageEach channel supports independent configuration (6 channels can be set separately)
Input type6 channels 3-wire input
Collect frequencyAD collecting frequency≤10Hz(total rate)
Resolution16 bit
Accuracy class≤ ±0.1%(wiring cable errors not included)
Input impedance20MΩ
InterfaceRS-485
Protocol

Default Modbus-RTU,support 8N1, 8O1, 8E1.

Data format: SCADA software, PLC, compatible with ADAM-4015+.

If you need MODBUS-ASCII or other, please specify when placing order

Baud rate1200bps, 2400bps, 4800bps, 9600bps, 19200bps, 38400bps, 57600bps, 115200bps
DistanceRS485 distance<1000m, can use repeater
StabilityUse high quality chips inside, built-in dual watchdog, reliable and stable operation
Protection levelPower Pin polarity protection, input Pin photoelectric isolation, AD input Pin and communication port ±15KV ESD protection, isolation voltage 2500Vrms, 500DC continuous, lightning protection, surge protection
Power consumption<2000mW
Weight0.3kg
Mounting wayStandard 35mm U-shaped Din rail installation

 

3. Pin Definition

Pin No.Pin nameDescription
1COM4Ch 4 COM port
2RTD4-RTD input ch4-
3RTD4+RTD input ch4+
4COM5Ch 5 COM port
5RTD5-RTD input ch5-
6RTD5+RTD input ch5+
7NCNC
8NCNC
9NCNC
10DATA+RS-485 A
11DATA-RS-485 B
12+VSPower supply +(9~30V)
13GNDPower supply -(ground of power)
14RTD0+RTD input ch0 +
15RTD0-RTD input ch0 -
16COM0Ch0 Com port
17RTD1+RTD input ch1+
18RTD1-RTD input ch1-
19COM1Ch1 Com port
20RTD2+RTD input ch2+
21RTD2-RTD input ch2-
22COM2Ch2 Com port
23RTD3+RTD input ch3+
24RTD3-RTD input ch3-
25COM3Ch3 Com port
26GNDGND
 

 

Hot Products

1W RS232 RS485 Wireless Radio Modem Modbus DTU PLC Communication 1W Wireless Radio Modem 1W RS232 ...
25W VHF Radio Modem 150MHz Audio Radio Marine Wireless Monitoring LS-V25000 25W power output radio ...
2ch Wireless Digital RTU 2DI2DO Modbus I/O Module for Wireless Alarm System diagram Master DI1 ON, ...
Wireless Modbus RTU for Stacker/Reclaimer Remote Control This application is widely used for PLC ...
Wireless Modbus DTU PLC Remote Control Sensors And Pumps Wireless Communication System Use LS-R324 ...
Lora Wireless RTU Remote I/O Mirroring Control 2km Wireless ON-OFF Control Master side 16DI16DO to ...