Sino-NSH Oil Purifier Manufacture Co., Ltd |
Verified Suppliers
|
|
With Single Axle Wheels Degassification 36kW Vacuum Transformer Oil Purifier
36kW 3000L/H Vacuum Transformer Oil Purifier Description:
1. Double-Stage Vacuum Transformer Oil Purifier is a dehydration
and degassing unit with thermal and double-stage vacuum processing.
2. Double-Stage Vacuum Transformer Oil Purifier is mainly used to
improve the properties of insulating oils in electric power
transformer and other oil filed electrical equipment. It can remove
dissolved and free water, dissolved gas and particulate impurities
effectively so as to increase special indexes of insulation oil.
3.Combines vacuum flashing evaporation technology and delaminating
gradual-close filter technology to reach best performance of oil
purification. Meanwhile, by integrating efficient thermal and
double-stage vacuum, the breakdown voltage is highly improved,
which can be increased from 25kV to over 70kV.
4. Maintains an optimized structure and safe controls as as to meet
compresive requirement of transformer manufacturers and service
company.
Other Optional for Transformer Oil/Insulation Oil:
VF series-- Single-Stage Vacuum Transformer oil Filtration machine.
VFD-R series-- Double-Stage Vacuum Black Insulation Oil
Regeneration Machine
Optional Auxiliary Equipment:
1. Oil tester
2. Water content tester
Accuracy: Aw0-1, measure scope: 0-100ppm, Output: one is ppm, the
other is temperature
3.SINO-NSH digital flow meter
Accuracy:1, test range: 300-30000(L/H), application:
water,oil,alcohol,liquid, working pressure: 0-25(Mpa), working
temperature: 0-120(℃)
4. SINO-NSH particle count meter
5. Foam level detector
When there id foam in the tank and foam reahesa certain level, a
singal will be sent to the magnetic valve, the magnetic valve will
automatically shut on. The foam will be removed quickly, after
removing foa, the magnetic valve will shut off.
6. SINO-NSH-PLC with touch screen and data monitor
Pre-set programmable logical control. Touch screen is installed on
the control cabinet and programmed to provide a simplified flow
diagram showing all maior components. All operating controls shall
be located on th eflow diagram, and maior function are controlled
and adjusted by the touch of screen. It allows maximum real-time
feedback of collecting data and value on the screen(function
customizable).
7.SINO-NSH dissolved gas meter
8. SINO-NSH digital dielectic dissipation factor tester
Corollary Equipment-VR Vacuum Pump Set:
SINO-NSH-VR is units create vacuum in transformer and other
equipment with double-stage vacuum system.
Parameter | Value | ||||||
VR-30 | VR-70 | VR-150 | VR-300 | VR-600 | VR-900 | ||
Capacity, liters/hour | 100 | 250 | 500 | 1000 | 2000 | 3000 | |
Total Power, kW | 3 | 3 | 5 | 7 | 8 | 13 | |
Power supply | Fully Customizable | ||||||
Maximum Vacuum Range,Pa | 0.06 | ||||||
Outlet Diameter, mm | 32 | 32 | 40 | 40 | 50 | 65 | |
Dimensions | length, mm | 900 | 550 | 1000 | 1200 | 1500 | 1950 |
width, mm | 800 | 900 | 800 | 800 | 1000 | 1800 | |
height, mm | 1200 | 800 | 1200 | 1200 | 1200 | 1300 | |
Weight(without trailer), kg | 450 | 550 | 600 | 900 | 950 | 1950 |
Double-Stage Vacuum Transformer Oil Purifier Technical Parameters:
Parameters | Value | |||||||
VFD-30 | VFD-50 | VFD-75 | VFD-100 | VFD-150 | VFD-200 | VFD-300 | ||
Capacity, liters/hour | 1800 | 3000 | 4000 | 6000 | 9000 | 12000 | 18000 | |
Heating Power, kW | 24 | 30 | 48 | 60 | 90 | 120 | 150 | |
Total Power, kW | 29 | 36 | 56 | 69 | 100 | 132 | 170 | |
Power supply | Fully Customizable | |||||||
Inlet Diameter, mm | 25 | 32 | 32 | 40 | 40 | 50 | 65 | |
Outlet Diameter, mm | 25 | 32 | 32 | 40 | 40 | 50 | 65 | |
Dimensions (without trailer) | length, mm | 1350 | 1500 | 1550 | 1900 | 2200 | 2400 | 2900 |
width, mm | 1100 | 1200 | 1250 | 1400 | 1500 | 1600 | 1800 | |
height, mm | 1700 | 1750 | 1800 | 1800 | 1850 | 1900 | 2000 | |
Weight(without trailer), kg | 600 | 800 | 900 | 1150 | 1500 | 1700 | 2400 | |
Processed Oil Spec | Water Content, ppm | ≤5 | ||||||
Dielectric Strength, Kv | ≥75 | |||||||
Filtration Fineness, um | ≤5( or 1-5 as needed ) | |||||||
Gas Content, % | ≤0.1 |