GF211 double clamp phase volt-ampere meter is a multi-functional
portable instrument. It can measure not only alternating voltage,
but also alternating current. Its important function is to measure
phase angle between two voltages, between two current or between
voltage and current. The current signal is obtained by the clamp
current transformer without cutting off current wire. It can
discern inductive circuit and capacitive circuit; can directly read
differential protection phase among every unit of CT; can check
connection of transformer; measure three way voltage phase
sequence; can check whether the meter connection is right or not;
can evaluate the running speed of electric kWh meter. It has high
resolution of current, so can be used as a leakage current meter.
It is an ideal choice for electric power bureau, factories, mine,
petroleum -chemistry enterprises, metallurgy factories and so on.
PARAMETERS
Electrical parameters |
---|
Accuracy class | 1%, 2% |
Power supply | Two 9V batteries |
Scale |
---|
Phase | 0-360° |
AC Voltage | 500V |
AC Current | 200mA/2A/10A |
Fundamental error (under standard operating environment) |
---|
Temperature | 23°C±5°C |
Moisture | <65% |
Wave form | Sine wave Distortion ≤1% |
Frequency | 50± 2Hz, 60± 2Hz |
Wire position | Center of clamp |
Phase measurement | Voltage: 100V± 25V Current: 1A±0.2A |
Phase accuracy | 1.0% FS |
Electrical parameters - continued |
---|
Fundamental error (under standard operating environment) - contiued |
---|
Voltage accuracy |
200V | 1.0FS, Resolution: 0.1V |
500V | 1.0FS, Resolution: 1V |
Voltage accuracy |
10A | 2.0FS, Resolution: 10mA |
2A | 2.0FS, Resolution: 1mA |
200mA | 2.0FS, Resolution: 0.1mA |
Input impedance |
---|
When measure voltage | 1MΩ |
Input voltage impedance | >120KΩ when measure phase |
Phase measurement |
---|
Voltage accuracy | 3V-500V |
Current range | 0.01A-10A |
Additional error |
---|
Measure phase angle, the voltage and the current | Less than the fundamental error |
Measure current | The error led by wires away from center of clamps is less than the
fundamental error |
Safety specification |
---|
Resistance to voltage | The meter can resist 1000V (AC sine wave, 50Hz or 60 Hz) for 1
minute between the meter circuit and the meter case; Between input
joint U1 and U2 can resist 500V (AC sine wave, 50Hz or 60 Hz) for 1
minute. |
Insulation resistance | The resistance both between the meter circuit and the meter surface
and between the terminals U1 and U2 is greater than 100MΩ. |
Mechanical parameters |
---|
Dimensions (W×D×H) (mm) | 185×167×35 |
Weight (kg) | 0.5 |
Environmental conditions |
---|
Working temperature | 0°C±40°C |
Humidity | ≤80% |
Accessory |
---|
Double clamp phase volt-ampere meter | 1 piece |
Clamps 10A | 2 pieces |
Clamp wire | 2 pieces |
Voltage wire | 2 pieces |
User's manual | 1 piece |
Accessory - continued |
---|
Certification of quality | 1 piece |
Box | 1 piece |