MODEL | HP9335C Plus 10-30KVA |
10K | 10K-XL | 15K | 15K-XL | 20K | 20K-XL | 30K | 30K-XL |
CAPACITY | 10KVA / 9KW | 15KVA / 13.5KW | 20KVA / 18KW | 30KVA / 27KW |
PHASE | 3 Phase with Neutral |
INPUT |
Voltage Range | Low Line Loss | 110 VAC(Ph-N) ± 3 % at 50% Load ; 176 VAC(Ph-N) ± 3 % at 100% Load |
Low Line Comeback | Low Line Loss Voltage + 10V |
High Line Loss | 300 VAC(Ph-N) ± 3 % |
High Line Comeback | High Line Loss Voltage - 10V |
Phase | Three phase with ground |
Power Factor | ≥ 0.99 at 100% Load |
OUTPUT |
Output voltage | 208/220/230/240VAC(Ph-N) |
AC Voltage Regulation | ± 1% |
Frequency Range (Synchronized Range) | 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
Overload | AC mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec |
Battery mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec |
Current Crest Ratio | 3:1 max |
Harmonic Distortion | ≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load |
Transfer Time | Line←→Battery | 0 ms |
Inverte←→Bypass | 0 ms (When phase lock fails, <4ms interruption occurs from
inverter to bypass) |
Line←→ECO | <10 ms |
EFFICIENCY |
AC mode | > 89% | > 89% | > 89% | > 90% |
Battery Mode | > 86% | > 88% | > 87% | > 89% |
BATTERY |
Standard Model | Type | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah |
Numbers | 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 3 x 20(18-20 adjustable) |
Recharge Time | 9 hours recover to 90% capacity |
Charging Current | 1.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 4.0 A ± 10% (max.) |
Charging Voltage | 273 VDC ± 1% |
Long-run Model | Type | Depending on applications |
Numbers | 18-20 |
Charging Current | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 12.0 A ± 10% (max.) |
Charging Voltage | 273 VDC ± 1% |
PHYSICAL |
Standard Model | Dimension,DxWxH(mm) | 832 X250X894 | 832 X250X1275 |
Long-run Model | Dimension,DxWxH(mm) | 609 X250X768 | 832 X250X828 |
ENVIRONMENT |
Operation Temperature | 0 ~ 40°C (the battery life will down when > 25°C) |
Operation Humidity | <95 % and non-condensing |
Operation Altitude | <1000m |
Acoustic Noise Level | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter |
MANAGEMENT |
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix,
and MAC |
USB | Power management from SNMP manager and web browser |