VICTORY POWER TECHNOLOGY Co.,LTD |
Verified Suppliers
|
|
Silent Deutz Diesel Generator 180KVA with CE / Soncap / Ciq Approval
Basic Info.
Model NO.: 20KVA~180KVA
Cooling Method: Water Cooling
Stroke: Four Stroke
Installation Method: Fixed
Type: Micro-Computer Control Automatic Diesel Generator
Output Type: AC Three Phase
Export Markets: Global
Additional Info.
Trademark: Victory
Packing: Plywood Package
Standard: single phase or three phases, 50Hz/60Hz
Origin: China
HS Code: 85021100
Production Capacity: 500 sets/month
Product Description
Deutz Diesel Silent Generator 20kVA~180kVA with CE/Soncap/CIQ
Approval
General specifications of silent generator:
Modular design
Anti-corrosion powder coated
Insulated with acoustic foam lining
Central lifting ring, exhaust pipe can be removed which is easy for
ransportation
Lockable doors with key
Protective mesh for rotating parts
Exterior emergency stop push button
Thermally insulated engine exhaust system
Doors fitted on each side
Panel observing window
Access to radiator filling or cap
20', 30' or 40' container canopy is optional
Color is optional
Fuel gauge or lube drain valve is optional
Normal or super soundproof canopy is optional
Base frame fuel tank or profile fuel tank is optional
The muffler's fixed position depend on the output power of gen-set
Silent generator set canopy
With special treated steel sheet
StaiVess steel locks
Control panel viewing window for monitoring the status of the
generator set
Good ventilation system and anti-heat radiation struction
Effective anti-vibration devices to ensure the geneartor set run
steadily
Super silent materials inside to ensure the noise lower than 68 dB
7 meters away
Emergency stop button mounted outside
Side lockable door easy for maintenance and installation
Lube oil and cooling water drains piped to exterior of the canopy
Fuel tank built-in with level gauge
1. Rated voltage: 400V/230V, 380V/220V, 240V/120V, 220V/110V
2. Line way: 3 phases & 4 lines
3. Frequency: 50Hz/60Hz
4. Power factor: 0.8 (lagging)
5. Frequency down (%): ≤ 0.5
6. Steady voltage windage (%): ≤ ± 1
7. Instantanous frequency windage (%): (rated power ) +10~ -7
8. Frequency recovering time (s): ≤ 3
9. Instantanous voltage windage (%): +20~ -15
10. Voltage recovering time (S): ≤ 4
11. Wave form distortion (%): ≤ 5
Diesel Genset set model | Frequency (HZ) | Prime Power | Standby Power | Fuel consumption(kg/H) | Engine model | The No. of cylinder | Measurement L X W X H (mm) | Weight(kg) | ||||
KW | KVA | KW | KVA | |||||||||
V24D | 50 | 20 | 25 | 24 | 30 | 4.5 | D226B-3D | 3 | 1650 x 900 x 1400 | 780 | ||
V28D | 50 | 25 | 31 | 28 | 35 | 5.4 | 800 | |||||
V33D | 60 | 30 | 38 | 33 | 41 | 6 | 850 | |||||
V32D | 50 | 28 | 35 | 32 | 40 | 6.7 | TD226B-3D | 3 | 1651 x 900 x 1400 | 780 | ||
V39D | 50 | 36 | 45 | 39 | 49 | 7.6 | 800 | |||||
V46D | 60 | 42 | 53 | 46 | 58 | 7 | 850 | |||||
V45D | 50 | 42 | 53 | 45 | 56 | 8.5 | TD226B-4D | 4 | 1950 x 1000 x 1450 | 950 | ||
V55D | 50 | 50 | 62 | 55 | 69 | 9 | 1020 | |||||
V66D | 60 | 60 | 75 | 66 | 83 | 11 | 1050 | |||||
V59D | 50 | 56 | 70 | 59 | 74 | 13.6 | TD226B-6D | 6 | 2300 x 1000 x 1600 | 1200 | ||
V75D | 50 | 68 | 85 | 75 | 93 | 14.5 | 1300 | |||||
V88D | 50 | 80 | 100 | 88 | 110 | 16 | 1380 | |||||
V99D | 60 | 90 | 113 | 99 | 125 | 17 | 1400 | |||||
V110D | 50 | 100 | 125 | 110 | 137 | 19.2 | TBD226B-6D | 6 | 2300 x 1000 x 1600 | 1560 | ||
V117D | 50 | 106 | 133 | 117 | 146 | 21.4 | 1560 | |||||
V132D | 50/60 | 120 | 150 | 132 | 165 | 25.7 | 1560 |