Zhengzhou Chaotong Electric Technology Co., Ltd |
Industrial Cooling Tower is used for water cooling of thyristor and transistor frequency converters, induction forge heaters, induction high-frequency units. And also for cooling induction melting furnaces and powerful inductors. They have two separate cooling circuits, one of which works in a closed mode of water circulation and serves to take heat from induction equipment using distilled water or antifreeze, and the second to take heat from the first
The main working principles of Industrial Cooling Tower:
Industrial Cooling Tower works with double-stage cooling images. The first is to wind the cooler by the wind, the second is wind and water cooling at the same time. The surface of the cooler was sprayed with water, the water evaporated, the heat left together, then to achieve excellent cooling results. It is characterized by stability and reliability. Installed inspection windows are convenient for the necessary maintenance. Blinds for waterproofing and light protection are equipped. Easy to dismantle and install.
Advantages of a double-circuit Industrial Cooling Tower:
1, Modern heat exchanger units for high-speed removal of large heat fluxes.
2, Energy-saving equipment, save electricity due to 3 modes of operation.
3, They have two separate cooling circuits, one of which works in a closed mode of water circulation and serves to collect heat from induction equipment using distilled water or antifreeze, and the second to take heat from the first circuit using evaporation of process water.
4, Do not consume distilled water (refrigerant), consume very little technical water for evaporation.
5, Shop dust does not get into the cooling circuit with distilled water (refrigerant).
6, In the cooling system of induction equipment there is no deposition of salts and scale.
7, Double-circuit Industrial Cooling Tower has a relatively small size and weight.
8, They are easy to operate, operate automatically without personnel intervention.
9, Do not require additional communications, tanks, foundation.
10, Double-circuit cooling towers convenient for transportation and subsequent installation.
11, When installing indoors, the workshop is heated, and the evaporating water compensates for the lack of moisture in the winter air.
Моdel | LNB-10Т | |
Cooling capacity | Kcal/h | 60000 |
Flow | Main machine(m³/h) | 8 |
Pipe diameter | Waer inlet | DN63 |
Waer outlet | DN63 | |
Waer supplement | DN32 | |
Drain outlet | DN32 | |
Fan | Power of the generator(kw) | 0.55 |
Spray pump | Power(kw) | 0.75
|
Flow(m³/h) | 15 | |
Circulating pump | Power(kw) | 2.2 |
Lift | 28 | |
Flow(m³/h) | 12 | |
Rated voltage (V) | 380V/50HZ | |
Size (L / W / H) | 2300*1000*2250mm | |
Heat exchanger tube | T2 copper tube Φ16×0.6 | |
Weight | 550kg |
Parameter list of all models
Моdel | LNB-6Т | LNB-10Т | LNB-15Т | LNB-20Т | LNB-25Т | LNB-30Т | LNB-40Т | LNB-50Т | |
Cooling capacity | Kcal/h | 36000 | 60000 | 90000 | 120000 | 150000 | 180000 | 240000 | 300000 |
Flow | Main machine (m³/h) | 8 | 8 | 23 | 28 | 28 | 28 | 32 | 32 |
Pipe diameter | Waer inlet | DN63 | DN75 | ||||||
Waer outlet | DN63 | DN75 | |||||||
Waer supplement | DN32 | DN32 | |||||||
Drain outlet | DN32 | DN32 | |||||||
Fan | Power of the generator(kw) | 0.37 | 0.55 | 0.37*2ps | 0.55*2ps | 0.75*2ps | 1.1*2ps | ||
Spray pump | Power(kw) | 0.75 | 0.75 | 1.1
| 1.1 | 1.1 | 1.5 | 1.5 | 1.5 |
Flow(m³/h) | 15 | 15 | 23 | 23 | 23 | 32 | 32 | 32 | |
Circulating pump | Power(kw) | 1.5 | 2.2 | 2.2 | 3 | 4 | 4 | 4 | 5.5 |
Lift | 25 | 28 | 28 | 28 | 32 | 32 | 32 | 32 | |
Flow(m³/h) | 10 | 12 | 12 | 23 | 25 | 25 | 25 | 46 | |
Rated voltage (V) | 380V/50HZ | ||||||||
Size (L / W / H) mm | 2300*1000* 2250mm | 3000*1000*2250mm
| Main machine 2750* 1250* 2250
Donkey machine 1000* 500* 2000 | Main machine 2750* 1250* 2250
Donkey machine 1000* 1000* 2000 | Main machine 2750*1250*2450mm
Donkey machine 1000*500*2000 | ||||
Heat exchanger tube | T2 copper tube Φ16×0.6 | ||||||||
Weight | 530kg | 550kg | 670kg | 700kg | 720kg | 870kg | 920kg | 1100kg |