Product Details

AC400V-600KW Dummy Load Bank In Good Performance And Resistive Inductive

Introduction

AC400V-600KW Dummy Load Bank is designed for AC power maintenance,could be used widely in communication base,power supply,power station etc.This machine is small , light weight digital table display , easy operation , high intelligence, set the parameters of constant current discharge process can be done automatically

Application

AC400V-600KW Dummy Load Bank can be used in a wide variety of applications , such as

Factory testing of engine generator sets,Periodic excercising of stand-by engine generator sets

Ups system testing,Battery system testing , Load optimization in prime power applications

Factory testing of turbines , To reduce wet stacking problems .

Technical specification

Voltage

AC400V(3 phase 4 wire)

Line voltage 400V,Phase voltage 230V

Power0-610KW
Step1KW,2KW,2KW,5KW, 10KW,20KW,20KW,50KW,100kW, 100kW,100kW,200kW
Environment temperature-10℃ - 50℃
CoolingAir cooling
Working power supplyAC380V, 50Hz
 
Main features

Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.

Fan Delivery Protection: insufficient air volume with any fan 2450m³/h, system unload automatically and give an alarm.

Fan Delivery Protection: insufficient air volume with any fan 2450m³/h, system unload automatically and give an alarm.
Overload protection with fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.
Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.
Protection Switch: some protection with switch, when misinformation or in special need, user can close the corresponding protection function temporarily.
Safety Monitor: through indicator lights on main interface, user can monitor system state. When system abnormally stop and protect, software interface prompt the cause immediately.

Overvoltage Protection: the input load voltage is over the safe threshold value, system unload automatically and give an alarm.

Short Circuit Protection and Over Current Protection: when short circuit, fuses in the load bank can insure to unload automatically.

Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Products

Professional Produce 1000kw dummy load bank for testing generator Product Description The system ...
Professional Produce Smart 400kw load bank For Generator Testing Product Description The system ...
Professional Produce 3 Phase AC Variable Resistive 400v 300kw load bank Product Description The ...
Professional Produce Automatic Portable AC 400v 500kw load bank Product Description The system ...
Professional Produce 1000kw resistive load to test generators Product Description The system ...
Professional Produce Anti Corrosion Materials 1250kw dummy load bank Product Description The system ...