For Diesel Generator 400V 1000K Watt AC Load Bank For Generator Testing
 
Product Description

 

The system consists of 1 sets of 1000 kw load bank. The system is made up of two parts of measurement and control and load, mainly including the dry type ac load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, remote control box and PC software and so on.

 

Technical Parameters

 

Rating Voltage/Frequency400VAC/50Hz, 3 phase 4 wire, line voltage 380V, phase voltage 230V
Rated Load PowerResistive load: 1000kW
Installed CapacityResistive load: 1010kW
Load Step1,2,2,5,10,20,20,50,100,200,200,200,200kW, min step load: 1kW
PF(Power Factor)1
Load Tolerance (each step)±5%
Load Tolerance(overall)±3%
Display Precision0.5 class
Control Power400VAC/50Hz, 3 phase 4 wire, 230V 1-phase
Wire Connection

Load power supply input——Copper bar (star coupling)

Control power supply input——Connector-bar

InsulationF
Protection GradeIP21
Way of WorkingContinuous Working
Casing Dimensions and Coolingabout 1600*2400*2100mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling
WeightAbout 1500kgs/set
TransportationHoisting, there are lifting lug in top of casing
Casing ColorGrey(RAL7035)
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Altitude≤2500 meter
Atmospheric Pressure86~106kPa
ContactorSchneider
FuseDELIXI
MCUINFINEON
Data processing softwareKaixiang(self-developed)
Alloy ResistanceKaixiang(self-developed)


Product Advantage
 

1. Communication pattern: Intelligent control use photoelectric isolated RS485 interface connect to PC, with great anti-interference performance to make system control stable.

2. Load pattern: Manual Load or Automatic Load.

3. Manual Load: Input power, system will load according to preset power.

4. Automatic load: User can preset power and length of working time of several load periods, as per 0%→25%→50%→75%→100% or 110% to make testing

 

Application
 

1. Manufacturers of standby power generators commonly use load banks to test and tune newly assembled units

2. generator has been set up in a test cell within the factory, a test engineer uses the load bank to apply a discrete, selectable electrical load to the generator and measure the response stability and endurance.

3. During this process, the test engineer calibrates and adjusts the generator performance to ensure it meets the intended product specifications and tolerances.

 

 

 
 

 
 

Hot Products

High Quality And Good Price 1000KW AC Load Bank Quality Tester Product Description 1. AC Load Bank ...
Professional Produce 1000KW AC Load Bank Quality Tester With ISO9001 Product Description It offers ...
Custome Design AC Load Bank At 400V 500kW For Diesel Generator Product Description Automatic AC load ...
For Diesel Generator 380V 1000KW AC Load Bank For Generator Testing Product Description The system ...
For Diesel Generator 400V 1000K Watt AC Load Bank For Generator Testing Product Description The ...
Accurate Test 415V 500KW Power Factor Automatic AC Load Bank for UAE Product Description Load banks ...