fangsheng co ltd |
Verified Suppliers
|
|
1.ISO9001
2.Brand name:Fangsheng
3.size:600X600mm
4.thicknes:1.0-4.5mm
PVC flooring
Description: This product has permanent anti-static function because it uses conductive staic network formed at the interface of plastic particles. Its appearance looks like the pattern of marble. So it has good decoration effect i
Application: It is widely used for program machine room, computer room, control room of electric power, cleaning and purification workshop of telecommunication, electric power, electronics, micro-electronics and medicine industries and other places where it is necessary to be protected from electrostatic discharge.
Specifications:
Item | System Resistance | Decay Time | Rate of size change at heating | Starting Voltage | Amount of wear | Combustion Property |
Standard | DIN51953 | SJ/T10694-2006 | SJ/T11236-2001 | SJ/T10694-2006 | SJ/T11236-2001 | SF/T11236-2001 |
Index | 104~106Ω(Conductive) 106~108Ω(Anti-static) | 1000V-100V ≤2s | ≤0.25% | ≤100V | ≤0.02g/cm2 | ≤10s FV-O |
Brief Introduction of Installation
(1)the requirements of foundation
1.The ground should be waterstone ground, caramic tile groud,
wooden ground or cement ground.
2.The ground should be smooth and level.Its unflatness should be
less than 0.2%.
3.The ground should have enough strength and no the phenomenon of
sand comimg out and separation.
4.The ground should be dry.It is necessary for a new ground to dry
about 30days.
(2)Procedure of construction
Clean the ground→spread the earthing conductive net→lead out the
earthing line→coat strong adhesive→coat conductive adhesive→lay
floor→welding floor→cleaning→inspect properties
(3)Maintenance of floor
1.It is not permitted that sharp and rough heavy matters scribe and
drag on the surface of floor and that personnel who wear shoes with
nails walk on the floor.The floor should be kept cleaning.
2.It is not permitted that the chairs which have black rubber
cushion put on the floor in order to avoid black sulfied polluting
its surface.
3.If there are oil or dirty on its surface, it may be cleaned with
detergent.If there is scribed sign, if can be recovered through
fine abrasive paper.
4.If there are heavy oil and dirty caused by install equipments.Our
factory has special washer to clean them.
5.Our factory also has anti-static wax that can be used to maintain
the floor.In general, it should be coated one time every six
months.If the personnel walking on the floor are busy, it should it
should be coated every three months.