Hefei Coolnet power Co., ltd |
Verified Suppliers
|
|
Experience the pinnacle of power protection with our state-of-the-art modular online UPS . Designed to ensure the safe and reliable operation of your critical systems, this UPS offers a seamless power supply solution. Its double conversion topology stands at the forefront, delivering continuous, high-quality AC power with no delay when transferring to battery, providing ultimate peace of mind for all your power needs. Our modular online UPS is engineered to operate at a rate frequency of 50/60Hz, accommodating a broad range of regional power grid standards. This versatility ensures that your essential equipment remains operational no matter the external power inconsistencies or disturbances. With rate voltages of 380/400/415VAC (Line-Line) and 220/230/240VAC (Line-Neutral), this UPS is capable of supporting a diverse spectrum of electrical devices and systems, making it an ideal choice for various applications, including data centers, medical facilities, and industrial environments. |
|
|
Model CNM | 020/10 | 030/15 | 040/20 | 040/10 | 045/15 | 060/15 | 080/20 | 090/15 | 120/20 |
Rate Power | 20KVA/20KW | 30KVA/30KW | 40KVA/40KW | 40KVA/40KW | 45KVA/45KW | 60KVA/60KW | 80KVA/80KW | 90KVA/90KW | 120KVA/120KW |
Main input | |||||||||
Input | 3P5W(3P+N+PE) | ||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Rate Freq | 50/60Hz | ||||||||
Input PF | >0.99 | ||||||||
Current Distortion | THDi<3%(100%Linear load) | ||||||||
Voltage Range | 304-478VAC(L-L)full load;304-228VAC(L-L)power derate from 100%to 75% | ||||||||
Freg.Range | 40-70Hz | ||||||||
Battery | |||||||||
Rate voltage | ±240VDC(adjustable for 32-44 sections) | ||||||||
Charging Capacity | 20%*Pout | ||||||||
Charging Accuracy | ±1% | ||||||||
Bypass | |||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Voltage Range | Range:-40%-+25%,Settable,default-20%~+15% | ||||||||
Overload | 110%,long time operation;110%<load<125%,5 mins 125%<load<150%,1min;>150%,1second | ||||||||
Inverter | |||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Rate Freq | 50/60Hz | ||||||||
Output PF | 1 | ||||||||
Voltage Accuracy | ±1.0% | ||||||||
load Response | <5%(20%-80%-20%step load) | ||||||||
Recovery Time | <20ms(0%-100%-0%step load) | ||||||||
Output THDu | <1%(linear load),<5%(non-linear load according to IEC 62040-3) | ||||||||
Overload | 110%,1 hour;125%,10 mins;150%,1min;>150%,200ms | ||||||||
Frequency Accuracy | 0.1% | ||||||||
Synchronize Window | Settable,±0.5Hz-±5Hz,default±3Hz | ||||||||
Slew Rate | Settable,0.5Hz/S-3Hz/S,default 0.5Hz/S | ||||||||
Phase Accuracy | 120°±0.5° | ||||||||
System | |||||||||
Efficiency | Normal Mode≥96%;Battery Mode≥96% | ||||||||
Display | LED+7inch touch LCD | ||||||||
Certification-Safety | IEC62040-1,IEC60950-1 | ||||||||
Certification-EMS | IEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4(EFT);IEC61000-4-5(Surge) | ||||||||
IP Degree | IP20 | ||||||||
Configuration | USB,RS232,RS485,Dry contact,Cold start | ||||||||
Option | SNMP card,AS400 card,Parallel kit,LBS,Air filter,Bottom entry kit,Wheels kit | ||||||||
Environment | 0-40℃(operation);-25~70(storage);0-95%(Humidity,non-condensing) | ||||||||
Noise(dB)(1meter) | 65dB @100%load,62dB @45%load | ||||||||
Dimension | |||||||||
Cabinet(W*D*H)mm | 482*700*396(9U, wheels not included) | 482*700*662(15U, wheels not included) | 482*700*840(19U, wheels not included) | ||||||
Module(W*D*H)mm | 440*555*85(2U) |