Product introduction
The surge protector is a lightning protection measure
adopted by Zhejiang toer Electric Co., Ltd. for the electrical
system. It is suitable for the N-S, NT-C, TH-C, TT, LT and other
power supply systems of 50/60Hz 380V and below, which can be used
as the equipotential connection at the interface of LPZ1, LPZ2 and
LPZ3.
The design is based on IEC61643-1 and GB18802.1. It is
an electronic device that provides security protection for all
kinds of electronic devices, instruments and communication lines.
Product specification
Model and specofocation | TRS4-D20 | TRS4-C40 | TRS4-B60 | ||||
Rated Operating Voltage | Un | 220V/380V | |||||
Max continuous operating voltage | Uc | 385V AC | |||||
Voltage protective level | Up(KV)≤ | 1.5 | 1.8 | 2.0 | |||
Max discharge current | Imax(8/20μS) | 20kA | 40kA | 60kA | |||
Nominal discharge current | In(8/20μS) | 10kA | 20kA | 30kA | |||
Response time | ns | 〈25 | |||||
Ingress Protection Rating | IP20 | ||||||
Indication of invalidation | Aging invalidation:green Normal,red:Invaldation | ||||||
Configuration dimension | Three-phase four-wire:72×62×90 | ||||||
Application | Primary protection for in line | ||||||
Operating condition | Temp:-40℃~+70℃ | ||||||
RH≤95%(25℃) | |||||||
Sea level elevation≤3km | |||||||
Remote signal function | Can also picking | ||||||
Remarks | Other max continuous operating voltage can be customized |
Product features
1. new technology, high energy, gap discharge electrode
N-PE.
2. leakage current is small, the response time is fast, and
the residual pressure is low
3. copper fittings have good electrical conductivity
4. the speed of response is 0.001 seconds, and the
voltage is controlled in the range that the equipment can
withstand.
Notice of product
1. surge protector is installed with 35MM standard guide
rail
2. standard RJ45 interface can be conveniently connected to
the front end of the protected equipment.
The grounding path should be as short as possible, and the length should not exceed 1.5 meters.
3. identify the input / output interface identifier of
the lightning protector, input the external line and output the
connection device.
4. lightning arresters are connected in series between
protected equipment
Product Installation
With 35mm standard DIN-rail mounting, connecting copper stranded conductor is 2.5~35mm²
At front of spd each pole must be setted protection---used fuse or miniature circuit breaker lightning current SPD protection,after SPD breakdown to short circuit protection.
SPD install on protected line(equipment) to the front and connected to the supply line. A class products install in the building home-entry line hold larger surge current total distribution box. B, C class products most install on the floor distribution box, D class products close to the front-end equipment that smaller surge current, smaller residual voltage place.
Working principle of product
Under normal working condition, the lightning
protection module is in a high resistance state. When the power
supply line has lightning invasion or operation transient
overvoltage, the lightning protection module will immediately pass
through the response speed of nanosecond level, and limit the
lightning overvoltage or transient overvoltage to the voltage range
allowed by the electrical equipment, thus protecting the normal
operation of the electronic equipment. After that, the lightning
protection module quickly returns to the high impedance state
without affecting the normal power supply of the grid.
Company profile
Thor is all about protecting against the damaging
effects of power transients. It is our goal and mission to connect
our customer challenges with high-quality, right-priced solutions
and products – completed by unrivaled customer service and