Home Companies Fangyu(shanghai)Automation Technology Co.,Ltd

35kv mv cable Medium Voltage Outdoor Energy SWA Power Cable

Fangyu(shanghai)Automation Technology Co.,Ltd

Contact Us

[China] country

Trade Verify

Address: Room 1702, Building 4, Lane 658, Guangfulin Road, Songjiang District, Shanghai

Contact name:Nora

Inquir Now

Fangyu(shanghai)Automation Technology Co.,Ltd

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

35kv mv cable Medium Voltage Outdoor Energy SWA Power Cable

Country/Region china
City & Province shanghai shanghai
Categories Power Cables
InquireNow

Product Details

 

Product Description

MV Underground Power Cables Outdoor Energy BS 7835 - 6.35/11kV SWA
 

Armoured 3-core cable with XLPE insualtion. Rated voltage 6.35/11 KV


STANDARDS
National : BS 7835


DESCRIPTION
Electric cable with copper conductors, semiconductive conductor screen, XLPE insulation, semiconductive insulation screen, copper metallic screen for each core, LSF bedding, galvanized steel wires armour (SWA), LSF outer sheath


Application
suitable for installation in energy networks where for safety reasons Low Smoke and Halogen Free cables are specified. The cable is suitable for installation underground, in ducts or in air


Note: the cable is suitable for rated voltage 6/10 KV according to IEC 60502-2

Cable Data

Sizes(mm2)Insulation Thickness(mm)App. Overall Dia.(mm)App. Weight(kg/km)(Cu)
3x353.451.54658
3x503.454.25355
3x703.458.36311
3x953.462.47415
3x1203.465.98479
3x1503.469.19678
3x1853.473.011093
3x2403.480.114191
3x3003.485.516457
3x4003.493.220188
 


Note: The single-core armored cables are used for the D.C. system only. If used for the A.C. system, the magnetic isolation should be applied to the steel armor wires of non-magnetical materials that should be used.

3 Operating characteristics
- Rated power-frepuency voltage U0/U: 6.35/11kV.
- Max.admissible operating temperature of the conductor:90ºC.
- Max. short-circurt temperature of conductor shall not exceed 250ºC. (5s maximum duration)
- The ambient temperature under installation should not below 0ºC.
- The bending radius of a single-core cable should not less than 20 times of the cable diameter. 
The bending radius of a multi-core cable should not less than 15 times of the cable diameter. 

 


----------------------------------------------------------------------------------------------------------------------------------------

The description "MV Underground Power Cables Outdoor Energy BS7835 - 6.35/11kV SWA" refers to medium voltage (MV) underground power cables designed for outdoor use and complying with the British Standard BS7835. The cables have a voltage rating of 6.35/11kV and feature a Steel Wire Armor (SWA) construction.

Here's a breakdown of the key components and characteristics:

Voltage Rating: The cables are designed to operate at a medium voltage level of 6.35/11kV. This indicates that they are suitable for power distribution applications requiring voltage levels within this range.

Underground Use: These cables are specifically designed for underground installation. They are suitable for burying directly in the ground or for use in ducts or trenches.

Outdoor Energy: The cables are intended for outdoor environments, where they are exposed to weather conditions like sunlight, rain, and temperature variations. They are constructed to withstand the outdoor elements and provide reliable power transmission.

BS7835 Standard: BS7835 is a British Standard that sets requirements for medium voltage cables used in electricity supply systems. Compliance with this standard ensures that the cables meet specified performance, construction, and testing criteria.

Steel Wire Armor (SWA): The SWA construction refers to a layer of steel wires that provides mechanical protection to the cables. The armor enhances the cables' resistance to physical damage, such as impact, compression, and mechanical stress. It also offers additional protection against rodents and other external hazards.

Hot Products

Product Description YJV32 YJV72 600/1000V Copper Underground XLPE Cable Armoured Power Cable Cable ...
Product Description 0.6/1kv LV Copper Aluminum Conductor XLPE Insulated PVC Sheath Armoured Power ...
Product Description YJV32 YJV72 600/1000V XLPE copper Cable Armoured Power Cable Cable Selection It ...
Product Description 600/1000V 4x150mm2 XLPE Copper Cable YJV32 Armoured Power Cable Cable Selection ...
Product Description 600/1000V 3x150mm2 XLPE Copper Cable YJV32 Armoured Power Cable Cable Selection ...
Product Description 600/1000V 4x120mm2 XLPE Copper Cable YJV32 Armoured Power Cable Cable Selection ...