Home Companies Knkong Electric Co.,Ltd

GB ISO 36KV Gas Insulated Switchgear Medium Voltage Ring Main Unit

Knkong Electric Co.,Ltd
Active Member

Contact Us

[China] country

Address: No. 25 Street , Hanghai Road, Zhengzhou,Henan,China

Contact name:Ken Chan (English)

Inquir Now

Knkong Electric Co.,Ltd

GB ISO 36KV Gas Insulated Switchgear Medium Voltage Ring Main Unit

Country/Region china
City & Province zhengzhou henan
InquireNow

Product Details

GB ISO 36KV Gas Insulated Switchgear Medium Voltage Ring Main Unit

Product Introduction

 

General

SF6 ring main unit is an air-insulated or gas-insulated medium-voltage electrical combination equipment that can be combined into multiple circuits at will, with switching, communication, and protection of the power system, with load switches as the core component. Its main circuit core component is composed of SF6 load switch or additional circuit breaker and other primary auxiliary electrical appliances.

In recent years, the SF6 ring network cabinet has developed very fast, and both the manufacturing process and the product reliability have the potential to be equal to the international electrical giants. Of course, the voltage level between 24kV and 40.5 still has a certain gap with foreign manufacturers. At present, there are only a handful of domestic manufacturers producing power distribution SF6 power distribution level at 40.5kV level. The others are C-GIS of the first-level system, based on the first-level power system with large current and large capacity. )

 

Feature
1. Metal-clad and fully enclosed structure, can prevent dirt and small animals from the entrance.
2. Through the observation windows in the door panel switch position and general condition can be clearly viewed.
3. The door and switch operating handle is mechanically interlocked to ensure the door cannot be opened with the switch closed and the switch cannot be closed with the door open.
4. The switchgear use vacuum switches combined with solid insulation material. This environmentally-friendly technology avoids the use of SF6 as an insulation gas.
5. Reliable FIVE-PREVENTION interlock can effectively prevent mal-operation.

 

Technical Data

No.ItemUnitParameter
1Rated voltagekV122436
2Rated frequencyHz50/60
3Rated currentA630(1250*)
4

1min Power frequency

withstand voltage

wetkV385070
drykV486085
5Lightning impulse withstand voltagekV75125/150170
6Rated short circuit breaking current (peak)kA806363
7Rated active load and close circuit breaking currentA635050
8Rated transferring currentA170012001200
9Rated short circuit making a current (peak)kA806363
10Rated cable(line) charging breaking currentA

50 and 10

50/10

11Cable charge breaking current in earthing faultA202020
12Rated withstand current (peak)kA806363
13Short-time withstand current (2s)kA252020
14Mechanism lifetimes500020002000

Note: For short circuit breaking and the peak current is based on Fuse plus combination

Hot Products

KYN28A-12KV for 6KV withdrawable switchgear Voltage: 12KV Current:630-2000A Circuit breaker: Vacuum ...
Withdrawable vacuum circuit breaker for medium voltage use KYN28A-12 Voltage: 12KV Current: 630...
Withdrawable VCB medium voltage switch panel KYN28A-12 metal-clad type Voltage: 3.6-24KV Current: ...
IEC GB standard 12KV 1250A KYN28 metal-enclosed switchgear for power plants use Voltage: 3.6KV-24KV...
KYN28A-12KV medium voltage 3.6KV 6.6KV 12KV 24KV withdrawable switchgear Voltage: 12KV Current:630...
Vacuum circuit breaker type switchgear KYN28 for medium voltage using Voltage: 3.6KV 6.6KV 12KV 24KV ...