JYL-KK Type 6-35kV Overhead Fault Indicator

 

Product Introduction

 

The ring network cabinet online monitoring equipment is mainly suitable for the automation transformation of the traditional ring network cabinet and the switchgear. While realizing two remote (remote signaling, telemetry) functions, detect and locate the position of short circuit and ground fault at the same time, shorten the power outage time and scope. Not only is important for improving the reliability of power supply, but also an indispensable technology for building an intelligent grid.

 

Advantages

Sampling the zero-sequence current synthesis algorithm, canceling the traditional zero-sequence transformer design, synthesizing the zero-sequence current by detecting the phase sequence to identify the single-phase ground fault, and effectively solving the situation where it is not convenient to install the zero-sequence transformer;
5A self-powered, the acquisition unit uses high magnetic permeability material CT, combined with low-power system design, to ensure that the primary current 5A achieve battery-free full-function operation, improve reliability;
Instead of using the traditional one-time battery power supply scheme, the three-level power architecture of CT power supply, supercapacitors, and non-rechargeable lithium batteries is adopted to guarantee the reliable operation of the equipment;
Electronic current transformer for current and ground electric field detection, It has great linearity of test data and is not affected by wire diameter, thus guarantee test accuracy;
Collection unit indicates failures locally and centrally, eliminating the need to install display panels in every interval;
The energy opening CT is made of anti-rust and anti-corrosion materials, supplemented by a high-level cutting process to ensure that the outdoor environment provides sufficient power for the equipment;
Both the collection unit and the acquisition unit can be controlled remotely and wirelessly.

 

Technical Parameter

ItemParameter

 

Applications

Voltage6~35kV
Neutral grounding methodVarious grounding methods are available
Wiring typeOverhead insulation and bare wires 35mm²~300mm²

 

Collection unit power supply

Main powerPT/CT
Backup power

Rechargeable battery: Lithium iron phosphate or lead-acid colloid battery is dependent on necessary.

All hardware design is compatible for them both.

 

Acquisition unit power supply

Main powerLine self-powered (5A full-function operation)
Backup powerDisposable lithium battery 3.6V, 8.5Ah
Time of duration of the supercapacitor battery> 12 hours
Static power dissipationAcquisition unit≤40uA
Collection unit≤0.2VA
Telemetry accuracyCurrent

0~200A,measurement accuracy:±2A

200A~600A,measurement accuracy:±1%

Sampling frequency4096Hz
Fault detectionRecognizable fault typeShort circuit between phases, various single-phase grounding
Instantaneous faults and permanent faults
Recognition minimum recognition time0.2s

 

Line status indication

IndicationBright LED
Flashing time after an outage>2000h
Fault reset methodTimed automatic reset can be set from 1 to 48 hours
Power-on automatic reset and remote manual reset

 

Local communication

Frequency band430~480MHz
Communication mediumPlastic optical fiber
Communication distance>20m
Mechanical propertiesWeight<2kg
Protection levelAcquisition unit IPX7;Collection unit IPX5
Working environmentTemperature-40℃~70℃ 10%~
Humidity100%
Service lifeOperating>8 years
Failure-free time (average)

MTBF≥70000h

 

 

Hot Products

KYN28A-12KV for 6KV withdrawable switchgear Voltage: 12KV Current:630-2000A Circuit breaker: Vacuum ...
Withdrawable vacuum circuit breaker for medium voltage use KYN28A-12 Voltage: 12KV Current: 630...
Withdrawable VCB medium voltage switch panel KYN28A-12 metal-clad type Voltage: 3.6-24KV Current: ...
IEC GB standard 12KV 1250A KYN28 metal-enclosed switchgear for power plants use Voltage: 3.6KV-24KV...
KYN28A-12KV medium voltage 3.6KV 6.6KV 12KV 24KV withdrawable switchgear Voltage: 12KV Current:630...
Vacuum circuit breaker type switchgear KYN28 for medium voltage using Voltage: 3.6KV 6.6KV 12KV 24KV ...