High Efficiency of Electrothermal Conversion Mineral Insulated Heating Element possesses good property on high efficiency of electrothermo conversion compared to other heating solutions.

 

Using the principle of the thermal effect of electrical current (Joule-Lenz law), the pure resistance heats up, converting almost 100% electric energy into heat energy.

 

Mineral Insulated Heating Element for Chemical Industry Heating or Heat Trace is to be designed based on selection of mineral insulated heating cable which is prefabricated in the manufacturer's workshop into a heating element that can be directly connected to the power supply. It is usually composed of heating cables, cold and hot joints, cold end cables, terminals, tail ends and lead wires, etc. There are the following types can be selected from including type A, Type B, Type C, Type D, Type E, Type F and Type G structures. Among them, Type A, B and C are only suitable for single-core heating cable, while type D, E, F and G are only suitable for double-core heating cable.

 

 

Common structure of the heating cable for the heating element is of single core and two core, while the customization can be according to clients’ needs to design and provide MI heating cable of three core or more.

 

 

Specifications

Heating cable instruction code


NO. 1 2 3 4 5 6 7MI CN-B 16K239/60/2520/220/E1

 

NO.Instruction 
1core number1 or 2
2Voltage grade3=300V, 6=600V
3conductor materialsK,N,C
4cold resistance ×1000239=0.239Ω/m×1000

 

 

 

 

 

 

 

Cable Code

1 6 K 239

No. 1 2 3 4

No.Instruction 
1Sheath materialCu-Ni
2structure of cable componentsshown in table 1
3cable codesshown in table 2, 3 and 4
4length of heating cableIn meter
5Heating cable powerIn Watt
6heating cable voltageIn Volt
7heating cable voltageSee table 5

 

 

 

 

 

 

 

 

 

 

 

Table 2 Heating Cable Specification (600V Single Core)

 

Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
16C2.16.80.0021130220.7
16C3.45.90.0034173162.5
16C5.35.30.0053214125.6
16C8.54.80.0085261101.6
16C134.30.01332579.1
16C214.00.02137665.8
16K405.80.04179157.1
16K505.40.05206135.6
16K605.20.06222122.8
16K804.80.08261101.2
16K1004.70.120099.5
16K1204.50.1220088.8
16K1606.50.16200202.2
16K2005.90.2200166.5
16K2505.30.25215131.7
16K4004.70.428096.7
16K5004.50.530087.7
16N6304.30.6318582.2
16N10003.91.023062.8
16N16003.61.627052.4
16N25003.42.530045.6
16N28003.42.830045.2
16N33003.43.330044.7
16N40003.24.035038.1
16N52003.25.235037.7
16N63003.26.335038.4
16N100003.21035038.9
 

Table 3 Heating Cable Specification (600V Double Cores)

 

Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
26K8.411.80.008443632.9
26K13.49.80.013463431.5
26K218.80.02178339.0
26K348.00.03494273.7
26K547.10.054119212.4
26K856.40.085147170.2
26K1306.00.13167147.8
26K1807.90.1896271.9
26K2607.40.26110234.2
26K3606.80.36130195.5
26K5006.40.5100171.2
26K6505.90.65100144.8
26K10005.71.0100133.3
26K13006.21.3100160.6
26K20005.82.0100139.1
26K33005.43.3100118.8
26N46005.84.6100138.3
26N80005.48.0100118.6
26N130005.013.0100100.8
26N270004.827.010092.1
26N400004.640.010084.4
26N600004.460.010077.1
26N720004.272.010070.2
 

Table 4 Heating Cable Specification (300V Double Cores)

 

Cable CodeDiameterNominal resistance at +20℃Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
23K2105.20.21222117.9
23K3004.80.326198.9
23K4004.80.426197.2
23K4804.80.4826196.0
23K6504.60.6528487.3
23K10004.11.010068.9
23K13003.81.310058.9
23K20005.02.0100104.7
23K24004.82.410095.7
23K30004.63.010087.3
23N46004.84.610096.3
23N75004.67.510086.9
23N112004.411.210078.7
23N140004.214.010071.6
23N180003.618.010052.6
23N260003.626.010052.2
23N400003.440.010046.4
23N500004.050.010063.8
23N600003.660.010051.7
23N720003.472.010046.1

Note: the resistance value of 2-core cable in the above table is the measured value after the end is twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals.

 

Table 5 terminal specifications

 

 Model: A, D, EModel: B

Maximum Voltage

(V)

Maximum Current (A)Terminal SpecificationMaximum Current (A)Terminal Specification
  
60015E220E1
60020E225E2
60030E340E2
60050E370E2
60070E3100E3

Note 1: E1 means 1/2 "NPT;E2 means 3/4 "NPT;E3 represents 1 "NPT (taper thread);Additional connection thread requirements are available.

Note 2: the length of cold end cable with standard configuration is 2 meters. If you increase or decrease of length required, please contact our professional personnel.

 

Corresponding reference table between the output power and sheath temperature

Anticorrosive specification

 

Material  
SulfateNot recommend 
Hydrochloric acidData checking required 
Hydrofluoric acidData checking required 
PhosphateData checking required 
CarbonateData checking required 
Organic acidData checking required 
Alkali metalData checking required 
Sea waterExcellent 
ChlorideExcellent 

 

Explosion-proof instructions

MICN series heating cable with explosion-proof terminal, can be used in potential explosive environment. Authenticated by the Chinese CQST, in accordance with Chinese GB3836 explosion-proof electrical standards, they can be applicable to A, B, C (C1D2) level of explosion-proof electrical equipment.

Hot Products

Radiation And High-Temperature Resistant Inorganic Mineral Insulated Coaxial And Triaxial Cables ...
Stainless Steel 304 Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable Stainless ...
Oxygen-Free Copper Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable Oxygen...
Pure Nickel Wire Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable Pure Nickel ...
SS Cladded Copper Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable SS Cladded ...
Magnesium Oxide Insulated Metal Conductor Coaxial Or Triaxial Signal Detecting Cable Magnesium Oxide ...