Mineral Insulated Cable For High-Temperature Process Line Heating is a magnesium oxide mineral insulated metal sheathed heating cables designed for high temperature process line heating, such as steam, boron, sodium, or lead bismuth.

 

A nuclear power plant is an industrial site intended for the production of electricity, which uses as boiler one or more nuclear reactors supplied with nuclear fuel (source of energy). The power of a power station varies from a few megawatts to several thousand megawatts depending on the number and type of reactor in service on the site (900 MWe or 1300 MWe in France per reactor). Electricity is produced by a chain reaction (nuclear fission) producing heat that will then generate steam. The steam thus produced makes it possible to rotate generators that flow on the national electricity grid.

 

To avoid the crystallization of the process fluids or the water freezing, heat Tracing is often installed on critical circuits and is therefore an essential equipment for safety.

 

 

Cable Structure

 

 

Specification

Heating cable instruction code

 

 

MI CU-B 16K320/60/2520/220/E1

No. 1 2 3 4 5 6 7

 

No.Instruction 
1Sheath materialCU
2structure of cable componentsshown in table 1
3cable codesshown in table 2, 3 and 4
4length of heating cableIn meter
5Heating cable powerIn Watt
6heating cable voltageIn Volt
7heating cable voltageSee table 5

 

 

 

 

 

 

 

 

 

 

Cable Code

 

1 6 K 320

No. 1 2 3 4

 

Serial NO.Instruction 
1core number1 or 2
2Voltage grade3=300V, 6=600V
3conductor materialsC,K
4cold resistance ×1000320=0.32Ω/m×1000

 

 

 

 

 

 

 

Table 1 Structure of Cable Element

 

 

Note: Model C, F and G are suitable for being used at temperature under 65

 

Table 2 Heating Cable Specification (600V Single Conductor)

 

Cable CodeDiameterHDPE DiameterStandard resistance value at +20Maximum Production LengthUnit weight
mmmmΩ/mmkg/km
16C1.78.2100.0017350366.54
16C2.27.69.40.0022380307.77
16C2.97.08.80.0029400264.45
16C45.97.70.004600190.88
16C75.37.10.007600154.08
16C114.96.70.011600132.25
16C134.66.40.013600 (300)☆125.7
16C174.66.40.017600 (300)☆117.16
16C214.66.40.021600 (300)☆111.9
16C253.75.50.025600 (480)☆68.83
16C333.75.50.033600 (480)☆63.76
16C403.45.20.04600 (560)☆58.87
16C633.250.06360051.47
16K806.88.60.08370 (140)☆254.18
16K1005.270.1450 (240)☆162.11
16K1404.96.70.14600 (270)☆122.55
16K1974.456.250.197600 (330)☆111.32
16K2204.56.30.22600 (330)☆102.89
16K3154.36.10.315600 (350)☆91.44
16K3454.26.00.345600 (370)☆85.9
16K4504.05.80.45600 (400)☆80.73
16K6304.05.80.63600 (400)☆77.26
16K8003.55.30.8600 (530)☆61.48
16K12502.84.61.2560040.83
16K20002.84.62.060038.96

 

 

Table 3 Heating Cable Specification (600V Double Conductors)

 

Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
26C3.412.90.0034150783.76
26C4.412.20.0044160701.56
26C5.811.30.0058170606.16
26C8.69.900.0086180451.43
26C11.49.300.0114200400.05
26C13.89.000.0138210375.20
26C17.28.600.0172220344.90
26C238.000.023250303.25
26C34.47.500.0344280269.20
26C49.27.100.0492300243.84
26K2409.900.24180451.43
26K3209.300.32200400.05
26K3849.000.384210375.20
26K4808.600.48220344.90
26K6408.000.64250303.25
26K9607.500.96280269.20

 

 

Table 4 Heating Cable Specification (300V Double Cores)

 

Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
23C3.412.00.0034200708.10
23C4.411.30.0044220629.07
23C5.810.40.0058240537.73
23C8.69.000.0086260392.56
23C11.48.400.0114280343.89
23C13.88.000.0138300314.57
23C17.27.600.0172320286.27
23C237.100.023340252.98
23C34.46.600.0344360221.19
23C49.26.200.0492380197.64
23K16010.40.16220508.37
23K2409.000.24240392.56
23K3208.400.32265343.89
23K3848.000.384280314.57
23K4807.700.48300291.91
23K6407.100.64320252.98
23K9606.500.96350216.11

Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals;

Mark of (300)☆ is a recommended production length by MICH

 

 

Table 5 terminal specifications

 

 Model: A, D, EModel: B 
Maximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)
    
60015E220E115E1
60020E225E220E1
60030E340E230E2
60050E370E250E2
60070E3100E370E2

 

Note 1: E1 means 1/2 "NPT;E2 means 3/4 "NPT;E3 represents 1 "NPT (taper thread);Additional connection thread requirements are available.

Note 2: the length of cold end cable with standard configuration is 2 meters. If you increase or decrease of length required, please contact our professional personnel.

 

Corresponding reference table between the output power and sheath temperature

 

 

Note: when applying a copper conductor heating cable, please pay attention to the conversion of its heated hot resistance and unheated cold resistance.

 

 

 

Hot Products

Radiation And High-Temperature Resistant Inorganic Mineral Insulated Coaxial And Triaxial Cables ...
Stainless Steel 304 Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable Stainless ...
Oxygen-Free Copper Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable Oxygen...
Pure Nickel Wire Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable Pure Nickel ...
SS Cladded Copper Conductor Mineral Insulated Coaxial Or Triaxial Signal Detecting Cable SS Cladded ...
Magnesium Oxide Insulated Metal Conductor Coaxial Or Triaxial Signal Detecting Cable Magnesium Oxide ...