325VA Transformer-A Type Emergency Converter For Field Installation

Country/Region china
City & Province dongguan guangdong
InquireNow

Product Details

325VA Transformer-A Type Emergency Converter For Feild Installation

Description

  • 325VA Transformer-A Type
  • INPUT VOLTAGE: 480Vac±10% / 347Vac ±10% / 277Vac ±10%
  • OUTPUT VOLTAGE: 208Vac @ 480Vac / 150Vac @ 347Vac / 120Vac @ 277Vac
  • Safety standard:UL 5085-3 listed,for feild installation
  • Warranty:5 years warranty

 
ELECTRICAL SPECIFICATIONS

Parameter
Symbol
Conditions
USA
CA
USA
 
Input Voltage
V Input
 480347277V
Output Voltage
V Output
Infliction Rated Voltage
208150120V
Input Current
A Input
Infliction Rated Voltage
0.75A
Output Current
A Output
Infliction Rated Voltage
1.56A
Output Watts
VA Output
Infliction Rated Voltage
325240185VA
Power Factor
PF
Nominal
0.96   
THD(Primary Lamp Type)
 
Infliction Rated Voltage
  10%
2nd Harmonic
 
Rated Voltage / Frequency
  2%
3nd Harmonic
 
Rated Voltage / Frequency
  30%
5nd Harmonic
 
Rated Voltage / Frequency
  10%
7nd Harmonic
 
Rated Voltage / Frequency
  7%
9nd Harmonic
 
Rated Voltage / Frequency
  5%
Temperature Rise Of Ballast Winding
 
Rated Voltage / Frequency
  55K
Max Casing Temperature
 
Faulty Status
  105C
14AWG Lead Lengths
  200210220MM

 

*EMI Shall Comply To GB17625-1-2003 ** Current power factory

 

 

 

DIMENSION

 

TRANSFORMER COVER BOX

♦Attach transformer to cover box.

♦Make wiring connections.

♦Attach transformer cover box assembly to luminaire driver enclosure.

 

TRANSFORMER BRACKET FOR PANELS

♦Attach transformer to bracket.

♦Attach transformer bracket to panel.

♦Make wiring connections.

Hot Products

The Microwave sensor HD05V-CRH with DIP switch and On/Off function HD05V-CRH .pdf Features Dual ...
HT36V Motion Sensr And Driver 2 in 1 Product with Dimmable Function *HT36V.pdf* Features: 5.8GHz ...
HD418M Wide Voltage Input Dimmable Sensor with UL Certificated Bi-level Dimming or ON/OFF Function ...
15M Highbay UL Sensor HD406VRH Suitable for UFO With On/Off Function *HD406VRH ON&OFF specification...
HD07VR-MH-B Highbay Bluetooth Sensor with UL Certification Dimmable Funnction *HD07VR-MH-B ...
Small Size DIP Swicth Sensor with UL And FCC Certification *HD401S 1 specification.pdf* Features: ...