High Voltage Outdoor Isolator Disconnector Switch 252KV

 

Main Description:

 

GW38-40.5~252/630~4000 Type Disconnector Switch is good for reducing the distance and station arranging, especially for outdoor station.

 

Because of electric rod's self-rotation and switching structure and having self-locking function, it has strong property of motor performance resistance. Meanwhile, it can resist motor, wind pressure, earthquake and other outside power.

 

Technical Parameter:

 

1. 252kv voltage disconnector

2. We have 20 years exprience

3. Best price & Best quality

 

Parameter Table
NoItemsTechnical parameter
1Rated Voltage kV 72.5126252
2Nominal system voltage kV 66110220
3Rated current A630;1250;1600;2000;2500;3150;4000
4Rated Short Time withstand current and Time kA/s25~50/4
5Rated Peak withstand current kA63~125
61min power frequency withstand voltage (effective value) kVTo earth140230460
To phase1402300460
Across Isolating DS180230+70460+145
7Lightning Impulse wishstand voltage(peak value) KVTo earth3255501050
To phase3255001050
Across Isolating DS385550+1001050+150
8Rated mechanical terminal load NLevel of lateral load75015002000
Level of vertical load50010001500
Vertical75010001250
9The min distance of insulation against ground mm 60010002000
10Max Man Operative Moment N. m200
11Motor Drive operating mechanism control voltage VAC220,380; DC110,220
12Motor Drive operating mechanism motor voltage VAC220,380; DC110,220

Hot Products

18KV Silicon Rubber Metal Oxide Station Class Surge Lightning Arresters for Transformer Protection ...
Lightning Protection Equipment Polymeric Metal Oxide Surge Lightning Arrester 10KA , 24KV Introducti...
15KV Distribution Power Networks Metal Oxide Gapless Surge Arrester with Kema Tested Specifications: ...
10KA Medium Voltage Silicone Housing Polymeric Metal Oxide ZnO Surge Lightning Arrester for ...
Electronics Electrical Composite Gapless Zinc Oxide Surge Protector Lightning Arrester with Bracket ...
36KV Medium Voltage Polymeric Housing Thunder ZnO Surge Arrester for 10KA Transformer Surge Arrester ...