Home Companies SKYLINE INSTRUMENTS CO.,LTD

EN54-7 / EN14604 Smoke Fire Detector Test Tunnel

SKYLINE INSTRUMENTS CO.,LTD

Contact Us

[China] country

Trade Verify

Address: No.1802 Room 6# Building Universal Commerce Center Nancheng District Dongguan Guangdong China

Contact name:Ivy Xie

Inquir Now

SKYLINE INSTRUMENTS CO.,LTD

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

EN54-7 / EN14604 Smoke Fire Detector Test Tunnel

Country/Region china
City & Province dongguan guangdong
Categories Physical Measuring Instruments
InquireNow

Product Details

EN54-7/EN14604 Smoke Fire Detector Test Tunnel

 

Product introduction 

I. Scope of application:

1.1 Applicable to civil buildings installed in accordance with the scattered light, transmitted light principle (photoelectric principle) work of the alarm of the independent smoke-sensing fire detection alarms, point-type smoke-sensing fire detectors each functional test.

1.2 Testing items:

1.2.1 Response threshold test

1.2.2 Function test

1.2.3 Polarity reversal test

1.2.4 Power-on test

1.2.5 Repeatability test;

1.2.6 Orientation test;

1.2.7 Consistency test;

1.2.8 Air flow test;

1.2.9 Ambient light test;

1.2.10 High temperature test

II standard

2.1 Comply with EN54-7"point-type smoke detectors": EN14604

 

III the main technical characteristics:

3.1 Ring box: modular design, with a sensor pre-hole, reserved production plug frame interface, with upgrading and expansion space;

3.2 Control part: developed by GXWORKS2 and GOOLMAYHMI development software, with clear and simple interface, it can automatically identify alarm, air change, record, automatic angle rotation, wind speed switching, etc., and display the test parameters such as wind speed, temperature, concentration, and rate of smoke rise;

3.3 Optical densitometer: reflective, vibration isolation design, automatic zero correction, automatic correction of smoke pollution measurement deviation;

3.4 Test smoke: the use of liquid paraffin aerosol generator. Uniform particle size distribution, stable smoke production, particle size accounts for more than 90% of the number of smoke particles. Automatic smoke generation, closed-loop control of the rate of rising smoke by the control host, automatically remove the remaining smoke from the pipeline;

3.5 Circulating wind, smoke mixing and heating insertion box: six circulating fans, fan using PWM control, two-layer smoke mixing board, SCR control heating rod;

3.6 Motorized lifting plate: controlled by servo motor, automatically controlling the azimuth of the smoke installation lifting plate, set with adapter plate;

3.7 Exhaust smoke and air exchange part: controlled by high-flow fan, with check valve controlled by computer programme execution;

3.8 Air intake system: adopting multi-layer filter to ensure clean air intake in the smoke box;

 

 

IV. Main technical parameters:

4.1 Composition of the instrument: it consists of annular box, smoke production device, test area, smoke concentration measurement, airflow regulation part, and measurement part;

4.2 Test box:

4.2.1 Composition: composed of test area, motorized lifting disc, smoke exhaust and air exchange part, air intake part and measurement part;

4.2.2 Structure: closed-loop hermetic box structure. The box is three layers, the inner layer is aluminum foil, the middle is rubber-plastic insulation layer, and the outer shell is high-temperature electrostatic baking paint.

4.2.3 Specification: the test area is 425mm*425mm*1100mm;

4.2.4 Airflow speed: 0.8m/s±0.1m/s, 0.2m/s±0.04m/s, 1.0m/s±0.2m/s;

4.3 Smoke production device:

4.3.1 Test smoke: using liquid paraffin aerosol generator;

4.3.2 particle size: 0.2um~1.0um, accounting for more than 90% of the number of smoke particles;

4.3.3 Good reproducibility and stability of particle size distribution;

 

 

4.3.4 Test smoke injection rate into the smoke box: photoelectric detector (m value): 0.015dBm-1 min-1≤Δm/Δt≤0.1dBm-1min-1;

4.3.5 Stability of smoke production and test smoke: ensure the stability of the test smoke by monitoring the stability of the smoke rising rate dBm-1min-1;

4.3.6 Smoke generation control mode:

4.3.6.1 Smoke rising mode: gradually increase the smoke concentration according to the preset smoke rising rate, and close-loop correction of the smoke rising rate in the process;

4.3.6.2 Constant smoke mode: keep the smoke concentration value to the preset level after rising smoke to a constant concentration, and the fluctuation rate of constant smoke concentration is not more than ±0.01dB/m.

4.4 Response threshold measurement:

4.4.1 Measurement method: there are optical method measurement;

4.4.2 Optical method measurement of response threshold.

4.4.2.1 working principle: with the light-sensitive coefficient m value (unit dB / m) that the detector alarm moment of the smoke density, measured by the photoelectric detector, that is, with the light-sensitive coefficient m value (unit dB / m), the calculation formula is m = (10 / d) lg (P0 / P);

4.4.2.2 Optical measurement length: not more than 1.1m;

4.4.2.3 Emitter: beam wavelength of 800nm ~ 950nm;

4.4.2.4 Response time (T90): ≤3s;

4.4.2.5 Measurement range: light reduction coefficient range 0.001~1.1dB/m;

4.4.2.6 Measurement error: (m*5%±0.02) dB/m;

4.4.2.7 Resolution: 0.001dB/m;

4.4.2.8 Before each measurement, the reading of the measuring instrument is compared with the reading in clean air (zero point), and the measurement error is ≤0.02dB/m;

4.4.2.9 Light source: 800nm~950nm infrared light source;

4.4.2.10 Acceptor: Japan Hamamatsu silicon light tube.

 

4.5 High temperature test:

4.5.1 Smoke box working temperature: room temperature ~70℃;

4.5.2 Rate of temperature rise: <1℃;

4.5.3 Heating power: 3kw;

4.5.3 Temperature uniformity: deviation of each region on the cross-section of the test area ≤ 0.2 ℃;

4.5.4 One-key start, alarm automatic identification, automatic completion of the angle rotation, cold threshold test, heating, heat preservation, high-temperature threshold test, recording, angle reset. Temperature curve, smoke concentration curve, rising smoke rate curve can be viewed;

4.6 Flash device:

4.6.1 Structure: a hexahedral cubic box with 4 non-drinking surfaces lined with glossy aluminum foil on the inside side;

4.6.2 Fluorescent lamps: each fluorescent lamp has a power of 30 W, a colour temperature of 3200 K^-4200 K, and a diameter of about 380 mm. They are fixed on the inside of each of the 4 closed surfaces;

4.6.3 The detector is mounted in the centre of the top surface of the hexahedron so that the light can reach the detector from the top, bottom and sides;

4.6.4 Lamp: first aging 100 h after use, use 2000h after the lamp should be scrapped ;

4.6.5 External dimensions: 380 * 380 * 380mm.

4.7 Control section:

4.7.1 consists of two parts: touch screen and computer control part;

4.7.2 Test curve: smoke concentration curve, rising smoke curve;

4.7.3 Data access and recording: automatic storage of test data, maximum 10000 items per item, can form EXCEL report;

4.7.4 Data acquisition: composed of acquisition card, temperature module, AD module;

4.8 overall structure:

4.8.1 chassis material: the main body of high-quality steel plate, high-temperature electrostatic baking paint;

4.8.2 Overall dimensions: length * width * height of 2600mm * 820mm * 1640mm;

4.8.3 Box material: USU304 # stainless steel, the middle of the 10mm heat insulation cotton;

4.8.4 Fixing method: the equipment comes with casters (with brakes), the whole smoke box can be adjusted by overall lift (150mm)

4.8.5 Power supply: AC220V, total power 3.5KW.

4.9 Use of the environment:

4.9.1 Applicable ambient temperature: 13℃~35℃;

4.9.2 Applicable relative humidity: 55% ± 20

4.9.3 The ground should be flat and solid;

4.9.4 Surrounding ventilation;

4.9.5 Anti-vibration, anti-light environment

 

 

 

SKYLINE is a company specializing in test equipment development and service Professional company.(is a professional manufacturer of various quality testing instruments.)

The company has a group of experienced technical managers and efficient.
Professional after-sales service personnel, strong technical force, advanced technology, product expertise,Has a rigorous testing system, fine quality management and perfect pre-sales and after-sales service system.
Since its establishment, the company has resolutely won the good reputation of customers with its exquisite design, serious and pragmatic work spirit and good and thoughtful follow-up service. We will, as always, adhere to the principle of “integrity management”, “Quality first, Service oriented”, and provide the most professional and new customers with the latest products, excellent quality, reasonable price and perfect service network. The most efficient and ideal service.
Our major customers are BV, ITS, TUV, SGS, Hasbro and SASO, For these customer 100% testing instruments are supplied by SKYLINE and we are the continuous supplier for these lab. Since SKYLINE is a manufacturer design/develop with advanced technology and having well experienced Technicians which will provide high quality service after sale.

 

Hot Products

ISO 340 Conveyor Belt Vertical Burning Test Chamber 1. Scope: This tester is suitable for conveyor ...
Intelligent Automatic Touch-Screen Control Oxygen Index Tester I. Intelligent Full-automatic Touch ...
Building Material Flammability Test Furnace with Touch Screen Control Description The building ...
Building Material Flammability Test Furnace with Touch Screen Control Description The building ...
ISO5660 Cone Calorimeter Analysis Instrument For Heat Release Product introduction Cone Calorimeter ...
ISO5660 Cone Calorimeter Analysis Instrument For Heat Release Product introduction Cone Calorimeter ...