Home Companies Advanced Instruments Co.,Limited

BS-476-7 Surface Spread Flame Tester for Building Material Spread of Flame Test

Advanced Instruments Co.,Limited

Contact Us

[China] country

Trade Verify

Address: Hi-tech Developing Industrial Area, Liuyang City,Changsha,Hunan Province,China

Contact name:Sandy

Inquir Now

Advanced Instruments Co.,Limited

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

BS-476-7 Surface Spread Flame Tester for Building Material Spread of Flame Test

Country/Region china
City & Province changsha hunan
Categories Solar Chargers
InquireNow

Product Details

BS-476-7 Surface Spread Flame Tester

 

Introduction

BS 476 Part 7 specifies a method of test for measuring the lateral spread of flame along the surface of the specimen of a product orientated in the vertical position under opposed flow conditions, and a classification system based on the rate and extent of the spread of flame. It provides data suitable for comparing the end-use performances of essentially flat materials, composites or assemblies, which are used primarily as the exposed surfaces of walls and ceilings.

 

Feature

  • This Surface Flame Spread Apparatus consists of a radiation panel mounted vertically in a surround and supported on a framework.

  • ​The radiation panel is sullied with an gas-air mixture.

  • ​The radiation panel is 850mm square for a porous refractory type burner block designed to give efficient combustion of the air-gas-air mixture, with no flaming occurring on the face of the panel under operational conditions.

  • ​The radiation panel and its surround are supported on a framework so that the center of the panel is about 1250±100mm above floor level.

  • ​A specimen holder and a pilot flame arrangement mounted to one side of the apparatus.

  • ​The specimen holder is comprise a water-cooled steel frame with water-cooled face plates. The face plates is overlap the specimens by 20±2mm on their top and bottom edges and over the vertical edge adjacent to the radiation panel.

  • ​A spring loaded clamp is positioned to clamp the specimen against the face plates.

  • ​The portable water supply to the specimen holder make the maximum temperature does not exceed 35℃ at the outlet from the specimen holder.

  • ​The specimen holder assembly is located at 90±2° to the face of the radiation panel and in such as way that the faces of the top and bottom guides of the specimen holder are in the same plane as the inside face of the surround to the radiation panel.

  • ​The height of the specimen holder is hinged to allow it to be swung horizontally, away from the face of the radiation panel between tests, from the test position to the standby position and vice-versa.

  • ​The pilot burner is consist of a steel tube.

  • ​The gas and air supply lines to the radiation panel contain flow meters, pressure regulators, control valves and safety devices.

  • ​Heat Flux Meter: Range : 0 ~ 50 kw/m2; Surface emissivity :ɛ=0.95±0.05.

  • ​Dummy calibration board with holder, calibrated heat flux meter and mounting.

Installation requirements

Electrical230 volts Nominal 10 Amps
Ambient Temperature10°C to 35°C
Gas suppliesPropane and air compressor
Testing room400m3
Dimensions

1220 mm (W) x 550 mm (D) x 1920 mm (H)

Weight210KG
Applicable standardsBS476-7

 

Hot Products

Lateral Flame Spread Testing For Walls Surfaces Introduction Lateral Flame Spread Testing Equipment ...
Fire Propagation Index Testing Equipment for Laminated Foil BS476-6 FPT.pdf Introduction: BS 476-6 ...
ISO9239 FRPT.pdf Introduction: Critical Radiant Flux is the main parameters of the fire risk for ...
Introduction This Fire Test Equipment is developed base on the standard AS1530.2, test for ...
Introduction: The BS 476-12 Ignitability Tester is designed according to the BS476-12:1991. Method ...
Product Introduction The smoke toxicity test device (squirrel cage method) is applicable to the GB/T ...