Home Companies Advanced Instruments Co.,Limited

ISO 5659-2 Smoke Density Test Apparatus ASTM E662

Advanced Instruments Co.,Limited

Contact Us

[China] country

Trade Verify

Address: Hi-tech Developing Industrial Area, Liuyang City,Changsha,Hunan Province,China

Contact name:Sandy

Inquir Now

Advanced Instruments Co.,Limited

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

ISO 5659-2 Smoke Density Test Apparatus ASTM E662

Country/Region china
City & Province changsha hunan
Categories Solar Chargers
InquireNow

Product Details

NBS Smoke Density Test Chamber

Introduction

The Smoke Density Test Chamber has proved to be one of the most versatile fire testing instruments since its inception in the 1980s. It is the most widely accepted apparatus for the measurement of smoke from burning materials and measures specific optical density under flaming and non-flaming conditions. It is also used for the extraction of toxic gas.

 

 

Structure of Chamber

1, The NBS Smoke Density Test Machine is consist of cabinet, sample case, the radiation cone, ignition, light and measuring devices and other relevant control device component;
2, The structural design and control design considers the ergonomics; The test box is designed with full door design approach; lock design for easy one-time close the door; optimize operational processes;
3, The smoke density equipment has fully opened door for easy loading and unloading of samples and cleaning the box;
4, The front door hinge installation with Windows and window has block the activity window opaque visor to prevent light from entering the sealed box;
, The controller is located in the side of the box, easy to operate. When the door is closed,it does not affect the view controller;
6, Security flameout board is simple to replace with safer operation;
7, The smoke density test machine is easy cleaning and coating chemical resistance.

 

Combustion System
1, The heating cone: Power 2600W, input temperature range of 0 ~ 1000 ºC, can be stable within ± 2 ºC within 50 minutes, providing irradiance 10KW / m²-50KW / m².
2, The use of mass flow controllers and differential pressure sensor can improve the accuracy of piezometers and automatic leak test.
3, Ignition with automatic ignition devices; flame length 30mm±5mm; in accordance with standards prescribed blue flame with a yellow tip.


Smoke density measurement system
1, Smoke density and temperature are digital display, viewing more convenient, more accurate values.
2, Photodetector assembly includes a photomultiplier, amplified filters, shutters, filters, neutral density filter, a lens, an optical window, and other components.
3, The light source is 6.5V incandescent light sources.
4, The installation of optical cartridge box at the top, light accepted as side-on photomultiplier, light transmission rate of 0.001% accuracy can be achieved.
5, Achromatic lens is provided with ASTM E662 Smoke density test equipment.
6, ISO 5659-2 Smoke Box adopts Japan imported Photomultiplier tubes.
7, High-gain low-noise amplifier control circuit.

Technical Specification

1, Light transmittance measurement range: 0 ~ 100%; Resolution is 0.00001%;
2, Accuracy of measurement is less than ± 2.5%;
3, Light 6.5 V incandescent light; 2200+100k color temperature incandescent lamp;
4, Optical system for transmittance as linear response, measuring at least accuracy + / - 3%;
5, Photomultiplier tube filled with partial data acquisition precision 0.5%;
6, Heater input temperature 0 ºC ~ 1000 ºC, accuracy of plus or minus 2 ºC;
7, Import K type armoured thermocouple accuracy of 0.1 ºC;
8, Mouth thermopile type heat flow meter range is 0 ~ 80 kw/m2; The thermopile type heat flow meter, heat meter accuracy is 1%, repeatability and 0.5%;
9, Propane gas flow meter range: 0 ~ 100 ml/min. Minimum pressure of 3.5 kPa plus or minus 1 kPa;
10, Air flow meter range: 0 ~ 1000 ml/min.
11, Fan provides the negative pressure in the cabinet at least 0.5 kPa;
12, Enclosure bear greater than the atmospheric pressure at least 1.5 kPa;
13, Water pressure gauge 1.5 kPa (150 mm water column);
14, Wall temperature measurement range: 0 ~ 100ºC±1ºC;
15, Window heater power 9 W;
16, Test the pressure inside the warehouse scope: < 1.5 kPa;
17, Radiation power range: 0 ~ 50 kW/m2.

 

 

 

Hot Products

Lateral Flame Spread Testing For Walls Surfaces Introduction Lateral Flame Spread Testing Equipment ...
Fire Propagation Index Testing Equipment for Laminated Foil BS476-6 FPT.pdf Introduction: BS 476-6 ...
ISO9239 FRPT.pdf Introduction: Critical Radiant Flux is the main parameters of the fire risk for ...
Introduction This Fire Test Equipment is developed base on the standard AS1530.2, test for ...
Introduction: The BS 476-12 Ignitability Tester is designed according to the BS476-12:1991. Method ...
Product Introduction The smoke toxicity test device (squirrel cage method) is applicable to the GB/T ...