Dynamic Characteristics Test Kit

 
I.Introduction

CBA-II Circuit Breaker Test Kit is designed to meet the need of onsite test the dynamic characteristics of High-Voltage Circuit Breakers . It takes the ARM7 unit for core to sample, process and output; the main characteristic is that it’s operated in alt. It has many advantages such as intelligence, multi-function, accurate data, strong anti-jamming, easy operation, small size, light weight ,beautiful appearance, etc.

It can test the Circuit Breakers as following: indoors or outdoors Circuit Breakers with less oil or more oil, vacuum Circuit Breakers, SF6 Circuit Breakers and so on.

 

 

II.Features
  • 12 contacts’ closing time and opening time
  • Reclosing time
  • Opening or closing’s asynchronism
  • Springing time or springing times
  • Clearance between open contacts/gaps, over-travel, over-shoot and springback
  • Speed at instant of contacts touching (separating)
  • Opening (Closing) max speed
  • Opening (Closing) average speed
  • Display and Print V-S curve
  • Operating current curve
  • Closing resistance measurement
  • Large color screen in touch operating

 

III.Technical specifications

1TimeSimultaneity measure Contacts:≤12
range:0~6s
resolution ratio:0.01ms
2Travelrange:< 250mm
resolution ratio:0.01mm
3ErrorTime measure error:±0.5%
Travel measure error:±1mm
4Speed measure range0~20m/s
5Internal PowerOutput Voltage:30V~260V error:1%
Output Current:0~20A
6Operating conditionOperating voltage:AC220V±10 %
Frequency:50Hz
Power dissipation:≤60w
Ambient temperature:0~40℃
Ambient humidity:≤90%RH
7Size460X340X200 mm3
8Weight7kg

 

 

Package List of CBA-II Dynamic Characteristics of High-Voltage Circuit Breaker Test Kit

CBA-II Circuit Breaker Test Kit1 unit
Seniors1 set
User manual1 copy
Test cables1 set

 

Hot Products

ISO9239 FRPT.pdf Introduction: Critical Radiant Flux is the main parameters of the fire risk for ...
Introduction This Fire Test Equipment is developed base on the standard AS1530.2, test for ...
Introduction: The BS 476-12 Ignitability Tester is designed according to the BS476-12:1991. Method ...
Product Introduction The smoke toxicity test device (squirrel cage method) is applicable to the GB/T ...
Roofing Fire Test Equipment with Burning Brands by ENV 1187 Test 1 and ISO 12468-1 Product ...
Product Introduction Smoldering characteristic test furnace is mainly used in the fire performance ...