Home Companies Advanced Instruments Co.,Limited

Transformer Test Equipment for Tan Delta Tester Dissipation Factor Test

Advanced Instruments Co.,Limited

Contact Us

[China] country

Trade Verify

Address: Hi-tech Developing Industrial Area, Liuyang City,Changsha,Hunan Province,China

Contact name:Sandy

Inquir Now

Advanced Instruments Co.,Limited

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Transformer Test Equipment for Tan Delta Tester Dissipation Factor Test

Country/Region china
City & Province changsha hunan
InquireNow

Product Details

Transformer Tan Delta Test Equipment

 

 

I.Introduction:

TDT Tan Delta Test Equipment is an integrated structure, there is a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor built-in;

This Loss Angle Test Equipment can also supply high voltage source for testing.

Frequency can be changed to 50Hz, 47.5Hz52.5Hz,45Hz55Hz, 60Hz, 57.5Hz62.5Hz, 55Hz65Hz; thus, this power factor tester can avoid interference of power frequency;

This dissipation factor test equipment can also be used as power supply;

 


II.Specifications:

No.Item NameTransformer Tan Delta Test Loss Angle Test Dissipation Factor Test Equipment
1Use conditions-15℃~40℃RH<80%
2Anti-interferenceFrequency conversion
3PowerAC 220V±10%Allowable generator
4High output0.5KV~10KVEvery 0.1kV
Precision2%
Maximum current200mA
Capacity2000VA
5Self-excited powerAC 0V~50V/15A

45HZ/55HZ 47.5HZ/52.5HZ

55HZ/65HZ 57.5HZ/62.5HZ

Automatic double frequency

6Resolving powertgδ: 0.001%Cx: 0.001pF
7Precisiontgδ:(Reading*1.0%+0.040%)
Cx :(Reading*1.0%+1.00PF)
8Measuring rangetgδUnlimited
Cx15pF < Cx < 300nF
 10KVCx < 60 nF
 5KVCx < 150 nF
 1KVCx < 300 nF
CVT testCx < 300 nF
9CVT range10~10000
accuracy0.1%
Resolving power0.01
10Dimension350*270*270mm
11Memory sizeThe 200 group supports U disk data storage
12Weight

28 Kg

 

Spares of Transformer Tan Delta Test Loss Angle Test Dissipation Factor Test Equipment

 

 

NO.NameQuantityUnit
1Main Unit1Set
2Accessory case1PC
3Red HV test cable1Root
4Black LV test cable1Root
5AC220V power cable1Root
6

CVT self-excited power cable (attached)

 

1Root
7

Ground wire

 

1Root
8Fuse, printer paperSpare 
 

Hot Products

ISO9239 FRPT.pdf Introduction: Critical Radiant Flux is the main parameters of the fire risk for ...
Introduction This Fire Test Equipment is developed base on the standard AS1530.2, test for ...
Introduction: The BS 476-12 Ignitability Tester is designed according to the BS476-12:1991. Method ...
Product Introduction The smoke toxicity test device (squirrel cage method) is applicable to the GB/T ...
Roofing Fire Test Equipment with Burning Brands by ENV 1187 Test 1 and ISO 12468-1 Product ...
Product Introduction Smoldering characteristic test furnace is mainly used in the fire performance ...