Home Companies Kingsine Electric Automation Co., Ltd.

7 Phase Voltage Protection Relay Tester / Overcurrent Test K3066Li

Contact Us

Trade Verify

Address: 6/F, Block 4-CD, TianAn Cyber Park, Futian District, Shenzhen 518048,.China

Phone: 86-00852-23892981

Contact name:Amy

Kingsine Electric Automation Co., Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

7 Phase Voltage Protection Relay Tester / Overcurrent Test K3066Li

City & Province shenzhen guangdong
Categories Used Measuring & Analysing Instruments

Product Details

 

7 Phase Voltage Protection Relay Test System / Overcurrent Test K3066Li

 

Unique power switch and amplifier technology
4 pairs Binary output
Power:2000VA
6-phase AC (L-N)

 

 

 Friendly PC software for easy operation!

K30 series relay tester is extremely design for overseas user, with Friendly PC software as your need, unique features and functions helps you all the way!

 

1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal ;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis;
 
 Technical Data of K3066Li

 

Voltage generators

Setting 

Range

7-phase AC (L-N)

7 x 0 ... 300 V 

2-phase AC (L-L)

2 x 0 ... 600 V

Power

7-phase AC (L-N)

7 x 110VA,  at 0 ... 300 V

2-phase AC (L-L)

2 x 220VA,  at 0 ... 600 V

Accuracy

<0.07% reading + 0.03% range guaranteed 

at 0 ... 300 V

<0.02% reading + 0.01% range typical 

at 0-300V

Resolution

1mV

Current generators

Setting 

Range

6-phase AC (L-N)

6 x 0 ... 30 A

3-phase AC (2L-N)

3 x 0 ... 60 A (Group A II B)

1-phase AC (3L-N)

1 x 0 ... 180 A 

Power

6-phase AC (L-N)

6x 450VA , at 0 ... 30A 

3-phase AC (2L-N)

3x 600VA,  at 0 ... 60A (Group A II B) 

1-phase AC (3L-N)

1 x 1500 VA,  at 0 ... 180A (Max.)

Accuracy

<0.07% reading + 0.06% range guaranteed at 0-30A 

<0.02% reading + 0.02% range typical at 0-30A

Resolution

1mA

Generators,  general

Frequency

Range

0 ... 1000 Hz

Accuracy / drift

Error < 0.001Hz at 10 ... 65Hz,

Error < 0.01Hz  at 65Hz...450Hz

Error < 0.02Hz  at 450Hz...1000Hz

Resolution

0.001Hz

Phase

Range

- 360° ... +360°

Accuracy / drift

Error < 0.2 °

Resolution

0.1°

Timer

Range

Infinite

Accuracy / drift

Error<0.1ms

DC generators

Voltage ranges

0 ... 300V/110W

Current ranges

0 ... 20A/300W

Accuracy

<0.07% reading + 0.03% range guaranteed at 0-300V 

<0.04% reading + 0.02% range typical at 0-300V

<0.14% reading + 0.06% range guaranteed at 0-20A

<0.05% reading + 0.02% range typical at 0-20A

Resolution

1mA; 1 mV

Aux DC Supply

Range

0...300V/110W

Binary inputs

Number

8 pairs

Compatible Voltage

10V ... 250V  DC

Binary outputs

Number

4 Pairs

Capacity

250V/3A  AC/DC

Synchronization

Synchronization mode

GPS

Harmonic

Harmonic overlap times

2 ... 20 times

Power supply

Nominal input voltage

85V…264V ac

Power

2000VA

Nominal frequency

47Hz….65Hz

Environmental conditions

Operation temperature

-5°C ... 55 °C

Storage temperature

-20°C ... 75 °C

Humidity range

5% ... 90 %,  non-condensing

Weight

17.5 KG

Dimensions

480(D)×140 (W)×360 (H) mm

PC connection

RJ45

 

K30 Series Protection Relay Test Set:

 

Model

Channels

AC Outputs

K3063i / K3063Li

10 output channels

6*30A/3*40A/4*300V

K3030i / K3030Li

7 output channels

3*30A/4*300V

K3066

13 output channels

6*20A/3*40A/7*130V

K3063

10 output channels

6*20A/3*40A/4*130V

K3040

7 output channels

3*40A/4*130V

K3030

7 output channels

3*30A/4*130V

 

Major Functions:

 

Items

IEEE(R) No.

Synchronization relay

 

Fault transplay

 

GPS Synchronization 

 

Overcurrent relays

50/76

Inverse time overcurrent relays

51

Undercurrent relays

37

Ground fault relays

50

Directional overcurrent relays

67

Directional ground fault relays

67N

Overvoltage relays

59

Undervoltage relays

27

Directional voltage relays

91

Directional power relays

32

Power factor relays

55

Differential protection (differential circuits)

87

Distance protection equipment (phase by phase)

21

Negative sequence overcurrent relays

46N

Motor overload protection

51/86

Automatic reclosing devices 

79

Tripping relays

94

Voltage regulating relays

 

Overimpedance relays,  Z>

 

Underimpedance relays,  Z

 

Time-delay relays

 

 


 

Hot Products

Manual 2000VA Protection Relay Testing Set K3030L , End to End Test 1.Easy test 2.operation menu, ...
6.4 LCD Screen Protection Relay Testing K1066 , 8 Pairs Binary Input Binary Inputs Number: 8 pairs ...
Protection Relay Testing / 50 Overcurrent Relay 3066i Relay protection test devices 1.Easy test 2...
GPS for orientation navigation , timing & frequency calibration High-precision measurement 12V DC ...
KF920 Fiber Universal Relay Test Set Features: Suitable testing for all kinds of Electro-magnetics ...
Automation Universal Relay Test Set K68i, Single Phase Advance software functions (optional for ...