Flexible Copper Insulated Electrical Wire H05Z K H07Z K BS EN 50525-3-41 Cable

 

APPLICATION

LSZH panel wiring for appliances with maximum operating temperatures of 90°C, and generally in areas (such as public and government buildings) where smoke and toxic fumes may cause a threat to life and equipment. The cables produce no corrosive gases when burnt which is particularly important where electronic equipment is installed.

 

 

CONSTRUCTION

Conductor

Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)

 

 

Insulation

LSZH (Low Smoke Zero Halogen) Type EI5 thermosetting insulation according to BS EN 50363

 

 

CABLE STANDARDS

BS EN 50525-3-41 (previously BS 7211 Table 3 and 4b CENELEC HD22.9), BS EN/IEC 60332-1-2,

BS EN/IEC 50267-2-1, BS EN/IEC 60754

 

 

The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.

Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.

 

 

CHARACTERISTICS

Voltage Rating (Uo/U)

H05Z-K - 0.5mm2 to 1mm2: 300/500V H07Z-K - 1.5mm2 to 240mm2: 450/750V

 

 

Temperature Rating

-25°C to +90°C

 

 

Minimum Bending Radius

Up to 35mm2: 4 x overall diameter 50mm2 and above: 6 x overall diameter

 

 

Insulation Colour

 Red  Black  Blue  Orange  White  Yellow Green/Yellow  Grey  Brown  Violet  Pink

 

 

DIMENSIONS

H05Z-K

 

Sunwin PART NO.

NOMINAL CROSS SECTIONAL AREA

mm²

THICKNESS OF INSULATION

mm

NOMINAL OVERALL DIAMETER

MINIMUM RESISTANCE OF INSULATION AT 90°C

Mohms/km

NOMINAL WEIGHT

kg/km

Lower Limit

mm

Upper Limit

mm

A2Z*00500.50.61.92.40.0158.7
A2Z*00750.750.62.22.80.01111.3
A2Z*001010.62.42.90.0113.9

 

H07Z-K

 

Sunwin PART NO.

NOMINAL CROSS SECTIONAL AREA

mm²

NOMINAL THICKNESS OF INSULATION

mm

NOMINAL OVERALL DIAMETER

MINIMUM RESISTANCE OF INSULATION AT 900C

Mohms/km

NOMINAL WEIGHT

kg/km

Lower limit

mm

Upper limit

mm

A2Z*00151.50.72.83.50.01019.3
A2Z*00252.50.83.44.30.00930.9
A2Z*004040.83.94.90.00744.9
A2Z*006060.84.45.50.00664.2
A2Z*0101015.77.10.0056108.2
A2Z*0161616.78.40.0046163.4
A2Z*025251.28.410.60.0044248.1
A2Z*035351.29.712.10.0038340.6
A2Z*050501.411.514.40.0037484.2
A2Z*070701.413.216.60.0032671
A2Z*095951.615.118.80.0032895.8
A2Z*1201201.616.720.90.00291111.1
A2Z*1501501.818.623.30.00291389.2
A2Z*185185220.625.80.00291724.1
A2Z*2402402.223.529.40.00282225.4

 

*Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A2ZRD0015 = 1.5mm2 Red

 

 

Colour Codes

 

COLOURBlackBlueGreyGreen/ YellowOrangeRedPinkYellowVioletBrownWhite
CODEBKBLGRGYORRDPKYWVIBRWH

 

CONDUCTORS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

 

NOMINAL CROSS SECTIONAL AREA

mm²

MAXIMUM DIAMETER OF WIRES IN CONDUCTOR

mm

MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC

Plain Wires

ohms/km

0.50.2139
0.750.2126
10.2119.5
1.50.2613.3
2.50.267.98
40.314.95
60.313.3
100.411.91
160.411.21
250.410.78
350.410.554
500.410.386
700.510.272
950.510.206
1200.510.161
1500.510.129
1850.510.106
2400.510.0801

The above table is in accordance with BS EN 60228 (previously BS 6360)

 

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity

 

NOMINAL CROSS SECTIONAL AREA

mm²

REFERENCE METHOD A (ENCLOSED IN CONDUIT IN THERMALLY INSULATING WALL ETC)

Amps

REFERENCE METHOD B (ENCLOSED IN CONDUIT ON A WALL OR IN A TRUNKING ETC)

Amps

REFERENCE METHOD C (CLIPPED DIRECT)

Amps

REFERENCE METHOD F

(IN FREE AIR OR ON A PERFORATED CABLE TRAY ETC HORIZONTAL OR VERTICAL ETC) TOUCHING

Amps

REFERENCE METHOD G (IN FREE AIR) SPACED BY ONE CABLE DIAMETER

Amps

2 Cables Single-Phase AC or DC or

3 Cables Three-Phase AC flat

 

 

2 Cables Single-Phase AC or DC

 

 

3 or 4 Cables Three-Phase AC

 

 

2 Cables Single-Phase AC or DC

 

 

3 or 4 Cables Three-Phase AC

 

2 Cables Single-Phase AC or DC flat or touching

 

3 or 4 Cables Three-Phase AC flat and touching or trefoil

 

2 Cables Single-Phase AC or DC

flat

 

3 Cables Three-Phase AC

flat

 

3 Cables Three-Phase AC

trefoil

 

 

 

Horizontal

 

 

 

Vertical

1141317151917.5-----
1.5191723202523-----
2.5262331283431-----
4353142374641-----
6454054485954-----
10615475668174-----
1681731008810999-----
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
150318285393342476436504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719

Ambient temperature: 30ºC

Conductor operating temperature: 90ºC

 

  1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see also Regulation 512.1.2).

 

  1. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for 70ºC thermoplastic insulated cables (Table 4D1A) must be used (see Regulation 523.1).

 

The above table is in accordance with Table 4E1A of the 17th Edition of IEE Wiring Regulations.

 

Voltage Drop

 

NOMINAL CROSS SECTIONAL AREA

mm²

2 CABLES DC

mV/A/m

2 CABLES SINGLE-PHASE AC

mV/A/m

3 OR 4 CABLES THREE-PHASE AC

mV/A/m

Reference Methods A and B

(enclosed in conduit or trunking)

Reference Methods C, F and G (clipped direct, on tray or in free air)

Reference Methods A and B

(enclosed in conduit

or trunking)

Reference Methods C, F and G

(clipped direct, on tray or in free air)

 

Cable Touching

 

Hot Products

SWA Low Voltage Armored Cable / Underground Low Voltage Control Cable Low Voltage Armored Cable ...
Multi Core Low Voltage Power Cable For Electricity Supply BS 5467 Standard Low Voltage Power Cable ...
EN/IEC 60332-1 Low Voltage Electrical Wire , Copper LV Power Cable Low Voltage Electrical Wire ...
XLPE/SWA/PVC Low Voltage Power Cable With Solid Copper Conductor 0.6/1kV Low Voltage Power Cable ...
BS 5467 Single Core Power Cable / Auxiliary Control Xlpe Armoured Cable Single Core Power Cable ...
Traffic Signal Low Voltage Power Cable BS 6346 Standard Customized Length Low Voltage Power Cable ...