318A / BS 6004 Arctic Grade Wire Stranded Conductor Blue Brown Green Yellow

 

APPLICATION

Arctic grade PVC cords manufactured to BS 6004 are designed to withstand severe external temperatures and will remain flexible at temperatures down to -40°C. Making them particularly suitable for outdoor applications and for use where flexibility is required at sub zero temperatures. At normal temperatures the cable is very flexible, offering some of the characteristics usually found in elastomeric cables.

 

 

CONSTRUCTION

Conductor

Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)

 

 

Insulation

Arctic grade PVC (Polyvinyl Chloride) Type TI4 according to BS EN 50363

 

 

Sheath

Arctic grade PVC (Polyvinyl Chloride) Type 10 according to BS 7655

 

 

CABLE STANDARDS

BS 6004 (previously BS 7919 Table 44), BS EN/IEC 60332-1-2

 

 

The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.

Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.

 

 

CHARACTERISTICS

Voltage Rating (Uo/U) 300/500V

 

 

Temperature Rating

Fixed: -40°C to +60°C

 

 

Minimum Bending Radius

Fixed: 6 x overall diameter

 

 

Core Identification

  1. core: Blue Brown
  2. core: Blue Brown Green/Yellow

 

Sheath Colour

Blue Yellow

 

 

DIMENSIONS

 

Sunwin PART NO.NO. OF CORES

NOMINAL CROSS SECTIONAL AREA

mm²

NOMINAL THICKNESS OF INSULATION

mm

NOMINAL THICKNESS OF SHEATH

mm

NOMINAL OVERALL DIAMETER

mm

NOMINAL WEIGHT

kg/km

A5A2075*1R20.750.60.86.255
A5A2010*1R210.60.86.461
A5A201*1R21.50.70.87.483
A5A202*1R22.50.819.2130
A5A204*1R240.81.110.4176
A5A206*1R260.81.211.3299
A5A3010*1R310.60.86.873
A5A301*1R31.50.70.98.1105
A5A302*1R32.50.81.110163
A5A304*1R340.81.211.3224
A5A306*1R36.00.81.212.7299

* Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A5A2075B1R = 0.75mm2 Blue

 

 

Colour Codes

 

COLOURBlueYellow
CODEBY

 

 

CONDUCTORS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

 

NOMINAL CROSS SECTIONAL AREA

mm²

MAXIMUM DIAMETER OF WIRES IN CONDUCTOR

mm

MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC

Plain Wires

ohms/km

0.750.2126
10.2119.5
1.50.2613.3
2.50.267.98
4 0.314.95
60313.30

 

 

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity

NOMINAL CROSS SECTIONAL AREA

mm²

CURRENT CARRYING CAPACITY AT 30ºC

Single-Phase AC

Amps

Three-Phase AC

Amps

0.7566
11010
1.51616
2.52520
43225
64840

 

 

Voltage Drop

 

NOMINAL CROSS SECTIONAL AREA

mm²

DC OR SINGLE-PHASE AC

mV/A/m

THREE-PHASE AC

mV/A/m

0.756254
14640
1.53227
2.51916
41210
687

 

Conductor operating temperature: 60ºC

The above table is in accordance with Table 4F3B of the 17th Edition of IEE Wiring Regulations.

 

 

DE-RATING FACTORS

60ºC Thermoplastic or Thermosetting Insulated Cords

 

AMBIENT TEMPERATURE35ºC40ºC45ºC50ºC55ºC
DE-RATING FACTOR0.910.820.710.580.41

The above table is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.

 

 

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.

Hot Products

SWA Low Voltage Armored Cable / Underground Low Voltage Control Cable Low Voltage Armored Cable ...
Multi Core Low Voltage Power Cable For Electricity Supply BS 5467 Standard Low Voltage Power Cable ...
EN/IEC 60332-1 Low Voltage Electrical Wire , Copper LV Power Cable Low Voltage Electrical Wire ...
XLPE/SWA/PVC Low Voltage Power Cable With Solid Copper Conductor 0.6/1kV Low Voltage Power Cable ...
BS 5467 Single Core Power Cable / Auxiliary Control Xlpe Armoured Cable Single Core Power Cable ...
Traffic Signal Low Voltage Power Cable BS 6346 Standard Customized Length Low Voltage Power Cable ...