MTL 5541 Repeater Power Supply 20-35VDC DIN Rail

Country/Region china
City & Province shenzhen
InquireNow

Product Details

Quick Detail of Repeater Power Supply

Manufacturer : MTL Instruments
Product No. : MTL5541
Product Type : Repeater Power Supply
Number of channels : One
Location of transmitter : Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A hazardous location
Safe-area circuit ripple : < 50µA peak-to-peak
Transfer accuracy at 20°C : Better than 15µA
Temperature drift : < 0.8µA/°C
Response time : Settles to within 10% of final value within 50µs
Communications supported : HART® (terminals 1 & 2 only)
LED indicator : Green: power indication
Maximum current consumption (with 20mA signal) : 51mA at 24V
Dimensions (LxWxH) : 1.58 cm x 10.98 cm x 12.36 cm
Weight : 0.11 Kg

 

Description of Repeater Power Supply

The MTLx541 provides a fully-floating dc supply for energising a conventional 2- or 3-wire 4/20mA transmitter, which is located in a hazardous area, and repeats the current in another floating circuit to drive a safe-area load. For HART 2-wire transmitters, the unit allows bi-directional communications signals superimposed on the 4/20mA loop current. Alternatively, the MTLx541S acts as a current sink for a safe-area connection rather than driving a current into the load.

 

Specification of Repeater Power Supply

Hazardous Area InputSignal range: 0-24 mA (including over-range); Transmitter voltage: 16.5 V at 20 mA
Safe Area OutputSignal range: 4-20 mA; Under/over-range: 0-24 mA; Load resistance: 0 to 360Ω @ 24 mA, or 0 to 450Ω @ 20 mA; Current sink: 600Ω max.; Maximum voltage source: 24 VDC; Output resistance: > 1 MΩ
Power Requirement20-35 VDC.
Response TimeSettles to within 10% of final value within 50 µs
Current Consumption51 mA @ 24V
Maximum Power Dissipation0.7 W @ 24 VDC, 1.0 W @ 24 VDC
Isolationn 250 V RMS, tested at 1500 V RMS minimum, between safe-area and hazardous-area terminals; 50 V between safe-area circuits and power supply
Transfer Accuracy at 68°F (20°C)Better than 15 µA
LED IndicatorGreen: Power indication
Temperature LimitsOperating: -6 to 140°F (-20 to 60°C); Storage: -40 to 176°F (-40 to 80°C)
Temperature Drift< 0.8µA/°C
Humidity5 to 95% RH
MountingT-section 35 mm DIN rail (7.5 or 15 mm) to EN 50022
TerminalsAccommodate up to 2.5 mm2 stranded or single-core
Safety DescriptionVo= 28 V, Io= 93 mA, Po= 651mW, Um= 253 RMS or DC
Weight150g

 

 

Advantage of Our Team

  • Best possible prices and delivery time
  • Long time experience in the field
  • Well trained staff
  • Own warehouse facilities
  • Best relationships with branch office of manufacture
  • Flexible and individual service for you
  • Cheap and safe forwarder for shipments (air)

 

 

Hot Products

Proline Promag PTFE Liner Electromagnetic Flowmeter 5P2B1F-AAACCAEA1K0A​ 5P2B1F-AAACCAEA1K0A Proline ...
Proline Promass Coriolis Flowmeter 8F2B80-BBEEBASAABSA+AADCJBJC 8F2B80-BBEEBASAABSA+AADCJBJC Proline ...
230VAC E&H Instrument CM442 CM442-AAM1A2F010A+AA Transmitter CM442-AAM1A2F010A+AA 1-/2-Channel ...
CLS21D E&H Instrument Digital Conductivity Meter Condumax CLS21D-C1E1 Digital Conductivity Sensor ...
25bar 2.5MPa E&H Instrument Absolute And Gauge Pressure Cerabar PMP23 PMP23-AA1U1RBWSJ+QJ Absolute ...
HART 4 Channel Transmitter Liquiline CM444 Enclosed Cable Entry CAM21A3FG11BAA 4-Channel Transmitter ...