Shenzhen Chuangyin Co., Ltd. |
Verified Suppliers
|
|
Electric voltage transformer/voltage Sensor/LPVT (Cable Connector type)
1 Apply to
≤24kV busbar connecting system with screened separable connector
Application
♦ Voltage sensor apply to voltage measurement of connecting busbar with screened cable connector in medium voltage gas insulation switchgear of smart grid;
♦ Voltage sensor should be installed on the back of the screened cable connector to replace the position of original rear connector.
3. Technical Data:
Model | CY-EVTDC3-10 | CY-EVTDC3-20 | |
Max. system voltage | 12kV | 24kV | |
Insulation level | 12/42/75kV | 24/50/125kV | |
lighting impulse withstand voltage | 75kV | 125kV | |
Rated voltage ratio | phase voltage | (10000/V3)/ C3.25/V3) V | (20000/V3)/ (3.25/V3) V |
zero sequence voltage | (10000/V3)/ (6.5/3) V | (20000/V3)/ C6.5/3) V | |
Phase voltage- Measuring Accuracy | 0.5 | 0.5 | |
zero sequence voltage-Protection Accuracy | 1 (3P) | 1 C3P) | |
Burden (load resistance) | 10MQ | ||
Rated voltage factor | 1.2Un continue /1.9Un/8h | ||
Frequency | 50/60 Hz | ||
Operating temperature | -40°C to +70°C | ||
LPVT type | Phase voltage + Zero sequence VT | ||
Installation method and size | rear connector type voltage transformer | ||
I EC rear cable connector type 15kV/630A | IEC rear cable connector type 24kV/630A | ||
Standard | GB/T 20840.7 (GB/T 20840.6) C 60044-7 (IEC 61869-6) | ||
Connecting type | aviation plug—lead terminal | ||
Connecting cable | RVSP Shield line L = 3 m (length can be customized) |
4. Outline Drawing: