Home Companies Shenzhen Chuangyin Co., Ltd.

Medium Voltage Separable Connectors 200 A 25 kV Class Loadbreak Elbow Connector T Type

Shenzhen Chuangyin Co., Ltd.

Contact Us

[China] country

Trade Verify

Address: 1st Floor, B Block, Jiada R&D Building, Nanshan, Shenzhen, China

Contact name:Dieky Lin

Inquir Now

Shenzhen Chuangyin Co., Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Medium Voltage Separable Connectors 200 A 25 kV Class Loadbreak Elbow Connector T Type

Country/Region china
City & Province shenzhen guangdong
Categories Other Roadway Products
InquireNow

Product Details

Medium Voltage Separable Connectors 200A 25 kV Class Loadbreak Elbow Connector Tee Type

 

Application

Chuangyin® Tee Connector is widely applicable for connecting a power cable to two in-line bushing interfaces. It designed to terminate underground cables to high-voltage apparatus such as transformers, switchgear, junction box. This allows the use of the fault indicators (energized indicator), and provides a hotstick operable.

Cable Section: 25 to 400 mm2

The interface complys with IEEE standard 386, 8.3/14.4 kV, 600 A deadbreak design.

 

Features

Made of high quality EPDM rubber

Connecting a power cable to two in-line bushing interfaces

Fully shielded, submersible connection for deadbreak system

With/Without test point

100% factory tested

In compliance with IEC standard 386

 

Construction

1. Bolt

2. Lug

3. Semi-conducting Shield

4. Insulating Layer

5. Adapter

6. Insulated Cap

7. Insulating Plug

8. Semi-conducting Insert

9. Test Point

10. Grounding Tab

Technical Data

ItemParameters
Voltage Class15 kV
Voltage Rating8.3/14.4 kV
AC Withstand Voltage 5min39 kV
DC Withstand Voltage 15min35 kV
Partial Discharge15 kV, ≤10 pC
BIL95 kV
Thermal Current23 kA, 2 s
Dynamic Current84 kA, 10 ms
Cable Section25 to 400 mm2

Kit Contents

T-Body Connector

Insulating Plug

Insulated Cap

Adapter

Lug

Bolt

Wipers

Silicone Grease

Installation Tools

Installation instruction

Certificate

 

Ordering Instructions

Part NumberCable Section (mm²)Diameter over Insulation (mm)Code
CYS-A(S)T-15/600-252516 to 17.8A
CYS-A(S)T-15/600-353517 to 19B
CYS-A(S)T-15/600-505018 to 20B
CYS-A(S)T-15/600-707020 to 21.4C
CYS-A(S)T-15/600-959521.6 to 23.1C
CYS-A(S)T-15/600-12012023 to 24.6D
CYS-A(S)T-15/600-15015024.4 to 26.1D
CYS-A(S)T-15/600-18518525.8 to 27.8E
CYS-A(S)T-15/600-24024028 to 30E
CYS-A(S)T-15/600-30030030.4 to 32.3F
CYS-A(S)T-15/600-40040033 to 35.4G

 

Hot Products

52kV outdoor MV PT epoxy resin full-closed for measuring and protective relaying 50/60Hz Chuangyin ...
Chuangyin Voltage Transformer-JDZW1-12R Description: This product is fully enclosed outdoor single...
36kV outdoor MV VT epoxy resin single phase for measuring and protective 50/60 Hz Chuangyin Voltage ...
17.5kV outdoor MV PT epoxy resin single phase for measuring and protective 50/60 Hz Chuangyin ...
17.5kV outdoor MV PT epoxy resin single phase double-pole for measuring and protective 50/60 Hz ...
36kV outdoor MV PT epoxy resin single-pole for measuring and protective 50/60 Hz Chuangyin Voltage ...