Home Companies Shenzhen Wisdomlong Technology CO.,LTD

Ge Fanuc IC660BBS102 , 115 VAC / 125 VDC Isolated I/O Block with eight circuits

Shenzhen Wisdomlong Technology CO.,LTD

Contact Us

[China] country

Trade Verify

Address: 23E BlockB,Lushan Building,Chunfeng Road,Luohu District,Shenzhen,518001,China

Contact name:Eva

Inquir Now

Shenzhen Wisdomlong Technology CO.,LTD

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Ge Fanuc IC660BBS102 , 115 VAC / 125 VDC Isolated I/O Block with eight circuits

Country/Region china
City & Province shenzhen guangdong
Categories Tool Processing Services
InquireNow

Product Details

Ge Fanuc IC660BBS102 , 115 VAC / 125 VDC Isolated I/O Block with eight circuits

Product Description


The IC660BBS102 is a 115 VAC / 125 VDC Isolated I/O Block with eight circuits and Failed Switch Diagnostics by GE Fanuc. The IC660BBS102 is reported to continuously withstand 250 VAC/VDC between any group or ground or between any two groups. The block has a transient rating of 2000V peak for 10 seconds. Some configuarble features include AC/DC circuit voltage, defaults for output power-ups, CPU redundancy, a selectable input filter type ranging from 10mS to 100mS, capability for output pulse test, and module control for bus switching.

 

The block performs diagnostic tests that detect overload and no overload, I/O power loss on pairs of circuits, over-temperature, and open wire for tristate inputs. As long as terminals 5 and 6 are recieving power, the isolated I/O block should operate. Temperatures in excess of 100°C trigger an OVERTEMPERATURE message and turns off the circuit to protect the internal electronics of the unit. The short circuit level sensor at the switching device protects the output circuits. Outputs are configured to report No-Load conditions for a new block. Genius I/O blocks are considered "open equipment" and must be installed in a protective enclosure, clean and free of airborne contaminants and with adequate cooling airflow. The block can be mounted right side up, or upside down. Leave at least 2 inches of space between blocks. The block’s mounting screws must not be used as the only means of grounding the block.

The IC660BBS102 block is fully compatible with handheld monitor IC660HHM501 and any GE Fanuc bus controller. Blocks numbered IC660CBS100, 1C660BBS100, and IC660BBS101 are backward compatible with previous versions of this Genius I/O block. Terminal assembly model IC66*TSS100E is not compatible with earlier versions of the block. During field wiring, all terminal blocks can accommodate one AWG #12 or two AWG #14 wires. Terminals labeled 1 to 4 can accommodate ring terminals measuring up to 0.27 inches. Recommended torque for all terminals is 6 inches/lb.


Technical Specifications


Rated Voltage:115 VAC / 125 VDC
# of Points:8
Input Voltage Range:93 - 132 VAC
Output Voltage Range:105 - 132 VDC
Load Current per Point:2.0 Amps
Points per CommonFour Groups of 2
 

 

 

Technical Information

Specifications

 

Block Type:

115VAC / 125VDCIsolatedI / OBlock: Terminal Assembly Only: ElectronicsAssemblyOnly:

115VAC / 125VDCIsolatedI / OBlock,NoFailed Switch: Terminal Assembly Only:

ElectronicsAssemblyOnly:

8 ckt isolated input / output in 4 isolated pairs IC660BBS102, replaces IC660BBS100 IC660TSS100

IC660EBS100

IC660BBS103, replaces IC660BBS101 IC660TSS100

IC660EBS101

Size (height x width x depth):

Weight:

LED’s (I/O Block): LED’s (each circuit): Block to Block Isolation: HeatDissipation:

8.83” (22.44cm) x 3.50” (8.89cm) x 3.94” x (10.00cm)

4 lbs. (1.8 kg)

Unit OK, I / OEnabled On logic side of switch 1500 V

16.8W max. with 8 inputs on, 45.6W max. with 8 outputs at 2 amps

Operating Temperature Storage Temperature Humidity

Vibration

–0 to +60C (32 to +140F)

–40 C (–40 to +212F)

5% to 95% (non–condensing)

5–10 Hz 0.2” (5.08mm) displacement, 10–200 Hz at 1G

Required control power (block only):

Operating voltage (four sources): Frequency/ripple:

Power supply dropout time:

8 Wattsmaximum

93–132 VAC105–132 VDC

47–63 Hz10% max. ripple

1 cycle10mS

Input Characteristics:

Non–tristate input, OFF state:

Minimum voltage across input device (IN to H) Maximum leakage through input device

Non–tristate input, ON state:

Maximum voltage across input device (IN to H) Maximumswitchcurrent threshold

Tristate input:

OFF, acceptable voltage across input device (IN to H) ON, maximum voltage across input device (IN to H)

Input load network: Resistor to N

Capacitor to H: for blocks BBS100 and BBS101 Capacitor to H: for blocks BBS102 and BBS103

Input processing time (typical)

Selectable input filter times Inputdiagnostics

For ACFor DC

60 VRMS70 VDC

1 mA2 mA

20 VRMS35 VDC

6 mA RMS5 mA

16 VRMS–40 VRMS16 VDC–35 VDC

4 VRMS3.5 VDC

13K ohms13K ohms

.22 ïf.22 ïf

.1 ïf.1 ïf

2mS + filter0.8mS + filter

10 to 100mS in 10mS increments

Open Wire, Overtemperature, Loss of I / O Power, Failed Switch

OutputCharacteristics: Output current (steady state) Maximum inrush current Output Leakage:

Current at 0 volt output: for blocks BBS102 and 103 Current at 0 volt output: for blocks BBS100 and 101 Voltage at open output: for blocks BBS102 and 103 Voltage at open output: for blocks BBS100 and 101

Output switch (OFF to ON / ON to OFF)

Rated switching frequency at maximum inrush Turn–on delay (maximum)

Voltage drop (at 2 amps)

Voltage drop (at 20 amps inrush) Minimum load (No Load disabled)

Resistive: for blocks BBS102 and BBS103 Resistive: for blocks BBS100 and BBS101 Inductive: for blocks BBS102 and BBS103 Inductive: for blocks BBS100 and BBS101

No Load enabled threshold

Maximum block output current Fusing

Output diagnostics

For ACFor DC

2 amps2 amps resistive 9 (1 amp inductive*)

25 amps (2 cycles)25 amps (10mS peak)

7 mA2 mA

13mA2 mA

65 volts40 volts

95 volts40 volts

Zerocrossing–––

Once per secondOnce per second

0.5 Hz + 1mS1mS

2.5 volts2.5 volts

10 volts10 volts

25 mA10 mA

30 mA10 mA

40 mA10 mA

100mA10 mA

50 mA50 mA

15 amps at 35 C, 7.5 amps at 60C

Internal electronic short circuit trip. 100ms(AC), 10ms (DC) long time trip

Short Circuit, Overload, No Load, Overtemp., Loss of I / O Power.Also,

for blocks BBS100 and BBS 102 only: Failed Switch

 


 


 

 

Hot Products

Description of EMERSON 01984-1137-0001 POWER SUPPLY I/O PCB BOARD MODULE Quick Details: 01984-1137...
Description of Mitsubishi​ MDS-C1-CV-220 B50756 POWER SUPPLY SERVO POWER CONVERTER 22 KW Quick ...
Description of Emerson SLS-24-120T LINEAR POWER SUPPLY SINGLE 24V 12A LINEAR PS Quick Details: SLS...
Description of SDN-20-24-100C​​ POWER SUPPLY SDN SERIES INPUT / 480 W / 20 AMP / 100-240 VAC Quick ...
Description of EMERSON 01984-0605-0001 DC POWER SUPPLY MODULE LED STATUS INDICATION Quick Details: ...
Description of 3BSE000863R1 POWER REGULATOR MODULE 310 W MAX 35 AMP 18-30 VDC INPUT 5 VDC OUTPUT ...