Shenzhen Viyork Technology Co., LTD |
Verified Suppliers
|
|
140DDM39000 New Factory Sealed Modicon DC Input Output Module
140-DDM-390-00
Quick Details:
SCHNEIDER ELECTRIC
MODICON
140DDM39000
TSX QUANTUM
INPUT / OUTPUT MODULE
24 VDC
16/8 SINK / SOURE
One Year warrabty
SPECIFICATION
Manufacturer | Schneider Electric |
Series | Modicon Quantum |
Module format | Standard |
Product or component type | Mixed discrete I/O module |
Discrete I/O number | 24 |
Discrete input number | 16 2 groups of 8 |
Discrete input logic | Sink |
Addressing requirement | 0.5 output word |
| 1 input word |
Network frequency limits | 47...63 Hz |
Discrete input voltage | 24 V DC |
Input voltage limits | <= 1 V during 10 s |
| <= 1 V during one cycle |
| 30 V |
| 56 V during 1.3 ms |
Voltage state 0 guaranteed | -3...5 V |
Voltage state 1 guaranteed | 15...30 V |
Current state 0 guaranteed | <= 0.5 mA |
Current state 1 guaranteed | >= 2 mA |
Input impedance | 2500 Ohm |
Discrete output number | 8 2 groups of 4 |
Discrete output type | Solid state |
Discrete output logic | Sink |
Discrete output voltage | 24 V |
Output voltage limits | 56 V DC during 1.3 ms |
| 19.2...30 V DC typical |
Maximum load current | <= 4 A per module |
| <= 2 A per group |
| <= 0.5 A per point |
Voltage drop | 0.4 V 0.5 A |
Absolute maximum output | 5 A during 500 µs per point |
Load inductance | 500 mH 4 Hz |
Load capacitance | <= 50 µF |
Leakage current | 0.4 mA 30 V DC |
Response time on output | <= 1 ms at state 1 to state 0 |
| <= 1 ms at state 0 to state 1 |
Protection type | Internal output protection by 5 A fuse per group |
| On input by resistor limited |
| On output by transient voltage suppression |
Associated fuse rating | 5 A per group |
Isolation between group | 500 Vrms for 1 minute |
Isolation between group and bus | 1780 Vrms for 1 minute |
Fault indication | Blown fuse on output |
| Loss of field power on output |
Power dissipation | 1.75 W + (0.36 x input point on) + (1.1 total output load current) |
Local signalling | 2 LEDs red fault detected on the output point |
| 2 LEDs red fault detected on the input point |
| 2 LEDs green output is turned on |
| 1 LED red no voltage in output and input (F) |
| 1 LED green bus communication is present (Active) |
Marking | CE |