Yong Xing Boiler Group Co.,Ltd |
|
2.8MW oil hot water boiler heating system hot water baseboard boiler prices for central heating
1. The oil hot water boiler heating system has the remarkable features of environmental protection, energy saving, safety and full-automatic operation. It is very convenient to use. In addition, due to the economic operation and government policies, gas-fired hot water boilers are more and more popular.
2. The oil hot water boiler heating system belongs to the range of atmospheric boilers and does not belong to special equipment. Therefore, the installation and use of gas hot water boilers are not subject to the technical supervision department horizontal fuel gas hot water boiler body.
oil hot water boiler heating system body
For the supervision of the door, as long as there is a gas
pipeline, a gas hot water boiler can be installed.
Attachment: The boiler defined in the "Special Equipment Safety Supervision Regulations" refers to equipment that uses various fuels, electricity or other energy sources to heat the liquid contained in the equipment to a certain parameter and externally output thermal energy. The scope is defined as a pressurized steam boiler having a volume greater than or equal to 30 L; a pressurized hot water boiler having an outlet water pressure greater than or equal to 0.1 MPa (gauge pressure) and a rated power greater than or equal to 0.1 Mw;
The fuel gas atmospheric pressure hot water boiler refers to an atmospheric water hot water boiler heated by fuel oil and gas, which belongs to the scope of a domestic boiler, and includes a vertical fuel gas hot water boiler.
Fuel atmospheric hot water boiler, gas atmospheric hot water
boiler, oil and gas dual-purpose atmospheric hot water boiler.
Their boiler body is the same, but the burners are different.
The oil hot water boiler heating system is mainly used for heating and bathing. Since it is not in the boiler category defined by the state, it is not managed by the technical supervision bureau and can save the user a lot of expenses. Because it runs at normal pressure, there is no safety hazard, so it can be installed in any Local, fuel gas and atmospheric pressure hot water boilers have developed very rapidly in recent years. Most of the units use heating and bathing.
best hot water boiler systems 0.35MW-14MW Oil Gas Fired hot water
boiler technical datasheet
Main technical parameters of CWNS oil (gas) atmospheric pressure and pressure hot water boiler | |||||||||||||||
Project model | CWNS, WNS series hot water boiler | ||||||||||||||
Rated calorific value (MW) | 0.35 | 0.7 | 1.05 | 1.4 | 2.1 | 2.8 | 3.5 | 4.2 | 5.6 | 7 | 8.4 | 10.5 | 12.6 | 14 | |
Working pressure (MPa) | Normal pressure / pressure | ||||||||||||||
Outlet water temperature (°C) | 85/115 | ||||||||||||||
Backwater temperature (°C) | 60/70 | ||||||||||||||
Boiler thermal efficiency (%) | 91—95 | ||||||||||||||
Feed water temperature (°C) | 20 | ||||||||||||||
Fuel consumption | Diesel (Kg/h) | 32 | 65.4 | 98 | 131 | 196.2 | 261.6 | 327 | 392.4 | 523.2 | 654 | 784.8 | 981 | 1177 | 1310 |
Heavy oil (Kg/h) | 34 | 69.5 | 105 | 139 | 208.5 | 278 | 347.5 | 417 | 556 | 695 | 864 | 1042.5 | 1251 | 1390 | |
Natural gas (m3/h) | 39.5 | 79.3 | 119 | 159 | 237.9 | 317.2 | 396.5 | 475.8 | 644 | 793 | 951.6 | 1189.5 | 1427.4 | 1586 | |
Liquefied gas (m3/h) | 14.2 | 29 | 43.5 | 58 | 87 | 116 | 145 | 174 | 232 | 290 | 348 | 435 | 522 | 580 | |
City gas (m3/h) | 84 | 168.5 | 253 | 337 | 505.5 | 674 | 842.5 | 1011 | 1348 | 1685 | 2022 | 2527.5 | 3033 | 3370 | |
Boiler transportation | Length (mm) | 2800 | 3500 | 4100 | 4500 | 4700 | 4550 | 5700 | 6300 | 7000 | 7200 | 7840 | 8100 | 8230 | 8250 |
Width (mm) | 1600 | 1600 | 1900 | 2000 | 2110 | 2210 | 2500 | 2600 | 2700 | 2800 | 2860 | 3100 | 3100 | 3400 | |
High (mm) | 2000 | 2100 | 2310 | 2360 | 2470 | 2580 | 2800 | 2900 | 3200 | 3300 | 3300 | 3400 | 3400 | 3550 | |
Total power consumption (KW) | 2.3 | 6.7 | 11 | 13.5 | 19 | 21 | 23.5 | 26 | 37 | 37 | 42 | 45 | 52 | 52 | |
Chimney diameter (mm) | 250 | 350 | 430 | 450 | 450 | 550 | 650 | 650 | 650 | 800 | 800 | 900 | 1200 | 1200 | |
Shipping weight (T) | 3.2 | 4.7 | 4.8 | 5.4 | 8 | 9.78 | 13.4 | 15.4 | 17.4 | 17.4 | 23.8 | 30 | 31.6 | 34.5 | |
Heating area (m2) | 3000 | 6000 | 900 0 | 1200 0 | 1800 0 | 2400 0 | 3000 0 | 3600 0 | 4800 0 | 6000 0 | 7200 0 | 900 00 | 1080 00 | 1200 00 | |
Water supply capacity (t) | 7 | 15 | 22 | 30 | 45 | 60 | 75 | 90 | 120 | 150 | 180 | 225 | 270 | 300 |