Wireless Conventional Addressable Fire Alarm Panel LPCB CE Certification 220VAC

City & Province beijing beijing
Categories Smoke Detector
InquireNow

Product Details

 

Wireless Conventional Fire Alarm Control Panel Addressable Fire Alarm System
Conventional Fire Alarm System
1 to 32 Zones Fire Alarm Systems Control Panel
 
OVERVIEW

 

Conventional Fire Alarm System has obtained LPCB CE certification consists.
The CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
It is the heart of the fire automatic alarm system, which can realize centralized control, can supply power to the detectors, manual call point, bell etc. One zone of the panel can match with 20 pieces fire alarm system accessories.
The conventional fire alarm panel could be customized as 1 zone, 2 zone, 4 zone,8 zone,12-32 zone.

 

 

FEATURES & BENEFITS

 

  • Meets all requirements of latest EN54 part 2 and EN54 part 4
  • Modularized design with extendable zones from 1 to 32 zones.
  • Two-level control modes by the lock.
  • 24VDC &5VDC power supply outputs.
  • FIRE & FAULT signal outputs.
  • 2 sounders outputs.
  • Each zone has 1-circuit detectors' input .
  • Each zone can be disabled by a button.
  • Manual RESET available.
  • SILENCE button to stop all outside BUZZER & SOUNDERS.
  • EVACUATE button to start manual fire alarm immediately.
  • Battery low level protection function.Lower than 21VDC, battery will be cut off automatically until the main power is on.
  • Optional GSM module to realize SMS notification in case of fire.
  • Economic, user-friendly & convenient maintenance.

 

APPLICATION


Fire alarm system is mostly used for laying fire system in office and commercial places. Any building needs fire alarm system, which can effectively prevent the occurrence of fire and give warning from the source.
 

 

SPECIFICATIONS

 

Item
1 Zone panel
2 Zone panel
4-8Zone panel
12-32 Zone panel
Model No.
CFP2166-01
CFP2166-02
CFP2166-04-08
CFP2166-12-32
Mains supply voltage
110VAC or 220VAC
Internal power supply
27.2VDC
Total output current limited
500mA @ 240VAC
500mA @ 240VAC
3A @ 240VAC
3A @ 240VAC
Batteries (Default Configuration)
12V2AH*2=24VDC in Total
End of Line device
6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
End of line resistor value
6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Dimensions(mm)
272*200*70
320*231*90
395*502*124
362*565*124
Weight (without batteries)
4kg
5kg
7kg
8kg
Weight (with batteries)
5.8kg
6.8kg
9.6kg
12.5kg

 

Hot Products

KANE458s Flue Gas Analyser with direct CO2, CO & over-range protection OVERVIEW Test domestic gas, ...
KANE 358 Flue Gas Analyser with CO sensor protection OVERVIEW KANE358 has a large 6 line display ...
KANE458s IAQ Indoor Air Quality Analyser FGA & IAQ Analyser measuring O2, CO & ambient CO2 OVERVIEW ...
KANE958 Commercial Analyser Flue Gas Analyser with direct CO O2 & CO sensor protection OVERVIEW ...
KANE988 Industrial Flue Gas Analyser With High Suction Pump FEATURES * Tests any boiler up to & over ...
KANE988+ Boiler Engine & A/C Refrigeration Analyser OVERVIEW Test any size boiler with high suction ...